background image

FIGURE 5A. ENABLING THE TAMPER-RESISTANT CAPABILITY:

PLASTIC LEVER

BREAK TAB AT DOTTED LINE BY 

TWISTING TOWARD CENTER OF BASE

USE SMALL-BLADED SCREWDRIVER TO PUSH 

PLASTIC LEVER IN DIRECTION OF ARROW

C0130-00

FIGURE 5B. REMOVING THE DETECTOR HEAD FROM THE BASE:

PLASTIC LEVER

BREAK TAB AT DOTTED LINE BY 

TWISTING TOWARD CENTER OF BASE

USE SMALL-BLADED SCREWDRIVER TO PUSH 

PLASTIC LEVER IN DIRECTION OF ARROW

C0130-00

FIGURE 6. CONNECTION TO REMOTE ANNUNCIATOR TERMINAL:

STRIPPED WIRE

WIRE WITH SPADE LUG

C0116-00

SS-450-005 

I56-1033-001 

 

 

©2011 System Sensor

System Sensor warrants its enclosed smoke detector base to be free from defects in 

materials and workmanship under normal use and service for a period of three years 

from  date  of  manufacture.  System  Sensor  makes  no  other  express  warranty  for  this 

smoke detector base. No agent, representative, dealer, or employee of the Company 

has the authority to increase or alter the obligations or limitations of this Warranty. The 

Company’s obligation of this Warranty shall be limited to the repair or replacement of any 

part of the smoke detector base which is found to be defective in materials or workman-

ship under normal use and service during the three year period commencing with the 

date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 

(736-7672)  for  a  Return Authorization  number,  send  defective  units  postage  prepaid 

to: System Sensor, Repair Department, RA #__________, 6581 Kitimat Road, Unit 6, 

Mississauga, Ontario L5N-3T5. Please include a note describing the malfunction and 

suspected cause of failure. The Company shall not be obligated to repair or replace units 

which are found to be defective because of damage, unreasonable use, modifications, 

or alterations occurring after the date of manufacture. In no case shall the Company 

be liable for any consequential or incidental damages for breach of this or any other 

Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the 

Company’s negligence or fault. Some states do not allow the exclusion or limitation of 

incidental or consequential damages, so the above limitation or exclusion may not apply 

to you. This Warranty gives you specific legal rights, and you may also have other rights 

which vary from state to state.

Please refer to insert for the Limitations of Fire Alarm Systems

2

3

1

2

3

3

1

2

1

(–)

(+)

+

-

ULC LISTED COM

PA

TIBLE

CONTRO

PA

NE

L

CAUTION: DO NOT LOOP WIRE 

UNDER TERMINAL 1 OR 2.

BREAK WIRE RUN TO PROVIDE 

SUPERVISION OF CONNECTIONS.

CLASS A OPTIONAL WIRING

REMOTE 

ANNUNCIATOR

(–)

(+)

TAMPER-RESIST FEATURE

NOTE: Do not use the tamper-resist feature if the removal tool will be used.

The detector base includes a tamper-resist feature that prevents removal of 

the detector without using a small screwdriver or similar tool.
To activate this feature, use needle-nose pliers to break the tab on the detec-

tor base as shown in Figure 5A. Then, install the detector. 
To  remove  the  detector  from  the  base  once  the  tamper-resist  feature  has 

been activated, remove the decorative ring by rotating it in either direction 

and  pulling  it  away  from  the  base.  Then,  insert  a  small  screwdriver  into 

the notch, as indicated in Figure 5B, and press the plastic lever toward the 

mounting surface before rotating the detector counterclockwise for removal. 
The  tamper-resist  feature  can  be  defeated  by  breaking  and  removing  the 

plastic lever from the base. However, this prevents the feature from being 

used again.

REMOTE ANNUNCIATOR (RA400ZA/RA100ZA)

Connect the remote annunciator between terminals 1 and 3 using the spade 

lug terminal included. The spade lug terminal is connected to the base termi-

nal as shown in Figure 6.
It is not acceptable to have three stripped wires under the same wiring termi-

nal unless they are separated by a washer or equivalent means. The spade 

lug supplied with the model RA400ZA/RA100ZA is considered an equivalent 

means. See Figure 3 for proper installation.

FIGURE 3. TYPICAL WIRING DIAGRAM FOR 2-WIRE LOOP:

FIGURE 4.:

C0129-02

C0473-00