[5] DETECTOR INSTALLATION
[5.1] VERIfy DUCT AIR fLOw DIRECTION AND VELOCITy

Model D2 detectors are designed to be used in air handling systems having air 
velocities of 100 to 4000 feet per minute. Duct widths from 6 inches to 12 feet 
can be accommodated. Be sure to check engineering specifications to ensure 
that the air velocity in the duct falls within these parameters. If necessary, use 
a velocity meter (anemometer) to check the air velocity in the duct.

[5.2] DETERMINE MOUNTINg LOCATION 
AND CONfIgURATION

On ducts wider than 18 inches it is recommended that the detector be 
mounted downstream of a bend, obstruction in the duct, or the supply or 
return air inlet. 

Exception: Installation of duct detectors can be on or within a commercial 
packaged rooftop heating and air-conditioning system, fire/smoke dampers 
and economizers. They may be mounted in either the supply and/or return air 
section as determined by local code.

Once a suitable location is selected, determine if the detector is to be mounted 
in a side-by-side “rectangular” configuration or a top-over-bottom “square” 
configuration as shown in 

Figure 2

. If mounting in the square configuration, 

remove the rear attachment screw, rotate the unit at hinge, and replace the 
screw into the new attachment hole as shown in 

Figure 2

. Do NOT remove 

the hinge screw during this process. Final installation approval shall be based 
upon passing section 10.4.2 and 10.4.4 tests.

fIgURE 2:

REMOVE SCREW AND PIVOT

DETECTOR AS SHOWN BELOW.

REPLACE SCREW

TO SECURE DETECTOR

IN PLACE.

H0550-00

[5.3] DRILL ThE MOUNTINg hOLES

Remove the paper backing from the mounting template supplied. Affix the tem-
plate to the duct at the desired mounting location. Make sure the template lies 
flat and smooth on the duct. 

[5.3.1] fOR RECTANgULAR SIDE-By-SIDE MOUNTINg CONfIgURATION:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “B” for 
the rectangular configuration mounting tabs as shown on mounting template. 
Drill pilot holes at target “A” centers and cut two 1.375 inch diameter holes us-
ing a 1

3

/

inch hole saw or punch. Drill .156 inch diameter holes using a 

5

/

32

” 

inch drill at target “B” centers.

[5.3.2] fOR SqUARE TOP-OVER-BOTTOM MOUNTINg CONfIgURATION:

Center punch at (4) target centers: (2) “A” for sampling tubes and (2) “C” for 
the square configuration mounting tabs as shown on mounting template. Drill 
pilot holes at target “A” centers and cut two 1.375 inch diameter holes using a 
1

3

/

8

” inch hole saw or punch. Drill .156 inch diameter holes using a 

5

/

32

 inch 

drill at target “C” centers. If desired, drill an additional .156 inch hole at the 
location of one of the mounting tabs on the lower housing.

[5.4] SECURE ThE DUCT DETECTOR TO ThE DUCT

Use two (rectangular configuration) or three (square configuration) of the pro-
vided sheet metal screws to screw the duct detector to the duct.

CAUTION: Do not overtighten the screws.

SS-300-014 

2 I56-3050-004R

[4] fIgURE 1. ExPLODED VIEw Of DUCT SMOkE DETECTOR COMPONENTS:

MAGNET TEST LOCATION

SENSOR MODULE COVER

TERMINAL HOUSING 

MODULE COVER

SAMPLING TUBE

EXHAUST TUBE

SENSOR HEAD

WIRING TERMINALS

(sold seperately)

H0574-05

Содержание Innovair flex D2

Страница 1: ...n ALL electrical and environmental specifications listed in this manual Failure to comply with these requirements may prevent the detector from activating when smoke is present in the air duct 2 General Description Smoke introduced into the air duct system will be distributed throughout the entire building Smoke detectors designed for use in air duct systems are used to sense the presence of smoke...

Страница 2: ...EW AND PIVOT DETECTOR AS SHOWN BELOW REPLACE SCREW TO SECURE DETECTOR IN PLACE H0550 00 5 3 Drill the Mounting Holes Remove the paper backing from the mounting template supplied Affix the tem plate to the duct at the desired mounting location Make sure the template lies flat and smooth on the duct 5 3 1 For rectangular side by side mounting configuration Center punch at 4 target centers 2 A for sa...

Страница 3: ... open to ambient air measure and record the voltage drop across the 1000Ω resistor measurement 1 4 00 volts is typical Using flexible tubing and rubber stoppers connect the HIGH side of the transmitter to the sampling tube of the duct smoke detec 6 Sampling Tube Installation 6 1 Sampling Tube Selection The sampling tube must be purchased separately Order the correct length as specified in Table 1 ...

Страница 4: ...e detector loop 8 1 Wiring Instructions The D2 detectors are designed for easy wiring The housing provides a ter minal strip with clamping plates Wiring connections are made by sliding the bare end of the wire under the plate and tightening the clamping plate screw See Figure 6 below for system wiring 9 DETECTOR STATUS INDICATION Detector status is indicated by the LED s on the sensor Refer to tab...

Страница 5: ...r With the air handler on measure the air velocity with an anemometer Air speed must be at least 100 FPM Spray aerosol smoke into the duct through the 1 4 inch hole for five seconds Wait two minutes for the duct smoke detector to alarm If the duct smoke detector alarms air is flowing through the detector Remove the duct smoke detector cover and blow out the residual aerosol smoke from the chamber ...

Страница 6: ...___ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any consequential or incidental damages for brea...