Sensitivity Testing

NOTE:

Before testing, notify the proper authorities that
the smoke detector system is undergoing mainte-
nance, and therefore the system will be tempo-
rarily out of service. Disable the zone or system
undergoing maintenance to prevent unwanted
alarms.

Detectors must be tested after installation and following
periodic maintenance. The sensitivity of the 6424 may be
tested as follows:

NOTE:

Before testing the detector, check for the presence
of the flashing green LED at the receiver, making
sure not to disturb or block the beam. If it does not
flash and the detector is not in trouble or alarm,
power has been lost to the detector (check the wir-
ing).

A. Calibrated Test Filter

1. Test the detector at the receiver.

2. Use the proper side of the test card depending on the

sensitivity setting (55 or 30) of the detector.

3. Place the NO ALARM section of the test filter over the

receiver lens. The green LED should continue to pulse
and the detector should not alarm after 15 seconds.

4. Place the ALARM section of the test filter over the

lens. The detector should alarm within 15 seconds.

5. The detector can be reset with the local reset, remote

reset, or by momentarily interrupting the power.

6. Notify the proper authorities that the system is back

on line.

Detectors that fail to alarm should be returned for repair.
Units that alarm during the non-alarm test (step 3) should
be cleaned and tested again before being returned. Follow
the maintenance instructions for cleaning.

B. Remote Test Switch

The remote test station, RTS451, can be used with the
6424 beam smoke detector. Follow instructions included
with the test station for proper use. See Figure 9 (Remote
Test Station) for wiring diagram.

If the detector is not in trouble and the unit fails to
alarm, check all related wiring. Once the proper wiring
is confirmed, perform the above calibrated test filter pro-
cedure. If the unit still fails to alarm it should be re-
turned for repair.

Maintenance

NOTE:

Before cleaning the detector lenses, notify the
proper authorities that the smoke detector system
is undergoing maintenance, and therefore the sys-
tem will be temporarily out of service. Disable the
zone or system undergoing maintenance to prevent
unwanted alarms.

1. Carefully clean the lenses of both the receiver and the

transmitter. A damp soft cloth with a mild soap may be
used. Avoid products with solvents or ammonia.

2. After the lenses are clean, switch the receiver to the

align mode. If three and only three alignment LEDs turn
on, slide the align switch back to normal mode and wait
approximately one minute for self calibration. The green
LED should pulse after the calibration time. If more or
fewer LEDs turn on in align mode, see the Beam Align-
ment Instructions on page 9 for realignment.

3. Notify the proper authorities that the system is back on

line.

D400-18-00

11

I56-494-10R

Содержание 6424

Страница 1: ...put Local LED yellow Normal Operation Local LED flashing green Alignment Aid LED Bar Graph 4 red LEDs Relays Alarm Trouble Environmental Temperature 30 C to 55 C 22 F to 131 F Humidity 10 to 93 RH Noncondensing Mechanical Weight Receiver 1 5 lbs 663 g Transmitter 1 3 lbs 598 g Mounting Ceiling or Wall Separate Mounting Brackets Provided Wiring Plug with Attached Cable Adjustment Angle Ceiling 30 H...

Страница 2: ...ectors the EOL Power Supervisory Module is energized The relay contacts along with the detector s trouble relay contacts can provide a closed series circuit in the control panel s alarm initiating loop A loss in power or a trouble condition at the detector causes the respective EOL or trouble relay to open resulting in a trouble signal at the control panel Parts List Description Quantity Receiver ...

Страница 3: ...roof or ceiling Figures 3 and 4 show the spac ing for both the shed type and peaked type sloped ceilings Figure 3 Sloped ceiling shed type S 3 FT MAX S 1 2 S MAX Tx Rx A78 2036 01 Figure 4 Sloped ceiling peaked type 1 2 S S S 1 2 S 3 FT MAX 3 FT MAX MOUNT DETECTOR ANYWHERE IN THIS AREA Tx Rx A78 2035 01 Mounting Locations Beam detectors require a stable mounting surface for proper operation A surf...

Страница 4: ...he likelihood of wiring er rors Improper connections can prevent a system from re sponding properly in the event of a fire Installation wire used for the beam detector shall be no smaller than 18 gauge 1 0 square mm For best system performance all wiring should be twisted pair and in stalled in separate grounded conduit Do NOT mix fire sys tem wiring in the same conduit as any other electrical wir...

Страница 5: ...nsmitter permanently wired to receiver A78 2043 00 CLASS A RETURN LOOP INITIATING LOOP POWER TO DETECTORS LISTED PANEL LISTED REMOTE POWER SOURCE POWER INPUTS TO TRANSMITTER ARE NONPOLAR TRANSMITTER BLUE GREEN WHITE BROWN BLACK RED ORANGE GREEN BLACK RED WHITE STRIPE WHITE WHITE BLACK STRIPE GRAY VIOLET WHITE VIOLET STRIPE BROWN WHITE YELLOW STRIPE WHITE RED STRIPE TRANSMITTER BLUE GREEN BLACK RED...

Страница 6: ...ve In any applications where the BMB Beam Mounting Bracket kit is used the kit should be installed before the detector is mounted Instructions for mount ing the BMB are included in the BMB kit 3 Insert the flange of the detector mounting bracket into the keyed hole of the wall or ceiling mounting bracket Slide the detector forward into position The detector should now hang from the bracket 4 Inser...

Страница 7: ...NT SCREWS 2 U BRACKET WALL MOUNTING BRACKET MOUNTING HOLE PLASTIC WASHER A78 2034 01 Figure 13 Ceiling mounting MOUNTING HUB MOUNTING HUB ALIGNMENT LEDs STATUS LEDs RECEIVER ONLY BEAM LENS HOLE PLUG ALIGNMENT ADJUST POTENTIOMETER RECEIVER ONLY CABLE EGRESS HOLE PLUG USED TO PLUG UNUSED HOLE VERTICAL ADJUSTMENT SCREWS 2 U BRACKET HORIZONTAL ADJUSTMENT SCREW 10 24 x 2 1 4 in CEILING MOUNTING BRACKET...

Страница 8: ...CTOR CABLE RESET SWITCH 30 55 SENSITIVITY SELECT SWITCH N A ALIGNMENT MODE SWITCH A78 2032 01 Figure 15 Rear view transmitter ACCESS DOOR CONNECTOR 6 CONDUCTOR CABLE A N ALIGNMENT MODE SWITCH SW1 L S RANGE SELECT SWITCH SW2 A78 2031 01 D400 18 00 8 I56 494 10R ...

Страница 9: ...ge L 100 to 330 feet 2 If the transmitter is directly wired to the receiver Figure 7 slide the alignment switch SW1 on the transmitter to the A align position see Figure 15 Point the trans mitter directly at the receiver then go to step 5 3 If the transmitter is wired directly to a power supply it should be temporarily wired to the receiver if pos sible see Figure 8 NOTE Temporarily wiring the tra...

Страница 10: ...this 3 When it is impossible to get more than three LEDs to light carefully tighten the horizontal adjustment screws and then the vertical adjustment screws on the transmitter bracket making sure all three alignment LEDs stay lit 4 Slide the alignment switch on the transmitter to the NORMAL MODE N position see figure 15 and dis connect any temporary wiring Carefully close the door on the transmitt...

Страница 11: ... Units that alarm during the non alarm test step 3 should be cleaned and tested again before being returned Follow the maintenance instructions for cleaning B Remote Test Switch The remote test station RTS451 can be used with the 6424 beam smoke detector Follow instructions included with the test station for proper use See Figure 9 Remote Test Station for wiring diagram If the detector is not in t...

Страница 12: ...ence or fault Some states do not allow the exclusion or limitation of incidental or conse quential damages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state FCC Statement This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 Thi...

Отзывы: