[10] VeRification of opeRation

[10.1] poweR the Unit

Apply  12VDC  or  24  VDC  to  terminals  marked  as  (+)  and  (–)IN,  see  Figure  6, 
and electrical specs for details.

[10.2] peRfoRM DetectoR check

VERIFY  STANDBY  per  Section  9  on  page  4.    The  use  of  a  remote  accessory  is 
recommended.

10.2.1 coVeR taMpeR

Removal  of  the  cover  on  the  sensor  side  of  the  housing  will  result  in  a  trouble 
condition.  The  unit  with  cover  removed  will  remain  powered  while  any  units 
between this unit and the eol resistor will loose power.

[10.3] DUct SMoke DetectoR teSt anD 

Maintenance pRoceDUReS

Test  and  maintain  duct  smoke  detectors  in  accordance  with  local  regulations 
and  codes  of  practice.  The  tests  contained  in  this  manual  were  devised  to  as-
sist maintenance personnel in verification of proper detector operation. 
Before  conducting  these  tests,  notify  the  proper  authorities  that  the  smoke 
detection system will be temporarily out of service. Disable the zone or system 
under test to prevent unwanted alarms.

[10.4] VeRify aiRfLow teSt peR Section 7 haS Been peR-

foRMeD.

[10.4.1] SMoke entRy USing aeRoSoL SMoke

This  test  is  intended  for  low-flow  systems  <2.54  m/sec.  If  the  air  speed  is 
greater  than  2.54  m/sec,  use  a  conventional  manometer  to  measure  differen-
tial pressure between the sampling tubes, as described in 7.1.
Drill  a  .63  cm  hole  91.4  cm  upstream  from  the  duct  smoke  detector.  With  the 
air  handler  on,  measure  the  air  velocity  with  an  anemometer.  Air  speed  must 
be  at  least  1.5  m/sec.  Spray  aerosol  smoke  into  the  duct  through  the  .63  cm 
hole  for  five  seconds.  Wait  two  minutes  for  the  duct  smoke  detector  to  alarm. 
If  the  duct  smoke  detector  alarms,  air  is  flowing  through  the  detector.  Remove 
the  duct  smoke  detector  cover  and  blow  out  the  residual  aerosol  smoke  from 
the chamber and reset the duct smoke detector. Use duct tape to seal the aero-
sol smoke entry hole.

CAUTION

Canned  aerosol  simulated  smoke  (canned  smoke  agent)  formulas  will  vary 
by  manufacturer.    Misuse  or  overuse  to  these  products  may  have  long  term 
adverse effects on the smoke detector.  Consult the canned smoke agent man-
ufacturer’s  published  instructions  for  any  further  warnings  or  caution  state-
ments.

[10.5] inStaLL the coVeR

Install  the  covers  making  sure  that  the  cover  fits  into  the  base  groove. Tighten 
the seven screws that are captured in the covers.
NOTE:  Verify  sensor  cover  gasket  is  properly  seated  on  cover  prior  to  cover 
installation

[11] DetectoR cLeaning pRoceDUReS

Notify  the  proper  authorities  that  the  smoke  detector  system  is  undergoing 
maintenance,  and  that  the  system  will  temporarily  be  out  of  service.  Disable 
the  zone  or  system  undergoing  maintenance  to  prevent  unwanted  alarms  and 
possible dispatch of the fire department.

[11.1] DetectoR SenSoR

1. 

Remove the sensor to be cleaned from the system.

2. 

 Refer to the relevant detector installation manual for cleaning instructions.

3. 

Re-install the detector

[11.2] ReinStaLLation

1. 

Reinstall the detector in its housing.

2. 

Restore system power. 

3. 

Perform Detector Check, Section [10.2].

4. 

 Notify  the  proper  authorities  testing  has  been  completed  and  the  smoke 
detector system is back in operation.

[12] SenSoR RepLaceMent

1. 

Remove the sensor head by rotating counterclockwise.

2. 

Pull gently to remove it. 

3. 

 To  replace  the  sensor  head,  align  the  mounting  features  and  rotate  clock-
wise into place.

[13] optionaL acceSSoRieS

The D2E duct smoke detector can be used with the RA400Z or RA100Z.

figURe 8. wiRing DiagRaMS foR optionaL acceSSoRieS:

RA (+) 

 (–)IN 

(+)

(–)

RED

RA400Z/RA100Z 

(OPTIONAL) 

REMOTE (LED)

ANNUNCIA TO R

D2E

DUCT  DETECTO R

H0611-06

SS-300-020 

I56-3536-003R

HO636-00

figURe 7. poweR BoaRD with ReMoVaBLe caRD:

Содержание Innovair Flex D2E

Страница 1: ...g in a building s regular fire detection system This device will not operate without electrical power Fire situations may cause an interruption of power The system safeguards should be discussed with your local fire protection specialist This device will not sense smoke unless the ventilation system is operating and the cover is installed For this detector to function properly it MUST be installed...

Страница 2: ...e 2 REMOVE SCREW AND PIVOT DETECTOR AS SHOWN BELOW REPLACE SCREW TO SECURE DETECTOR IN PLACE H0550 00 5 3 Drill the Mounting Holes Remove the paper backing from the mounting template supplied Affix the tem plate to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct 5 3 1 For rectangular side by side mounting configuration Center punch at 4 target cent...

Страница 3: ...two sam pling tubes The differential pressure should measure at least 25 mm of water and no more than 28 2 mm of water Because most commercially available manometers cannot accurately measure very low pressure differentials ap plications with less than 2 54 m sec of duct air speed may require one of the following 1 the use of a current sourcing pressure transmitter per Section 7 2 or 2 the use of ...

Страница 4: ...lor coded to prevent wiring mistakes Improper connections can prevent a system from responding properly in the event of a fire For signal wiring the wiring between interconnected detectors or from detec tors to auxiliary devices it is recommended that single conductor wire be no smaller than 18 gauge The duct smoke detector terminals accommodate wire sizes up to 12gauge Smoke detectors and alarm s...

Страница 5: ...low out the residual aerosol smoke from the chamber and reset the duct smoke detector Use duct tape to seal the aero sol smoke entry hole CAUTION Canned aerosol simulated smoke canned smoke agent formulas will vary by manufacturer Misuse or overuse to these products may have long term adverse effects on the smoke detector Consult the canned smoke agent man ufacturer s published instructions for an...

Страница 6: ...thorization number send defective units to Returns Department RA __________ Pittway Tecnologica Srl Via Caboto 19 3 34147Trieste Italy Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufactu...

Отзывы: