2451 and 2451TH Photoelectronic 
Plug-in Smoke Detectors

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Before Installing

Please  thoroughly  read  the  System  Sensor  publication, 
A05-1003, 

Applications Guide for System Smoke Detectors

which  provides  detailed  information  on  detector  spacing, 
placement, zoning, wiring, and special applications. Copies 
of this guide are available at no charge from System Sensor. 
(For installations in Canada, refer to CAN4-S524, Standard 
for the Installation of Fire Alarm Systems and CEC Part 1, 
Sec. 32.)

NOTICE: 

This manual should be left with the owner/user 

of this equipment.

IMPORTANT: 

This sensor must be tested and maintained 

regularly  following  NFPA  72  requirements.  This  sensor 
should be cleaned at least once a year.

General Description

The  2451  photoelectronic  detectors  utilize  state-of-the-art, 
optical sensing chambers. These detectors are designed to 
provide open area protection, and to be used with compat-
ible  UL-listed  control  panels  only.  Model  2451TH  has  the 
same  specifications  as  Model  2451,  with  the  addition  of 
a  built-in  fixed  temperature  (135°F–57°C)  thermal  detec-
tion  unit.  The  capability  of  plugging  these  detectors  into 
a variety of special bases makes them more versatile than 
equivalent direct-wired models.

Specifications

Size                                              
Height:                                          2.4 inches (61 cm)
                                                     Add 0.5 inches (13 cm) for thermal model 2451TH
Diameter:                                       4.0 inches (101 cm)
Weight:                                          0.5 lb. (277 g)
Operating Temperature Range:        0°C to 49°C (32°F to 120°F)
Operating Humidity Range:             10% to 93% Relative Humidity
Maximum Air Velocity:                   3000 Ft./Min. (15 M/S)
Locking Alarm:                              Reset by momentary power interruption
Fixed Temperature Thermal:           135°F (57°C)

Two  LEDs  on  each  detector  light  to  provide  a  local  360° 
visible alarm indication. They flash every ten seconds indi-
cating that power is applied  and the detector is operating 
properly.  The  LEDs  light  continuously  in  alarm.  Remote 
LED  annunciator  capability  is  available  as  an  optional 
accessory.  These  detectors  also  have  the  Latching  Alarm 
feature. The alarm can be reset only by a momentary power 
interruption.  These  detectors  may  be  tested  by  activating 
the internal reed switch with a magnet, or by inserting a 
calibrated test card in a test slot after removing the detec-
tor cover.

The 2451 has been approved for marine use in dry locations 
by Underwriters Laboratory, Inc. The detector is to be used 
in dry interior locations only.

Base Selection and Wiring Guide

Refer  to  the  installation  instructions  for  the  Plug-in 
Detector Bases for base selection and wiring instructions. 
System Sensor has a variety of detector bases available for 
this smoke detector. This includes 2-wire applications with 
and without relays and/or current limiting resistors, 4-wire 
and 120VAC applications. (Note: the 120VAC detector base 
is not available in Canada.)

All  bases  are  provided  with  screw  terminals  for  power, 
ground, remote annunciator connections and relay contact 
connections,  if  applicable.  The  electrical  ratings  for  each 
detector-base  combination  are  also  included  in  the  base 
installation instructions. 

Содержание 2451, 2451TH

Страница 1: ...er 4 0 inches 101 cm Weight 0 5 lb 277 g Operating Temperature Range 0 C to 49 C 32 F to 120 F Operating Humidity Range 10 to 93 Relative Humidity Maximum Air Velocity 3000 Ft Min 15 M S Locking Alarm Reset by momentary power interruption Fixed Temperature Thermal 135 F 57 C Two LEDs on each detector light to provide a local 360 visible alarm indication They flash every ten seconds indi cating tha...

Страница 2: ... the detector mounting bracket then install the detector To remove the detector from the bracket once it has been made tamper resistant use a pocket screwdriver or similar tool to depress the tamper resistant tab located in the slot on the mounting bracket Then turn the detector counterclockwise until it separates from the base 3 After all detectors have been installed apply power to the control u...

Страница 3: ...arm 4 Remove the test card by sliding it clockwise before removing then insert the ALARM end 5 The LEDs should latch on within 20 seconds indicat ing alarm and annunciating the panel 6 Put the cover back by gently rotating it clockwise until it locks in place C Test Module System Sensor no MOD400R The MOD400R is used with your DMM or voltmeter to check the detector sensitivity as described in the ...

Страница 4: ...r can be turned counterclock wise for removal 2 Vacuum the screen carefully without removing it If fur ther cleaning is required continue with Step 3 otherwise skip to Step 6 3 Remove the screen by pulling it straight out see Figure 2 Vacuum the inside 4 Clean the vaned chamber piece by vacuuming or blow ing out dust and particles 5 To replace the screen orient it so that the arrow on top aligns w...