Testing

Before testing, notify the proper authorities that the smoke 
detector system is undergoing maintenance and will tem-
porarily  be  out  of  service.  Disable  the  zone  or  system 
undergoing maintenance to prevent unwanted alarms.

Detectors  must  be  tested  after  installation  and  periodic 
maintenance. To test the 2451:

NOTE:

  Before  testing  the  detector,  check  to  ensure  that 

the LEDs are blinking. If they are not, the detector 
has lost power (check the wiring) or it is defective 
(return for repair).

A. Test Magnet (System Sensor model no. M02-04-00)
    1. Place the magnet against the cover opposite the test 

module  slot  to  activate  the  test  feature  (see  Figure 
1).

    2. The LEDs should latch on within 5 seconds indicating 

alarm and annunciating the panel.

B. Calibrated Test Card (System Sensor no. R59-18-00)
    1. Remove the detector cover by placing a small bladed 

screwdriver  in  the  side  slot  of  the  detector  cover, 
twisting  it  slightly  until  the  cover  can  be  turned 
counterclockwise for removal.

    2. Insert the NO ALARM end of the test card fully into 

the test slot (see Figure 2) then slide it counterclock-
wise until it stops.

    3. Wait for at least 20 seconds. The detector should NOT 

alarm.

    4. Remove  the  test  card  by  sliding  it  clockwise  before 

removing, then insert the ALARM end.

    5. The LEDs should latch on within 20 seconds indicat-

ing alarm and annunciating the panel.

    6. Put  the  cover  back  by  gently  rotating  it  clockwise 

until it locks in place.

C. Test Module (System Sensor no. MOD400R)
    The  MOD400R  is  used  with  your  DMM  or  voltmeter 

to  check  the  detector  sensitivity  as  described  in  the 
MOD400R’s manual.

D. Aerosol Generator (Gemini 501)
    Set the generator to represent 4% to 5%/Ft. obscuration 

as described in the Gemini 501 Manual. Using the bowl 
shaped applicator, apply aerosol until the unit alarms.

E. Direct Heat Test (2451TH only)
    To test the bi-metallic thermal collector, aim a heat source, 

such as a low powered heat gun or blow dryer, across the 
detector. Hold the heat source about 12 inches (30 cm) 
from the detector to avoid damaging the plastic.

    When  the  temperature  rises  to  greater  than  135°F 

(57°C),  the  detector  should  latch  into  the  alarm.  The 
bi-metallic collector automatically resets after the test.

Notify  the  proper  authorities  that  the  detection  system  is 
back on line.

Detectors that fail these tests should be cleaned as described 
under  MAINTENANCE  and  retested.  If  the  detectors  still 
fail these tests they should be returned for repair.

Figure 2:

REMOVABLE HEAD COVER

CLEANABLE SCREEN

HEAD COVER

REMOVAL SLOT

VANED CHAMBER

TEST SLOT

P/N RS24 (W/O THERMAL)

C0722-00

Содержание 2451, 2451TH

Страница 1: ...er 4 0 inches 101 cm Weight 0 5 lb 277 g Operating Temperature Range 0 C to 49 C 32 F to 120 F Operating Humidity Range 10 to 93 Relative Humidity Maximum Air Velocity 3000 Ft Min 15 M S Locking Alarm Reset by momentary power interruption Fixed Temperature Thermal 135 F 57 C Two LEDs on each detector light to provide a local 360 visible alarm indication They flash every ten seconds indi cating tha...

Страница 2: ... the detector mounting bracket then install the detector To remove the detector from the bracket once it has been made tamper resistant use a pocket screwdriver or similar tool to depress the tamper resistant tab located in the slot on the mounting bracket Then turn the detector counterclockwise until it separates from the base 3 After all detectors have been installed apply power to the control u...

Страница 3: ...arm 4 Remove the test card by sliding it clockwise before removing then insert the ALARM end 5 The LEDs should latch on within 20 seconds indicat ing alarm and annunciating the panel 6 Put the cover back by gently rotating it clockwise until it locks in place C Test Module System Sensor no MOD400R The MOD400R is used with your DMM or voltmeter to check the detector sensitivity as described in the ...

Страница 4: ...r can be turned counterclock wise for removal 2 Vacuum the screen carefully without removing it If fur ther cleaning is required continue with Step 3 otherwise skip to Step 6 3 Remove the screen by pulling it straight out see Figure 2 Vacuum the inside 4 Clean the vaned chamber piece by vacuuming or blow ing out dust and particles 5 To replace the screen orient it so that the arrow on top aligns w...

Отзывы: