background image

D150-03-00              REV: 001 

I56-1030-000

Installation Guidelines

NOTE:  Refer  to  the  releasing  device  manufacturer’s  in-

structions for connection instructions.

Allowable loop resistance is an important specification for 

control  panels  as  well  as  for  smoke  detectors  and  their 

bases.  The  alarm  system  cannot  be  expected  to  oper-

ate  correctly  if  system  components  have  incompatible 

allowable  loop  resistances.  Therefore,  before  beginning 

installation, refer to the control panel manufacturer’s loop 

resistance specification to ensure that it is listed as com

-

patible with the System Sensor base and smoke detector 

being installed.

All  wiring  must  be  installed  in  compliance  with  the  Ca-

nadian Electrical Code, all applicable local codes and any 

special  requirements  of  the  authority  having  jurisdiction, 

using the proper wire size. The conductors used to con-

nect  smoke  detectors  to  control  panels  and  accessory 

devices should be color-coded to reduce the likelihood of 

wiring errors. Improper connections can prevent a system 

from responding properly in the event of a fire.

Wiring

For  signal  wiring  (the  wiring  between  interconnected 

detectors), it is recommended that the wire be no smaller 

than AWG  18.  However,  the  screws  and  clamping  plate 

in the base can accommodate wire sizes up to AWG 12. 

The  use  of  twisted  pair  wiring  for  the  power  (+  and  -) 

loop is recommended to minimize the effects of electrical 

interference.

NOTE:

  To  ensure  that  electrical  connections  are  super-

vised,  DO  NOT  loop  wires  under  terminals  2,  3, 

and 5 –break the wire at each terminal.

To make electrical connections, strip approximately 3/8" (1 

cm) insulation from the end of each wire. Slide the wires 

under the clamp plate and tighten the terminal screw.

If the base is being installed in a zoned system, check the 

zone wiring before installing the smoke detector head. The 

built-in shorting spring makes it convenient to do this. After 

the  detector  base  is  wired  and  attached  to  the  electrical 

box,  position  the  shorting  spring  against  terminal  3.  Use 

the slot in the retaining clip to hold the spring against the 

terminal, as shown in Figure 1. This shorts the negative-in 

and negative-out leads so that loop wiring can be tested 

for continuity.

The shorting spring in the base will disengage automatically 

when  the  detector  head  is  removed  from  the  base.  DO 

NOT  remove  the  shorting  spring  since  it  reengages  as 

the detector head is turned into the base, completing the 

circuit.

Tamper-resistance Feature

NOTE:

  DO NOT use the tamper-resistance feature if the 

SNAP ON 

DECORATIVE

RING

SCREWS (NOT

SUPPLIED)

DETECTOR

BASE

BOX (NOT

SUPPLIED)

SHORTING

SPRING

A78-1175-01

Figure 1. Mounting base to box:

System Sensor XR2 Removal Tool will be used to 

remove detectors from the base.

This detector base can be made tamper resistant so the 

detector cannot be removed without the use of a tool. To 

make the base tamper-resistant, break off the smaller tab 

at the scribed line on the tamper-resistance tab, on the de-

tector mounting bracket (see Figure 3A), before installing 

the detector.

To  remove  the  detector  from  the  base  after  it  has  been 

made  tamper  resistant,  remove  the  decorative  ring  by 

rotating it in either direction and pulling it away from the 

base. Then, insert a small screwdriver into the notch, as 

indicated in figure 3B, and press the plastic lever toward 

the mounting surface before rotating the detector counter-

clockwise for removal.

Содержание B112LPA

Страница 1: ...s peak to peak Start Up Capacitance 0 02µF Maximum Standby Ratings 20 VDC Minimum 29 VDC Maximum 120 µA Maximum Alarm Ratings 17 mA Minimum 36 mA Maximum Reset Voltage 1 4 VDC Minimum Reset Time 0 3 Seconds Maximum The optional RA400ZA operates within specified detector alarm currents Start up Time 34 0 Seconds Maximum Relay Contact Ratings Resistive or Inductive 60 Power Factor Form A 2 0 A 30 VA...

Страница 2: ...3 8 1 cm insulation from the end of each wire Slide the wires under the clamp plate and tighten the terminal screw If the base is being installed in a zoned system check the zone wiring before installing the smoke detector head The built in shorting spring makes it convenient to do this After the detector base is wired and attached to the electrical box position the shorting spring against termina...

Страница 3: ...OUT LAST DETECTOR IN LOOP EOL RESISTOR EOL RELAY NOTE Schematic Shown for Reference 1 2 3 4 5 8 9 10 11 12 13 14 ULC LISTED 4 WIRE CONTROL PANEL REMOTE ANNUNCIATOR RELEASING DEVICE OPTIONAL 1 2 3 4 5 8 9 10 11 12 13 14 REMOTE ANNUNCIATOR POWER LOOP POWER LOOP ALARM CIRCUIT RELEASING DEVICE OPTIONAL EOL RELAY RESISTOR D150 03 00 REV 001 3 I56 1030 000 Figure 2 Typical wiring diagram Figure 3A Activ...

Страница 4: ...d in high air velocity conditions may have a delay in alarm due to dilution of smoke densities created by frequent and rapid air exchanges Additionally high air velocity environments may create increased dust contamination demanding more frequent maintenance To keep your equipment in excellent working order ongoing mainte nance is required per the manufacturer s recommendations and ULC standards A...

Отзывы: