background image

D150-03-00 

I56-597-03R

B112LP Plug-in Detector Base

For use with the following smoke detectors:
IN US:   

1151, 2151

IN CANADA:  1151A, 2151A
IN EUROPE: 

1151E, 2151E

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Before Installing

Please thoroughly read the System Sensor manual I56-407, 

Guide for Proper Use of System Smoke Detectors

, which pro-

vides detailed information on detector spacing, placement, 
zoning,  wiring,  and  special  applications.  Copies  of  this 
manual are available at no charge from System Sensor. (For 
installation  in  Canada,  refer  to  CAN/ULC-S524, 

Standard 

for the Installation of Fire Alarm Systems

 and CEC Part 1, 

Sec. 32.)

NOTICE:

 This manual should be left with the owner/user 

of this equipment.

IMPORTANT:

  The  detector  used  with  this  base  must  be 

tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned 
at least once a year.

Specifications

Base Diameter: 

6.2 inches (157 mm)

Base Height: 

0.95 inches (24 mm)

Weight: 

0.3 lb. (137 g)

Mounting: 

4-inch square box with or without  plaster ring. Min. depth–1.5 inches

 

3-1/2-inch octagon box. Min. depth–1.5 inches

Operating Temperature Range: 

0° to 49°C (32° to 120°F)

Operating Humidity Range: 

10% to 93% Relative Humidity,  Noncondensing                

Electrical Ratings - includes base and detector

System Voltage: 

24 VDC

Maximum Ripple Voltage: 

4 Volts peak-to-peak

Start-Up Capacitance: 

0.02µF Maximum

Standby Ratings:  

20 VDC Minimum

 

29 VDC Maximum

 

120 µA Maximum

Alarm Ratings: 

17 mA Minimum

 

36 mA Maximum

Reset Voltage: 

1.4 VDC Minimum

Reset Time: 

0.3 Seconds Maximum

 

(The optional RA400Z operates within specified detector alarm currents.)

Start-up Time: 

34.0 Seconds Maximum

Relay Contact Ratings:
Resistive or Inductive (60% Power Factor)
Form A:  

2.0 A @ 30 VAC/DC

Form C: 

2.0 A @ 30 VAC/DC

 

0.6 A @ 110 VDC

 

1.0 A @ 125 VAC

General Description

The Model B112LP detector base is designed for use with 
System Sensor model 2151 photoelectronic and 1151 ioniza-
tion detector heads. This four-wire base is equipped with 
screw terminals for the connection of power, ground, and 
an optional remote annunciator.

Mounting

The detector base mounts directly to 3-1/2 inch and 4-inch 
octagon  boxes  and  4-inch  square  boxes,  with  or  without 
plaster  rings.  To  mount  the  base,  remove  the  decorative 
ring by rotating it in either direction to unhook the snaps 
before  separating  the  ring  from  the  base.  Use  the  screws 
supplied  with  the  junction  box  to  attach  the  base  to  the 
box  through  the  appropriate  slots  in  the  base  (see  Figure 
1). Position the decorative ring around the base and rotate 
it in either direction until the ring snaps into place. 

D150-03-00 

I56-597-03R

 

©2001 System Sensor

Three-Year Limited Warranty

System Sensor warrants its enclosed smoke detector base to be free from 
defects in materials and workmanship under normal use and service for a 
period of three years from date of manufacture. System Sensor makes no 
other express warranty for this smoke detector base. No agent, represen-
tative, dealer, or employee of the Company has the authority to increase 
or  alter  the  obligations  or  limitations  of  this  Warranty.  The  Company’s 
obligation of this Warranty shall be limited to the repair or replacement 
of any part of the smoke detector base which is found to be defective in 
materials or workmanship under normal use and service during the three 
year  period  commencing  with  the  date  of  manufacture.  After  phoning 
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return 
Authorization  number,  send  defective  units  postage  prepaid  to:  System 
Sensor,  Repair  Department,  RA  #__________,  3825  Ohio  Avenue,  St. 

Charles, IL 60174. Please include a note describing the malfunction and 
suspected cause of failure. The Company shall not be obligated to repair 
or  replace  units  which  are  found  to  be  defective  because  of  damage, 
unreasonable  use,  modifications,  or  alterations  occurring  after  the  date 
of  manufacture.  In  no  case  shall  the  Company  be  liable  for  any  conse-
quential or incidental damages for breach of this or any other Warranty, 
expressed or implied whatsoever, even if the loss or damage is caused by 
the Company’s negligence or fault. Some states do not allow the exclu-
sion  or  limitation  of  incidental  or  consequential  damages,  so  the  above 
limitation  or  exclusion  may  not  apply  to  you.  This  Warranty  gives  you 
specific legal rights, and you may also have other rights which vary from 
state to state.

Please refer to insert for the Limitations of Fire Alarm Systems

I56-
597-03R

Отзывы: