background image

 

2

                                                                                               

I56

2700

004

 

 
 
 
 
 
 
 
 
 
 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

A.Test

 

Magnet

 

(Model

 

No.

 

M02

04)

         

1.

 

Place

 

the

 

magnet

 

against

 

the

 

cover

 

in

 

the

 

magnet

 

test

 

area

 

as

 

shown

 

in

 

Figure

 

3

 

to

 

activate

 

the

 

test

 

feature.

         

2.

 

The

 

LEDs

 

should

 

latch

 

ON

 

within

 

10

 

seconds,

 

indicating

 

alarm

 

and

 

annunciating

 

the

 

panel.

         

3.

 

Reset

 

the

 

detector

 

at

 

the

 

system

 

control

 

panel.

 

 

B.

 

Direct

 

Heat

 

Method

 

(Hair

 

dryer

 

of

 

1000

 

 

1500

 

watts)

         

1.

 

From

 

the

 

side

 

of

 

the

 

detector,

 

direct

 

the

 

heat

 

toward

 

the

 

sensor.

 

Hold

 

the

 

heat

 

source

 

about

 

15cm

 

(6

 

inches)

 

away

 

to

 

prevent

 

damage

 

to

 

the

 

cover

 

during

 

testing.

         

2.

 

The

 

LEDs

 

on

 

the

 

detector

 

should

 

light

 

when

 

the

 

temperature

 

at

 

the

 

detector

 

reaches

 

the

 

alarm

 

setpoint.

 

If

 

the

 

LEDs

 

fail

 

to

 

light,

 

check

 

the

 

power

 

to

 

the

 

detector

 

and

 

the

 

wiring

 

in

 

the

 

detector

 

adapter.

 

3.

 

Reset

 

the

 

detector

 

at

 

the

 

system

 

control

 

panel.

 

 

Detectors

 

that

 

fail

 

these

 

tests

 

should

 

be

 

cleaned

 

as

 

described

 

under

 

MAINTENANCE

 

and

 

retested.

 

If

 

the

 

detectors

 

still

 

fail

 

these

 

tests

 

they

 

should

 

be

 

replaced

 

immediately.

 

 

 

MAINTENANCE

 

NOTE:

   

Before

 

cleaning

 

notify

 

the

 

proper

 

authorities

 

that

 

the

 

system

 

is

 

undergoing

 

maintenance,

 

and

 

therefore

 

the

 

system

 

will

 

temporarily

 

be

 

out

 

of

 

service.

 

Disable

 

the

 

loop

 

or

 

system

 

undergoing

 

maintenance

 

to

 

prevent

 

unwanted

 

alarms.

 

 

 
 
 
 
 
 
 

 

 

 
 

Please

 

refer

 

to

 

insert

 

for

 

the

 

Limitations

 

of

 

Fire

 

Alarm

 

Systems

 

Figure 2A. Detector Wiring Diagram 

Figure 3. Views Showing Position of Test Magnet 

Ver.B

TAMPER

 

RESISTANT

 

FEATURE

 

The

 

sensor

 

adapter

 

have

 

a

 

tamper

resistant

 

feature.

 

When

 

this

feature

 

is

 

enabled,

 

sensors

 

cannot

 

be

 

removed

 

from

 

the

 

adapter

without

 

the

 

use

 

of

 

a

 

small

 

screwdriver

 

or

 

other

 

similar

 

tool.

 

Refer

to

 

the

 

sensor

 

adapter

 

installation

 

instruction

 

manual

 

for

 

details

 

in

using

 

this

 

feature.

 

 

 

TESTING

 

Before

 

testing,

 

notify

 

the

 

proper

 

authorities

 

that

 

the

 

system

 

is

undergoing

 

maintenance,

 

and

 

will

 

temporarily

 

be

 

out

 

of

 

service.

Disable

 

the

 

system

 

to

 

prevent

 

unwanted

 

alarms.

     

 

All

 

sensors

 

must

 

be

 

tested

 

after

 

installation

 

and

 

periodically

thereafter.

 

Testing

 

methods

 

must

 

satisfy

 

the

 

Authority

 

Having

Jurisdiction

 

(AHJ).

 

Sensors

 

offer

 

maximum

 

performance

 

when

tested

 

and

 

maintained

 

in

 

compliance

 

with

 

AS1851

2005

.

 

The

 

sensor

 

may

 

be

 

tested

 

in

 

the

 

following

 

ways:

Figure 2B. Field Wiring Diagram 

Отзывы: