background image

D150-03-00              REV: 001 

I56-1030-000

 

 

 © System Sensor 1997

The smoke detector used with this base is designed to 

activate and ini-

tiate

 emergency action, but will do so only when it is used in conjunction 

with an authorized fire alarm system. This detector must be installed in 

accordance with CAN/ULC-S524.

Smoke  detectors  will  not  work  without  power. 

AC  or  DC  powered 

smoke detectors will not work if the power supply is cut off.

Smoke detectors will not sense fires which start where smoke does 

not reach the detectors.

 Smoldering fires typically do not generate a lot 

of heat which is needed to drive the smoke up to the ceiling where the 
smoke detector is usually located. For this reason, there may be large 

delays in detecting a smoldering fire with either an ionization type detec

-

tor or a photoelectric type detector. Either one of them may alarm only 

after flaming has initiated which will generate the heat needed to drive the 

smoke to the ceiling.

Smoke from fires in chimneys, in walls, on roofs or on the other side of a 

closed door(s) may not reach the smoke detector and alarm it. A detector 

cannot detect a fire developing on another level of a building quickly or at 

all. For these reasons, detectors 

shall be located on every level and in 

every bedroom within a building.

Smoke detectors have sensing limitations, too.

 Ionization detectors 

and photoelectric detectors are required to pass fire tests of the flaming 

and smoldering type. This is to ensure that both can detect a wide range 

of types of fires. Ionization detectors offer a broad range of fire sensing 
capability but they are somewhat better at detecting fast flaming fires than 
slow smoldering fires. Photoelectric detectors sense smoldering fires bet

-

ter than flaming fires which have little, if any, visible smoke. Because fires 

develop in different ways and are often unpredictable in their growth, nei-
ther type of detector is always best, and a given detector may not always 

provide early warning of a specific type of fire.

In  general,  detectors  cannot  be  expected  to  provide  warnings  for  fires 
resulting  from  inadequate  fire  protection  practices,  violent  explosions, 
escaping gases which ignite, improper storage of flammable liquids like 

cleaning solvents which ignite, other similar safety hazards, arson, smok-
ing in bed, children playing with matches or lighters, etc. Smoke detectors 
used  in  high  air  velocity  conditions  may  have  a  delay  in  alarm  due  to 
dilution of smoke densities created by frequent and rapid air exchanges. 
Additionally,  high  air  velocity  environments  may  create  increased  dust 
contamination, demanding more frequent maintenance.

To keep your equipment in excellent working order, ongoing mainte-
nance is required per the manufacturer’s recommendations and ULC 
standards.  At a minimum, the requirements of the National Fire Alarm 
Code, shall be followed.  A preventative maintenance agreement should 
be arranged through the local manufacturer’s representative.  Though 
smoke detectors are designed for long life, they may fail at any time.  

Any smoke detector, fire alarm equipment or any component of that 

system which fails shall be repaired or replaced as soon as possible.

WARNING

The Limitations of Property Protection Smoke Detectors

Three-Year Limited Warranty

System  Sensor  warrants  its  enclosed  base  to  be  free  from  defects  in 
materials and workmanship under normal use and service for a period 
of three years from date of manufacture. System Sensor makes no other 
express warranty for this base. No agent, representative, dealer, or em-
ployee  of  the  Company  has  the  authority  to  increase  or  alter  the  obli-
gations or limitations of this Warranty. The Company’s obligation of this 
Warranty shall be limited to the repair or replacement of any part of the 
base which is found to be defective in materials or workmanship under 
normal use and service during the three year period commencing with 
the date of manufacture. After phoning System Sensor’s toll free number 
800-SENSOR2 (736-7672) for a Return Authorization number, send de-
fective units postage prepaid to: System Sensor, Repair Department, RA 

#__________, 6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5. 
Please include a note describing the malfunction and suspected cause 
of failure. The Company shall not be obligated to repair or replace units 
which are found to be defective because of damage, unreasonable use, 

modifications, or alterations occurring after the date of manufacture. In 

no case shall the Company be liable for any consequential or incidental 
damages for breach of this or any other Warranty, expressed or implied 
whatsoever, even if the loss or damage is caused by the Company’s neg-
ligence or fault. Some legislations do not allow the exclusion or limitation 
of incidental or consequential damages, so the above limitation or exclu-

sion may not apply to you. This Warranty gives you specific legal rights, 

and you may also have other rights under common law.

Содержание B112LPA

Страница 1: ...s peak to peak Start Up Capacitance 0 02µF Maximum Standby Ratings 20 VDC Minimum 29 VDC Maximum 120 µA Maximum Alarm Ratings 17 mA Minimum 36 mA Maximum Reset Voltage 1 4 VDC Minimum Reset Time 0 3 Seconds Maximum The optional RA400ZA operates within specified detector alarm currents Start up Time 34 0 Seconds Maximum Relay Contact Ratings Resistive or Inductive 60 Power Factor Form A 2 0 A 30 VA...

Страница 2: ...3 8 1 cm insulation from the end of each wire Slide the wires under the clamp plate and tighten the terminal screw If the base is being installed in a zoned system check the zone wiring before installing the smoke detector head The built in shorting spring makes it convenient to do this After the detector base is wired and attached to the electrical box position the shorting spring against termina...

Страница 3: ...OUT LAST DETECTOR IN LOOP EOL RESISTOR EOL RELAY NOTE Schematic Shown for Reference 1 2 3 4 5 8 9 10 11 12 13 14 ULC LISTED 4 WIRE CONTROL PANEL REMOTE ANNUNCIATOR RELEASING DEVICE OPTIONAL 1 2 3 4 5 8 9 10 11 12 13 14 REMOTE ANNUNCIATOR POWER LOOP POWER LOOP ALARM CIRCUIT RELEASING DEVICE OPTIONAL EOL RELAY RESISTOR D150 03 00 REV 001 3 I56 1030 000 Figure 2 Typical wiring diagram Figure 3A Activ...

Страница 4: ...d in high air velocity conditions may have a delay in alarm due to dilution of smoke densities created by frequent and rapid air exchanges Additionally high air velocity environments may create increased dust contamination demanding more frequent maintenance To keep your equipment in excellent working order ongoing mainte nance is required per the manufacturer s recommendations and ULC standards A...

Отзывы: