B210LPA Plug-in Detector Base

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5

1-800-SENSOR2, FAX: 905-812-0771

www.systemsensor.ca

BEFORE INSTALLING

Please read the System Smoke Detectors Application Guide, which provides 

detailed information on detector spacing, placement, zoning, wiring, and spe-

cial applications. Copies of this application guide are available from System 

Sensor. CAN/ULC-S524 guidelines should be observed. 

NOTICE

: This manual should be left with the owner/user of this equipment.

IMPORTANT

: The detector used with this base must be tested and main-

tained regularly following CAN/ULC-S536 requirements. The detector should 

be cleaned at least once a year.

GENERAL DESCRIPTION

The B210LPA is a plug-in detector base intended for use in an intelligent sys-

tem, with screw terminals provided for power (+ and –), and remote annunciator 

connections. Communication takes place over the power (+ and –) lines.

BASE TERMINALS

NO.    FUNCTION

  Power (–), Remote Annunciator (–)

  Power (+)

  Remote Annunciator (+)

SPECIFICATIONS

Base Diameter: 

6.1 inches (155 mm)

Base Height: 

.76 inches (19 mm)

Operating Temperature: 

Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at 

                                                                   www.systemsensor.com

Electrical Ratings

Operating Voltage: 

15 to 32 VDC

Standby Current: 

170 µA

SNAP ON

DECORATIVE

RING

SCREWS

(NOT SUPPLIED)

DETECTOR

BASE

BOX

(NOT SUPPLIED)

FIGURE 2. MOUNTING DETECTOR BASE TO BOX:

C0128-05

TERMINAL 1

TERMINAL 2

TERMINAL 3

TAMPER PROOF

TAB

C0127-04

FIGURE 1. TERMINAL LAYOUT:

MOUNTING

This detector base mounts directly to 4-inch square (with and without plaster 

rings), 4-inch octagon, 3 

1

/

2

-inch octagon, and single gang junction boxes. To 

mount, remove the decorative ring by turning it in either direction to unhook 

the snaps, then separate the ring from the base. Install the base on the box 

using the screws supplied with the junction box and the appropriate mounting 

slots in the base.
Place the decorative ring on the base and rotate it in either direction until it 

snaps into place (see Figure 2).

INSTALLATION AND WIRING GUIDELINES (SEE FIGURE 3)

All wiring must be installed in compliance with all applicable local codes and 

any  special  requirements  of  the  authority  having  jurisdiction.  Proper  wire 

gauges should be used. The conductors used to connect smoke detectors 

to control panels and accessory devices should be color-coded to reduce the 

likelihood of wiring errors. Improper connections can prevent a system from 

responding properly in the event of a fire.
For signal wiring (the wiring between interconnected detectors), it is recom-

mended that the wire be no smaller than 18 AWG (0.823 square mm). Wire 

sizes up to 12 AWG (3.31 square mm) may be used with the base. 
Make electrical connections by stripping about 

3

/

8

 inch (10 mm) of insulation 

from the end of the wire (use strip gauge molded in base). Then slide the wire 

under the clamping plate and tighten the clamping plate screw. Do not loop 

the wire under the clamping plate. (See Figure 4)
Check the zone wiring of all bases in the system before installing the detec-

tors. This includes checking the wiring for continuity, correct polarity, ground 

fault testing and performing a dielectric test.
The base includes an area for recording the zone, address, and type of de-

tector being installed. This information is useful for setting the detector head 

address and for verification of the detector type required for that location. 
Once all detector bases have been wired and mounted, and the loop wiring 

has been checked, the detector heads may be installed in the bases.