tor housing, and the LOW side of the transmitter to the exhaust tube of the 
duct smoke detector housing. Measure and record the voltage drop across the 
1000

Ω

 resistor (measurement 2). Subtract the voltage recorded in measure-

ment 1 from the voltage recorded in measurement 2. If the difference is greater 
than 0.15 volts, there is enough air flow through the duct smoke detector for 
proper operation.

fIgURE 5. PROCEDURE fOR VERIfyINg AIR fLOw:

HIGH

LOW

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

TO SAMPLING TUBE

TO EXHAUST TUBE

DIFFERENTIAL 

PRESSURE 

TRANSMITTER 

MODEL #607-01

15 TO 36 

VDC SUPPLY

1000 OHM 5%

1 WATT RESISTOR

VOLT METER FLUKE 

MODEL 87 OR 

EQUIVALENT

+

H0163-01

[8] fIELD wIRINg; INSTALLATION gUIDELINES

All wiring must be installed in compliance with the National Electrical Code 
and the local codes having jurisdiction. Proper wire gauges should be used. 
The conductors used to connect smoke detectors to control panels and acces-
sory devices should be color-coded to prevent wiring mistakes. Improper con-
nections can prevent a system from responding properly in the event of a fire.

For signal wiring, (the wiring between interconnected detectors or from detec-
tors to auxiliary devices), it is recommended that single conductor wire be no 
smaller than 18 gauge. The duct smoke detector terminals accommodate wire 
sizes up to 12 gauge.

Smoke detectors and alarm system control panels have specifications for al-
lowable loop resistance. Consult the control panel manufacturer’s specifica-
tions for the total loop resistance allowed for the particular model control 
panel being used before wiring the detector loop. 

[8.1] wIRINg INSTRUCTIONS

The D2 detectors are designed for easy wiring. The housing provides a ter-
minal strip with clamping plates. Wiring connections are made by sliding the 
bare end of the wire under the plate, and tightening the clamping plate screw. 
See 

Figure 6

 below for system wiring.

[9] DETECTOR STATUS INDICATION

Detector status is indicated by the LED’s on the sensor.  Refer to table below 
for more details.

SS-300-014 

4 I56-3050-004R

Status

Sensor LEDs Designation

Description/Trouble Shooting

Sensor 

Initialization

Alternating red blink every 

5 seconds

At power up the sensor will take approximately 30 seconds to inialize. Also occurs when 

sensor is removed during a seven minute delay. 

Standby

Simultaneous red blink every 

5 seconds

The LED on the sensor should flash approximately every 5 seconds. If the sensor LEDs 

are not illuminated, then the detector lacks power (check wiring, panel or power supply).

Maintenance

Not illuminated

The sensor is outside of its sensitivity limits and shall be cleaned or replaced. 

See Section 10.3 for details.

Alarm

Solid Red

The unit is in alarm.

TABLE 2. DETECTOR STATUS INDICATIONS

(+) IN

(+) OUT

(+)

(+)

(–)

(–)

1ST DETECTOR

IN LOOP D2

(–)

RA400Z (OPTIONAL)

REMOTE ALARM LED

4.4 VDC NOM.

IN ALARM

(+) IN

(+) OUT

(+)

(+)

(–)

LAST DETECTOR

IN LOOP D2

(–)

RA400Z (OPTIONAL)

REMOTE ALARM LED

4.4 VDC NOM.

IN ALARM

E

O

L

R

STYLE D OPTIONAL WIRING

UL/FM LISTED

COMPATIBLE 2-WIRE

CONTROL PANEL

ALARM

INITIATION

LOOP

(+)

(–)

EOL RESISTOR

SPECIFIED

BY PANEL

MANUFACTURER

RA

RA

RA

RA

(–)

~~

~~

(+) IN

(+) OUT

(+)

(+)

(–)

(–)

2ND DETECTOR

IN LOOP D2

(–)

RA400Z (OPTIONAL)

REMOTE ALARM LED

4.4 VDC NOM.

IN ALARM

RA

RA

~~

~~

fIgURE 6. SySTEM wIRINg DIAgRAM fOR D2 2-wIRE DUCT SMOkE DETECTORS 
(DETECTORS POwERED fROM INITIATINg CIRCUIT):

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

H0564-01

Содержание Innovair flex D2

Страница 1: ...n ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct 2 General Description Smoke introduced into the air duct system will be distributed throughout the entire building Smoke detectors designed for use in air duct systems are used to sense the presence of smoke...

Страница 2: ...EW AND PIVOT DETECTOR AS SHOWN BELOW REPLACE SCREW TO SECURE DETECTOR IN PLACE H0550 00 5 3 Drill the Mounting Holes Remove the paper backing from the mounting template supplied Affix the tem plate to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct 5 3 1 For rectangular side by side mounting configuration Center punch at 4 target centers 2 A for sa...

Страница 3: ... open to ambient air measure and record the voltage drop across the 1000Ω resistor measurement 1 4 00 volts is typical Using flexible tubing and rubber stoppers connect the HIGH side of the transmitter to the sampling tube of the duct smoke detec 6 Sampling Tube Installation 6 1 Sampling Tube Selection The sampling tube must be purchased separately Order the correct length as specified in Table 1 ...

Страница 4: ...e detector loop 8 1 Wiring Instructions The D2 detectors are designed for easy wiring The housing provides a ter minal strip with clamping plates Wiring connections are made by sliding the bare end of the wire under the plate and tightening the clamping plate screw See Figure 6 below for system wiring 9 DETECTOR STATUS INDICATION Detector status is indicated by the LED s on the sensor Refer to tab...

Страница 5: ...r With the air handler on measure the air velocity with an anemometer Air speed must be at least 100 FPM Spray aerosol smoke into the duct through the 1 4 inch hole for five seconds Wait two minutes for the duct smoke detector to alarm If the duct smoke detector alarms air is flowing through the detector Remove the duct smoke detector cover and blow out the residual aerosol smoke from the chamber ...

Страница 6: ...___ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any consequential or incidental damages for brea...

Отзывы: