background image

System Sensor warrants its enclosed smoke detector base to be free from defects in ma-
terials and workmanship under normal use and service for a period of three years from 
date of manufacture. System Sensor makes no other express warranty for this smoke 
detector base. No agent, representative, dealer, or employee of the Company has the au-
thority to increase or alter the obligations or limitations of this Warranty. The Company’s 
obligation of this Warranty shall be limited to the repair or replacement of any part of 
the smoke detector base which is found to be defective in materials or workmanship 
under normal use and service during the three year period commencing with the date of 
manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) 
for a Return Authorization number, send defective units postage prepaid to: Honeywell, 

12220 Rojas Drive, Suite 700, El Paso TX 79936 USA. Please include a note describing the 
malfunction and suspected cause of failure. The Company shall not be obligated to repair 
or replace units which are found to be defective because of damage, unreasonable use, 
modifications, or alterations occurring after the date of manufacture. In no case shall the 
Company be liable for any consequential or incidental damages for breach of this or any 
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by 
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of 
incidental or consequential damages, so the above limitation or exclusion may not apply 
to you. This Warranty gives you specific legal rights, and you may also have other rights 
which vary from state to state.

Please refer to insert for the Limitations of Fire Alarm Systems

THREE-YEAR LIMITED WARRANTY

System Sensor

®

 is a registered trademark of Honeywell International, Inc.

FIGURE 5A. ACTIVATE TAMPER-RESIST FEATURE

PLASTIC LEVER

BREAK TAB AT DOTTED LINE BY 

TWISTING TOWARD CENTER OF BASE

USE SMALL-BLADED SCREWDRIVER TO PUSH 

PLASTIC LEVER IN DIRECTION OF ARROW

C0130-00

FIGURE 5B. DETECTOR REMOVAL

PLASTIC LEVER

BREAK TAB AT DOTTED LINE BY 

TWISTING TOWARD CENTER OF BASE

USE SMALL-BLADED SCREWDRIVER TO PUSH 

PLASTIC LEVER IN DIRECTION OF ARROW

C0130-00

FIGURE 6. CONNECTION TO REMOTE ANNUNCIATOR TERMINAL

STRIPPED WIRE

WIRE WITH SPADE LUG

C0116-00

TAMPER-RESIST FEATURE

NOTE: Do not use the tamper-resist feature if a removal tool will be used.

The detector base includes a tamper-resist feature that prevents removal of the 
detector without using a small screwdriver or similar tool.

To activate this feature, use needle-nose pliers to break the tab on the detector 
base as shown in Figure 5A. Then, install the detector. 

To remove the detector from the base once the tamper-resist feature has been 
activated, remove the decorative ring by rotating it in either direction and 
pulling it away from the base. Then, insert a small screwdriver into the notch, 
as indicated in Figure 5B, and press the plastic lever toward the mounting 
surface before rotating the detector counterclockwise for removal.

The tamper-resist feature can be defeated by breaking and removing the plas-
tic lever from the base. However, this prevents the feature from being used 
again.

REMOTE ANNUNCIATOR (RA100Z)

Connect the remote annunciator between terminals 1 and 3 using the spade 
lug terminal included. The spade lug terminal is connected to the base termi-
nal as shown in Figure 6.

It is not acceptable to have three stripped wires under the same wiring ter-
minal unless they are separated by a washer or equivalent means. The spade 
lug supplied with the model RA100Z is considered an equivalent means. See 
Figure 3 for proper installation.

FIGURE 3. TYPICAL WIRING DIAGRAM FOR 2-WIRE LOOP

2

3

1

2

3

3

1

2

1

(–)

(+)

+

-

UL

 LISTED COM

PA

TIBLE

CONTROL

 P

ANEL

CAUTION: DO NOT LOOP WIRE 

UNDER TERMINAL 1 OR 2.

BREAK WIRE RUN TO PROVIDE 

SUPERVISION OF CONNECTIONS.

CLASS A OPTIONAL WIRING

REMOTE 

ANNUNCIATOR

(–)
(+)

C0129-02

FIGURE 4. TERMINAL WIRE INSTALLATION

 

 

C0473-00

  

I56-6566-001 

 

 

©2017 System Sensor. 11/17/2017