CAUTION

Do not use the tamper resist feature if the XR5 removal tool is to be used.

This detector base also includes an optional tamper resist feature that, when 
activated, prevents removal of the detector without the use of a tool.

To  activate  this  feature,  break  the  tab  from  the  detector  base,  as  shown  in 
Figure 3A, and install the detector. To remove the detector from the base once 
the tamper resist feature has been activated, insert a small-bladed screwdriver 
into the slot in the side of the base and press the plastic lever away from the 
detector head (see Figure 3B). This allows the detector to be rotated counter-
clockwise and removed.

NOTE: 

Head  removal  after  the  tamper  resist  feature  has  been  activated 

first requires removal of the decorative ring.

The tamper resist feature can be defeated by breaking and removing the plas-
tic lever from the base. However, this permanently defeats the tamper resist 
feature.

figUre 1. mOUnTing deTeCTOr TO BOx:

SNAP ON 

DECORATIVE 

RING

SCREWS 

(NOT SUPPLIED)

DETECTOR 

BASE

BOX

(NOT SUPPLIED)

SHORTING 

SPRING

C0503-00

firealarmresources.com

Содержание B401BR

Страница 1: ...x with or without plaster ring Min Depth 1 5 inches 4 inch octagon box Min Depth 1 5 inches 3 1 2 inch octagon box Min Depth 1 5 inches Operating Temperature Range 10 to 60 C 14 to 140 F NOTE Do not install where normal ambient temperature extends beyond 0 to 49 32 to 120 F Operating Humidity Range 10 to 93 Relative Humidity Electrical Ratings includes base and detector System Voltage 24 VDC Maxim...

Страница 2: ...s been activated insert a small bladed screwdriver into the slot in the side of the base and press the plastic lever away from the detector head see Figure 3B This allows the detector to be rotated counter clockwise and removed NOTE Head removal after the tamper resist feature has been activated first requires removal of the decorative ring The tamper resist feature can be defeated by breaking and...

Страница 3: ...detector head from base Figure 3A Activating tamperproof feature 2 WIRE CONTROL PANEL 1 2 3 4 5 REMOTE ANNUNCIATOR 1 2 3 4 5 REMOTE ANNUNCIATOR E O L OPTIONAL FAULT TOLERANT WIRING NOTE For system supervision Do not loop wire under terminals 2 3 and 5 Break wire run to ensure system supervision of connections Figure 2 Typical wiring diagram for 2 wire detector systems C0593 00 firealarmresources c...

Страница 4: ...uthorization number send defective units postage prepaid to System Sensor Please refer to insert for the Limitations of Fire Alarm Systems Three Year Limited Warranty Repair Department RA __________ 3825 Ohio Avenue St Charles IL 60174 Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be ...

Отзывы: