background image

[5.2.2] Alarm Tests
[5.2.2.1] M02-04-01 Magnet Test

1. Place  the  painted  surface  of  the  magnet  into  the  Test 

locator molded into the side of the housing (see Figure 
10). 

2. The  red  alarm  LEDs  on  the  detector  should  latch  on, 

as  should  any  accessories  (PA400,  RA400Z,  RTS451, 
APA451).  Verify  auxiliary  functions  (such  as  fan  shut-
down) and system control panel alarm status.

3. Place the painted surface of the magnet into the Reset 

locator molded into the side of the housing (see Figure 
10). This should clear the latched alarm condition at the 
detector. If a system control panel is used, the panel may 
also require resetting.

[5.2.2.2] RTS451/RTS451KEY Remote Test Station

The RTS451/RTS451KEY Remote Test Station facilitates test 
of  the  alarm  capability  of  the  duct  detector  as  indicated 
in  the  RTS451/RTS451KEY  manual.  The  DH400ACDCIHT 
duct  detector  can  be  reset  by  the  RTS451/RTS451KEY.  If 
a  system  control  panel  is  used,  the  panel  itself  may  also 
require resetting.
  
To  install  the  RTS451/RTS451KEY,  connect  the  device  as 
shown in Figure 8; wire runs must be limited to 25 ohms or 
less per interconnecting wire. Place the coil in the detector 
housing with the arrow facing up and pointing toward the 
detector as in Figure 12. Attach the coil leads to the hous-
ing  terminals  as  shown;  polarity  is  not  important.  Firmly 
screw the bracket in place over the test coil. 
 

Figure 10. Testing detector alarm:

Figure 11. Detector head removal:

TEST

LOCATOR

TEST

MAGNET

PAINTED SIDE

TOWARD HOUSING

DUCT

HOUSING

DETECTOR

HEAD

RESET 

LOCATOR

TWIST

COUNTERCLOCKWISE

TO REMOVE

DUCT

HOUSING

TWIST

CLOCKWISE

TO INSTALL

DETECTOR

HEAD

H0243-00

H0244-00

[5.2.3] Sensitivity Tests
[5.2.3.1] MOD400R Sensitivity Test 

After verification of alarm capability, use the MOD400R test 
module  with  a  voltmeter  to  check  detector  sensitivity  as 
described in the test module’s manual. The housing cover 
must be removed to perform this test.

If  test  module  readings  indicate  that  the  detector  head  is 
outside of the acceptable range that is printed on the back 
of  the  detector  head,  the  detector  head  requires  cleaning 
per Section [7].

[6] Detector Cleaning Procedures

Notify the proper authorities that the smoke detector sys-
tem  is  undergoing  maintenance,  and  that  the  system  will 
be temporarily out of service. Disable the zone or system 
undergoing maintenance to prevent unwanted alarms and 
possible dispatch of the fire department.

[6.1] Air Filters

1. Turn off power to the system.
2. Remove and inspect the sampling tube filters.
3. If the filters are heavily coated with dirt, replace them 

with  new  filters.  If  they  are  not  heavily  coated,  use  a 
vacuum  cleaner  or  compressed  air  nozzle  to  remove 
dust, then reinstall the filters. 

[6.2] Ion Heads 

1. Remove the detector cover by depressing the three lock 

prongs  on  the  top  of  the  cover  and  rotating  the  cover 
counterclockwise to remove the cover and screen assem-
bly (see Figure 14). The optional CRT400 Cover Removal 
Tool makes cover removal easier.

2. Carefully pull the screen out of the cover.

D400-64-00                                                                                              9                                                                                              I56-991-08R

Содержание DH400ACDCIHT

Страница 1: ...Fig 11 Detector Head Removal 9 Fig 12 RTS451 RTS451KEY Test Coil Installation 10 Fig 13 Ion Head Exploded View 10 1 General Description An HVAC system supplies conditioned air to virtually every area of a building Smoke introduced into this air duct sys tem will be distributed to the entire building Smoke detec tors designed for use in air duct systems are used to sense the presence of smoke in th...

Страница 2: ...4 7 Perform detector check 5 4 8 Install the cover 8 4 1 Verify Duct Air Flow Direction And Velocity Model DH400ACDCIHT detectors are designed to be used in air handling systems having air velocities of 500 to 4000 feet per minute Be sure to check engineering specifications to ensure that the air velocity in the duct falls within these parameters If necessary use a velocity meter to check the air ...

Страница 3: ...o the sampling tube holes as indicated in Figure 4 Table 1 Inlet tubes required for different duct widths Outside Duct Width Inlet Tube Required 1 to 2 ft ST 1 5 2 to 4 ft ST 3 4 to 8 ft ST 5 8 to 12 ft ST 10 4 4 1 Installation For Ducts Less Than 8 Feet Wide 1 If the tube is longer than the width of the air duct drill a 3 4 inch hole in the duct directly opposite the hole already cut for the inle...

Страница 4: ...TION FLANGE H0108 02 AIR FLOW DIRECTION DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DETECTOR HOUSING SAMPLING TUBE EXHAUST TUBE AIR FLOW DIRECTION EXHAUST TUBE SAMPLING TUBE SAMPLING TUBE EXHAUST TUBE DETECTOR HOUSING AIR FLOW DIRECTION DETECTOR HOUSING A B C D HORIZONTAL MOUNTING OF HOUSING VERTICAL MOUNTING OF HOUSING Figure 5 Tube mounting configurations wi...

Страница 5: ...l strip with clamp ing plates Wiring connections are made by stripping about 3 8 inch of insulation from the end of the wire sliding the bare end under the plate and tightening the clamping plate screw The detector may be wired for interconnection to UL listed control panels or for stand alone service per NFPA 90A Refer to the wiring diagrams of Figures 6 7 and 8 to select the appropriate circuit ...

Страница 6: ... IN STANDBY CONTACTS CLOSE IN ALARM 8 9 ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY CONTACTS CLOSE IN ALARM ALARM INITIATION LOOP UL LISTED CONTROL PANEL FIRST DETECTOR IN THE LOOP DH400ACDCIHT LAST DETECTOR IN THE LOOP DH400ACDCIHT EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY...

Страница 7: ...S REFER TO MANUFACTURER S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER TROUBLE CONTACT RATING 0 3A 32 VAC DC POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR ALARM AUXILIARY CONTACT RATINGS 10A 30 VDC RESISTIVE 10A 250 VAC 500mA MINIMUM 24 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS ALARM I...

Страница 8: ...ke behavior even when they are up to 90 clogged Quarterly visual inspec tion is usually often enough to determine if filters should be replace because only a high percentage of contamina tion affects duct detector performance Figure 9 Wiring diagrams for optional accessories see Figure 7 for APA451 wiring diagram ALARM SIGNAL AUX POWER 5 6 DUCT DETECTOR DH400ACDC PA400 OPTIONAL AUDIBLE ALERT ALARM...

Страница 9: ...head removal TEST LOCATOR TEST MAGNET PAINTED SIDE TOWARD HOUSING DUCT HOUSING DETECTOR HEAD RESET LOCATOR TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TWIST CLOCKWISE TO INSTALL DETECTOR HEAD H0243 00 H0244 00 5 2 3 Sensitivity Tests 5 2 3 1 MOD400R Sensitivity Test After verification of alarm capability use the MOD400R test module with a voltmeter to check detector sensitivity as described in t...

Страница 10: ...H400ACDCIHT Air Duct Smoke Detector Specifications Description HVAC air duct mounted ionization smoke detector for separately powered systems or stand alone systems Auxiliary alarm relay contacts provide fan contactor shutdown to prevent HVAC circulation of smoke Environmental Limits Operating Temperature 32 to 158 F 0 to 70 C Storage Temperature 22 to 158 F 30 to 70 C Humidity 10 to 93 R H non co...

Страница 11: ...ements This enclosure provides protection in outdoor installations against rain sleet and snow or in indoor installations against dripping water NOTE The DH400 OE 1 is designed solely for the use with System Sensor model DH400ACDCIHT high temperature duct smoke detector Preparation Locate the two adhesive backed gaskets packaged with the enclosure NOTE In order to provide effective sealing these g...

Страница 12: ... repair or replace units which are found to be defective because of damage unrea sonable use modifications or alterations occurring after the date of manu facture In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty expressed or implied whatsoever even if the loss or damage is caused by the Company s negligence or fault Some st...

Отзывы: