FIGURE 5A. ENABLING THE TAMPER-RESISTANT CAPABILITY:
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARD CENTER OF BASE
USE SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC LEVER IN DIRECTION OF ARROW
C0130-00
FIGURE 5B. REMOVING THE DETECTOR HEAD FROM THE BASE:
PLASTIC LEVER
BREAK TAB AT DOTTED LINE BY
TWISTING TOWARD CENTER OF BASE
USE SMALL-BLADED SCREWDRIVER TO PUSH
PLASTIC LEVER IN DIRECTION OF ARROW
C0130-00
FIGURE 6. CONNECTION TO REMOTE ANNUNCIATOR TERMINAL:
STRIPPED WIRE
WIRE WITH SPADE LUG
C0116-00
SS-450-005
2
I56-1033-001
©2011 System Sensor
System Sensor warrants its enclosed smoke detector base to be free from defects in
materials and workmanship under normal use and service for a period of three years
from date of manufacture. System Sensor makes no other express warranty for this
smoke detector base. No agent, representative, dealer, or employee of the Company
has the authority to increase or alter the obligations or limitations of this Warranty. The
Company’s obligation of this Warranty shall be limited to the repair or replacement of any
part of the smoke detector base which is found to be defective in materials or workman-
ship under normal use and service during the three year period commencing with the
date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2
(736-7672) for a Return Authorization number, send defective units postage prepaid
to: System Sensor, Repair Department, RA #__________, 6581 Kitimat Road, Unit 6,
Mississauga, Ontario L5N-3T5. Please include a note describing the malfunction and
suspected cause of failure. The Company shall not be obligated to repair or replace units
which are found to be defective because of damage, unreasonable use, modifications,
or alterations occurring after the date of manufacture. In no case shall the Company
be liable for any consequential or incidental damages for breach of this or any other
Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the
Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
Please refer to insert for the Limitations of Fire Alarm Systems
2
3
1
2
3
3
1
2
1
(–)
(+)
+
-
ULC LISTED COM
PA
TIBLE
CONTRO
L
PA
NE
L
CAUTION: DO NOT LOOP WIRE
UNDER TERMINAL 1 OR 2.
BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTIONS.
CLASS A OPTIONAL WIRING
REMOTE
ANNUNCIATOR
(–)
(+)
TAMPER-RESIST FEATURE
NOTE: Do not use the tamper-resist feature if the removal tool will be used.
The detector base includes a tamper-resist feature that prevents removal of
the detector without using a small screwdriver or similar tool.
To activate this feature, use needle-nose pliers to break the tab on the detec-
tor base as shown in Figure 5A. Then, install the detector.
To remove the detector from the base once the tamper-resist feature has
been activated, remove the decorative ring by rotating it in either direction
and pulling it away from the base. Then, insert a small screwdriver into
the notch, as indicated in Figure 5B, and press the plastic lever toward the
mounting surface before rotating the detector counterclockwise for removal.
The tamper-resist feature can be defeated by breaking and removing the
plastic lever from the base. However, this prevents the feature from being
used again.
REMOTE ANNUNCIATOR (RA400ZA/RA100ZA)
Connect the remote annunciator between terminals 1 and 3 using the spade
lug terminal included. The spade lug terminal is connected to the base termi-
nal as shown in Figure 6.
It is not acceptable to have three stripped wires under the same wiring termi-
nal unless they are separated by a washer or equivalent means. The spade
lug supplied with the model RA400ZA/RA100ZA is considered an equivalent
means. See Figure 3 for proper installation.
FIGURE 3. TYPICAL WIRING DIAGRAM FOR 2-WIRE LOOP:
FIGURE 4.:
C0129-02
C0473-00
THREE-YEAR LIMITED WARRANTY