background image

D900-06-00

1

I56-750-57

SS24ADAS Series Strobes and

MASS24ADAS Series Synchronized

Horn/Strobes for Fire Protective

Signaling Systems

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

General Description

The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the listed appliances. It is recommended that the
installer be familiar with these requirements, with local
codes, and any special requirements of the local fire au-
thority having jurisdiction.

The Multi-Alert sounder and signaling strobe are intended
to be connected to the alarm indicating circuit of a UL-
listed fire alarm control panel  and  is compatible with DC
line supervision. The electronic sounder can be connected
to either 12 or 24 VDC panels. Models SS2415ADAS,
SS241575ADAS, and combination models incorporating
these strobes, require 24 volt panels.  Panels may have full-
wave rectified, unfiltered power supplies. The strobes are
synchronized and flash at a rate of one flash per second
with continuous voltage applied. SS24ADAS, SS24ADA,
MASS24ADAS, and MASS24ADA series devices may be
combined in the same zone.

Model

Supply

Operating Current from

Operating Current from Full-Wave

Voltage

Regulated Supply

Rectified Unfiltered Supply

Range

SS2415ADAS

20-30V

106

200

5.0/7.0

125

250

5.0/7.0

SS241575ADAS

20-30V

195

350

5.0/7.0

180

395

5.0/7.0

Average

Peak

Inrush

Average

Peak

Inrush

Operating Current

Current

Operating

Current

Current

Current

(mA)

(Amps)

Current

(mA)

(Amps)

(mA)

20/30

(mArms)

20/30

Vrms

Vrms

NOTE:

In-rush current du-
ration is less than 20
m i c r o s e c o n d s
(.00002 seconds).

Table 2. Sound output and current ratings for the MA12/24D:

Sound (Hz)

Clips on

Current (mA)

Output (dBA)

UL (dBA)

Tabs

DC Regulated/

(Note 3)

Ratings

(Note 1)

FWR Unfiltered

(Note 4)

12V

24V

30V

12V

24V

12V

24V

Slow Whoop

ABC

21/40

38/56

46/72

85

92

79

85

800 Continuous

BC

15/24

28/45

35/55

87

93

79

85

800/1000 Alternating

AC

17/32

34/46

43/58

85

92

79

85

2400 Interrupted

AB

19/23

35/56

43/64

89

90

79

85

2400 Continuous

C

21/31

38/59

46/73

85

94

79

85

1200 Interrupted

B

13/19

23/33

27/41

85

91

75

82

Swept Frequency

A

17/24

34/47

43/60

85

92

79

85

Fast Warble

NONE

15/27

30/47

38/59

85

92

79

85

Table 1. SS24ADAS Series Electrical Ratings:

Note 1:

See  Figure 2 for tab clip removal & storage.

Note 2:

All models can be powered using full wave rectified unfiltered
supplies. Under no circumstances can  SS24ADAS or
MASS24ADAS series devices input voltage exceed 33 VDC or be

less than 16 VDC (18-33Vrms for full-wave rectified, unfiltered
supplies).

Note 3:

Measured at 10 feet in an anechoic chamber.

Note 4:

Measured in a UL reverberant room.

The MA12/24D sounder is suitable for outdoor applica-
tions (-35

°

 to 66

°

 C) when it is used with a WBB Weather-

proof Back Box. The signaling strobe is rated for 0

°

 to 49

°

C and is NOT suitable for outdoor use.

The UL-rated light output of the SS2415ADAS,
SS241575ADAS, MASS2415ADAS, and MASS241575ADAS
is 15 cd  (See Figure 1).

NOTE:

The light output at 0

°

 viewing angle for

SS241575ADAS and MASS241575ADAS is 75 cd.

Any one of eight sounds can be selected on the electronic
sounder, as indicated in Table 2.

NOTE:

SS24ADAS, MASS24ADAS AND MAEH24ADAS
SERIES DEVICES OPERATING IN THE SAME
ZONE WILL NOT BE SYNCHRONIZED IF ENER-
GIZED AT DIFFERENT TIMES (I.E., IF MORE
THAN ONE CONTROLLER IS CONTROLLING THE
SAME ZONE.)

Technical Manuals Online! - http://www.tech-man.com

Содержание MA12D

Страница 1: ... 27 30 47 38 59 85 92 79 85 Note 1 Total current for horn strobe combinations horn current strobe current refer to tables 1 and 2 Note 2 Sound output measured in anechoic room at 10 feet Note 3 Sound output measured in UL reverberant room Note 4 See Figure 4 for tab clip removal storage Note 5 All horn or combination strobe models can be powered using full wave rectified unfiltered supplies Under ...

Страница 2: ...ions within a room Addi tional sounders may be needed to ensure sound output level com plies with NFPA requirements WARNING Limitations Of Sounder Strobes The sounder and or strobe will not work without power The sounder strobe gets its power from the fire security panel monitoring the alarm system If power is cut off for any reason the sounder strobe will not pro vide the desired audio or visual ...

Страница 3: ... VDC VDC Figure 5 Multi Alert Sounder From panel or previous device To Next Device or EOL VDC VDC Figure 6 Strobe only SS Series only A78 2467 01 From panel or previous device To Next Device or EOL VDC VDC Note Use uncoded supply only INOUT STROBE ONLY INOUT INOUT STROBE ONLY INOUT Figure 7 Multi Alert Sounder and Strobe Multi Alert Sounder and Strobe operating in tandem A78 1137 01 From panel or ...

Страница 4: ...screws C and nuts D 2 Complete field wiring See Fig 5 3 Screw plate sounder to box with screws F 1 Plaster ring should be properly mounted to electrical box with screws supplied with box 2 Screw plate to plaster ring with screw G 3 Complete field wiring See Fig 5 7 and 8 4 Screw sounder or sounder strobe to plate with screw A 5 Fill remaining holes with screw B A78 1137 08 A78 1137 20 C F F C MP F...

Страница 5: ...plies Under no circumstances can the MA12 24D input Table 1 SS12 24ADA Series electrical ratings Model Supply Voltage Range Operating Current from Regulated Supply Operating Current from Full Wave Rectified Unfiltered Supply Average Operating Current Peak Current mA 20 30V Peak Current mA 10 5V 17V Inrush Current mA in access of Peak Average Operating Current mArms Peak Current mA 20Vrms 30Vrms Pe...

Страница 6: ...ast once every three seconds meets or exceeds current Un derwriters Laboratories standard 1971 and uses an extremely reliable xe non flash tube The visual warning signal is suitable for direct viewing and must be installed within an area where it can be seen by building occu pants The strobe must not be installed in direct sunlight or areas of high light intensity over 60 foot candles where the vi...

Страница 7: ...ELECT DESIRED TONE COVER SLOT TAB A TAB B TAB C FOR STORING UNUSED CLIPS SLIDE COVER BACK TO ALIGN COVER SLOT WITH CLIP STORAGE POST SLIDE COVER FOR CLIP STORAGE USE A SMALL BLADED SCREWDRIVER TO REMOVE CLIPS TONE SELECTION TABS Figure 2 Figure 3 Multi alert sounder Figure 4 Strobe Figure 5 Multi alert sounder and strobe operating in tandem From panel or previous device To Next Device or EOL VDC V...

Страница 8: ...te to box with screw A 1 Screw sounder to plate 2 Complete field wiring 3 Screw plate sounder to box with screw F 1 Plaster ring should be properly mounted to electrical box with screws supplied with box 2 Screw plate to plaster ring with screw G 3 Complete field wiring 4 Screw sounder strobe to plate with screw A 5 Fill remaining holes with screw B B A A B Signal Strobe Standard Backbox TOP MA 12...

Страница 9: ...h current du ration is less than 20 m i c r o s e c o n d s 00002 seconds Table 2 Sound output and current ratings for the MA12 24D Sound Hz Clips on Current mA Output dBA UL dBA Tabs DC Regulated Note 3 Ratings Note 1 FWR Unfiltered Note 4 12V 24V 30V 12V 24V 12V 24V Slow Whoop ABC 21 40 38 56 46 72 85 92 79 85 800 Continuous BC 15 24 28 45 35 55 87 93 79 85 800 1000 Alternating AC 17 32 34 46 43...

Страница 10: ...ambient noise at all locations within a room Additional sounders may be needed to ensure sound output level complies with NFPA requirements The Sounder and or Strobe will not work without power The sounder strobe gets its power from the fire security panel monitoring the alarm system If power is cut off for any reason the sounder strobe will not pro vide the desired audio or visual warning The Sou...

Страница 11: ...STORING UNUSED CLIPS SLIDE COVER BACK TO ALIGN COVER SLOT WITH CLIP STORAGE POST SLIDE COVER FOR CLIP STORAGE USE A SMALL BLADED SCREWDRIVER TO REMOVE CLIPS TONE SELECTION TABS Figure 2 Figure 3 Multi alert sounder Figure 4 Multi alert sounder and strobe operating in tandem Figure 5 Strobe From panel or previous device To Next Device or EOL VDC VDC VDC VDC STROBE SOUNDER INOUT STROBE ONLY INOUT IN...

Страница 12: ...137 11 1 Complete field wiring 2 Screw plate sounder to Box with screw F A78 1137 08 C F F C MP F MA 12 24D D D BB D A78 2515 00 A78 2514 00 Figure 9 Strobe surface mount 1 Complete field wiring 2 Screw sounder strobe to box with screw A 3 Fill remaining screw holes with screw B Figure 10 Sounder strobe surface mount MA 12 24D A B B A Signal Strobe Standard Backbox 1 Complete field wiring 2 Screw ...

Страница 13: ...ge Current from from Rectified Current 100 Viewing Regulated Supply Unfiltered Supply Angle see Fig 3 VDC mA mA RMS mA Candela SS12LO 12 17 50 80 550 1 5 SS24LOA 22 5 30 22 35o C SS12M 12 17 180 300 440 15 SS24MA 22 5 30 5 9 35o C SS24LO 22 5 30 25 45 225 1 5 22 35o C SS24M 22 5 30 75 125 450 15 5 9 35o C Table 2 Sound output and current ratings for the MA12 24EH Table 1 SS12 24 electrical and lig...

Страница 14: ...must conform to appropriate agency re quirements including but not limited to the following NFPA 72 NEC ART 760 ET AL CAN ULC S524 CEC PART 1 SEC 32 ULC models have suffix A CAUTION The rated output of the sounder is specified at 10 feet It should not be assumed that the output will meet the NFPA requirement of 15 dB over ambient noise at all locations within a room Addi tional sounders may be nee...

Страница 15: ...t Device or EOL VDC VDC Figure 5 Multi alert sounder From panel or previous device To Next Device or EOL VDC VDC Figure 6 Strobe only SS series only From panel or previous device To Next Device or EOL VDC VDC Note Use uncoded supply only INOUT STROBE ONLY INOUT INOUT STROBE ONLY INOUT Figure 7 Multi alert sounder and strobe operating in tandem From panel or previous device To Next Device or EOL VD...

Страница 16: ...upplied with box 2 Screw plate to plaster ring with screw G 3 Complete field wiring See Fig 5 7 and 8 4 Screw sounder or sounder strobe to plate with screw A 5 Fill remaining holes with screw B A78 1137 08E A78 1137 20E C F F C MP F MA 12 24EH D D BB D 1 Screw plate to box with screw E 2 Complete field wiring See Fig 5 7 and 8 3 Screw sounder or sounder strobe to plate with screw A 4 Fill remainin...

Страница 17: ...nder can be connected to either 12 or 24 VDC pan Model Supply Voltage Range Operating Current from Regulated Supply Operating Current from Full Wave Rectified Unfiltered Supply Average Operating Current Peak Current mA 20 30V Peak Current mA 10 5V 17V Inrush Current mA in access of Peak Average Operating Current mArms Peak Current mA 20Vrms 30Vrms Peak Current mA 10 5Vrms 17Vrms Inrush Current Amp...

Страница 18: ...1 and uses an extremely reliable xe non flash tube The visual warning signal is suitable for direct viewing and must be installed within an area where it can be seen by building occu pants The strobe must not be installed in direct sunlight or areas of high light intensity over 60 foot candles where the visual flash might be disre garded or not seen The strobe may not be seen by the visually im pa...

Страница 19: ...E SELECTION TABS Figure 3 INOUT STROBE ONLY INOUT INOUT STROBE ONLY INOUT From panel or previous device To Next Device or EOL VDC VDC Figure 4 Multi alert sounder From panel or previous device To Next Device or EOL VDC VDC Note Use uncoded supply only INOUT STROBE ONLY INOUT INOUT STROBE ONLY INOUT Figure 5 Multi alert sounder and strobe operating in tandem From panel or previous device To Next De...

Страница 20: ...ate sounder to box with screw F C F F C MP F MA 12 24EH D D BB D A78 1137 08E 1 Plaster ring should be properly mounted to electrical box with screws supplied with box 2 Screw plate to plaster ring with screw G 3 Complete field wiring See Fig 4 5 and 6 4 Screw sounder strobe to plate with screw A and fill remaining holes with screw B A B B G G MA 12 24EH MP SF Plaster Ring Standard Backbox A A78 1...

Страница 21: ...Vrms Vrms NOTE In rush current du ration is less than 20 m i c r o s e c o n d s 00002 seconds Table 2 Sound output and current ratings for the MA12 24EH Sound Hz Clips on Current mA Output dBA UL dBA Tabs DC Regulated Note 3 Ratings Note 1 FWR Unfiltered Note 4 12V 24V 30V 12V 24V 12V 24V Fast Whoop ABC 21 40 38 56 46 72 85 92 79 85 800 Continuous BC 15 24 28 45 35 55 87 93 79 85 800 1000 Alterna...

Страница 22: ...ambient noise at all locations within a room Additional sounders may be needed to ensure sound output level complies with NFPA requirements The Sounder and or Strobe will not work without power The sounder strobe gets its power from the fire security panel monitoring the alarm system If power is cut off for any reason the sounder strobe will not pro vide the desired audio or visual warning The Sou...

Страница 23: ... STORING UNUSED CLIPS SLIDE COVER BACK TO ALIGN COVER SLOT WITH CLIP STORAGE POST SLIDE COVER FOR CLIP STORAGE USE A SMALL BLADED SCREWDRIVER TO REMOVE CLIPS TONE SELECTION TABS Figure 2 Figure 3 Multi alert sounder Figure 4 Multi alert sounder and strobe operating in tandem Figure 5 Strobe From panel or previous device To Next Device or EOL VDC VDC VDC VDC STROBE SOUNDER INOUT STROBE ONLY INOUT I...

Страница 24: ...78 1137 31 1 Complete field wiring 2 Screw plate sounder to box with screw F A78 1137 30 C F F C MP F MA12 24EH D D BB D A78 2515 03 A78 2514 00 Figure 9 Strobe surface mount 1 Complete field wiring 2 Screw sounder strobe to box with screw A 3 Fill remaining screw holes with screw B Figure 10 Sounder strobe surface mount MA12 24EH A B B A Signal Strobe Standard Backbox 1 Complete field wiring 2 Sc...

Отзывы: