Break wire as shown for
supervision of connection.
DO NOT allow stripped wire
leads to extend beyond 
switch housing. Do NOT
loop wires.

D770-29-00

3

I56-1570-003R

Figure 3. Wiring AFD to bell:

BELL

BELL

POWER SOURCE

A   B

 C

OM

POWER 
TERMINALS

AUX RELAY 
TERMINALS

Figure 7. Wiring the AFD to a panel and other device:

Leave the Relay Wires installed under the Power Terminals and connect the
panel initiating loop wires as shown below. The AFD requires power to
operate, therefore connect the FACP initiating loop wires to the Power
Terminals and Relay Wires as shown.

EOL

OR NEXT 
DEVICE

FACP

POWER SOURCE

BELL

BELL

A   B

  C

OM

POWER 
TERMINALS

AUX RELAY 
TERMINALS

RELAY
WIRES

Figure 6. Wiring the AFD to a panel:

Leave the Relay wires installed under the Power Terminals and connect the
panel initiating loop wires as shown below.

OR NEXT 
DEVICE

POWER 
TERMINALS

AUX RELAY 
TERMINALS

A   B COM

EOL

FACP

RELAY
WIRES

TO NEXT MODULE
         OR EOL

INTELLIGENT

MODULE

FACP

A   B COM

POWER 
TERMINALS

AUX RELAY 
TERMINALS

RELAY
WIRES

Figure 8. (2 Wire Addressable) Wiring the AFD to an addressable

panel using the SLC loop wires for power:

Remove the Relay Wires from under the Power Terminals. Connect these
wires to the Addressable Module.

NOTE

Consult FACP Manufacturers’ Compatibility Guide prior to instal-
lation.

Figure 4. (4 Wire Addressable) Wiring the AFD to an addressable

panel using an auxiliary power supply for power:

Remove the Relay Wires from under the Power Terminals. Connect these
wires to the Addressable Module.

Figure 5. Wiring the AFD using 4 wires. (Aux. Power from Panel): 

Remove the Relay Wires from the Power Terminals. Cut off the spade
lugs from the ends of the Relay Wires. Put wire nuts over ends of Relay
Wires as shown. Use Aux. Relay Terminals to make connection to panel
and next device as shown.

AUX. POWER
OUTPUT

INITIATING
LOOP

A   B COM

POWER 
TERMINALS

AUX RELAY 
TERMINALS

RELAY
WIRES

FACP

EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V

EOL

NOTE

To comply with NFPA code, never put more than two wires in
a wire nut.

Relay wires and power terminal wiring must be contained within either a
common enclosure or enclosures within 6 meters (20 feet) of each other
with wiring inside conduit.

CAUTION

AUX.
POWER
OUTPUT

MODULE

SLC
LOOP

A   B

 CO

M

POWER 
TERMINALS

AUX RELAY 
TERMINALS

RELAY
WIRES

FACP

MODULE

A   B

 C

OM

POWER 
TERMINALS

AUX RELAY 
TERMINALS

RELAY
WIRES

NOTE: PLACE MODULE EOL
RESISTOR ACROSS RELAY
WIRES INSIDE AFD COVER.

NOTE: PLACE MODULE EOL
RESISTOR ACROSS RELAY
WIRES INSIDE AFD COVER.

AFD
ENCLOSURE

AFD
ENCLOSURE

EOL POWER
SUPERVISION
RELAY (SHOWN
ENERGIZED)
A77-716 12/24V

firealarmresources.com

Содержание AFD Accuflow

Страница 1: ...quate clearance for installation and removal and a clear view of it for inspections See Figure 1 for mounting dimensions 2 Locate detector 6 to 7 ft above the floor to protect from potential damage 3 On horizontal runs position the detector on the top or side of the pipe Do not mount it upside down because condensation may collect in the housing and impair the operation of the detector For vertica...

Страница 2: ...d clamp wire with screw in hole located between conduit entrance holes See Figure 10A page 4 5 If a second conduit entry is required remove the knockout plug using a flat blade screwdriver as shown on Figure 10B page 4 Strike sharply with a hammer to pierce the wall of the knockout plug Move to an adjacent wall section and repeat until the plug falls out Make sure that the waterflow detector is su...

Страница 3: ... Module NOTE Consult FACP Manufacturers Compatibility Guide prior to instal lation Figure 4 4 Wire Addressable Wiring the AFD to an addressable panel using an auxiliary power supply for power Remove the Relay Wires from under the Power Terminals Connect these wires to the Addressable Module Figure 5 Wiring the AFD using 4 wires Aux Power from Panel Remove the Relay Wires from the Power Terminals C...

Страница 4: ...n and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of dam age unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any con sequential or incidental damages for breach of this or any other Warranty expressed or implied whatsoever even if the...

Отзывы: