background image

Section II 

General Product Information

006-0006504  02/27/18 

 

Rev R 

10 of 56 

UPS-3000 Guide 

www.synqor.com

Part Numbering Scheme and Options

This table shows the part numbering scheme for the full line of SynQor UPS products: 

Family Output Power Battery Pack 

Size

Height

AC Input 

Frequency

AC Output 

Voltage

AC Output 

Neutral Wire

AC Output 

Set Point 

Frequency

DC Input / 

DC2 Output

Dual DC1 

Output 

Voltage

Additional Options

UPS

3000

S

2U

L

1

G

6

D

28

000

 UPS  3000:

3000 VA 

2500 W

 S: 

Standard

2U:

3.40”

L:  

W: 

  

47-65 Hz 

47-800 Hz

 1:  

 2: 

5:  

6:  

4: 

   50 Hz 

   60 Hz 

 400 Hz

S:

 Not Installed

00: 

 None

000: 

 None

D:

 DC Input

12:

 12 V

0CE:

 CE Marking

G:

 Grounded

M:

 DC2 Out

15:

 15 V

E00:

 Ethernet / 

 115 Vrms 

F:

 Floating *

 24 VDC with

24:

 24 V

 SNMP

 230 Vrms

R:

AC Output

 Droop Share

28:

 28 V

ECE:

 Ethernet / 

Electronic

R:

 DC2 Out

40:

 40 V

 SNMP &

Breaker *

 28 VDC with

50:

 50 V

 CE Marking

 Droop Share

Not all combinations make valid part numbers, please contact SynQor for availability. See the Product Summary web page for more options.

* Note:

 Order “F: Floating” option when configuring the AC output for multi-unit combinations of up to 3 units.

 Order “R: AC Output Electronic Breaker” option for fault-tolerant, glitch-free parallel systems of up to 32 units with N+M redundancy; 

 The AC output neutral wire will not be connected to the chassis

Example:

 UPS-3000-S-2U-L1G6D28-000

The UPS-3000 Series of products provide up to 3000 VA and 2500 W of total output power  

(AC plus DC).

•  A 2U high, 65 lbs. rackmount unit that uses two standard battery packs which provide >10 minutes of battery 

run-time at full power

Each format has various options that can be specified according to the part numbering scheme 

shown in the table:

•  The allowable frequency of the AC INPUT can either be in the 47-65 Hz range (for 50 Hz and/or 60 Hz systems) 

or in the 360-800 Hz range (for 400 Hz and Variable Frequency systems)

•  The output voltage of the UPS-3000 Series can be 115 Vrms or 230 Vrms.

•  The AC output can be configured with its neutral wire internally grounded to the chassis of the UPS or left 

floating for shipboard applications.

•  The initial set-point frequency of the AC OUTPUT voltage can be 50 Hz, 60 Hz or 400 Hz.  Regardless of the initial 

set-point frequency, the actual frequency can be set through the communications/control port.

•  There is an optional DC INPUT that is specified to comply with MIL-STD-704F and MIL-STD-1275D for 28 V 

systems.

•  Two optional DC OUTPUT capabilities are available: DC1 with up to 2x500 W capability, and DC2 with up to 

2500 W capability.

•  RS232 serial port and logic-level I/O communication are included in the standard model.  An Ethernet port 

providing web and SNMP interfaces is an available option.

•  The Electronic Breaker option adds fault tolerant, glitch free multi-unit operation for N+1 or N+M redundancy.  

This option also allows up to 32 units to be combined to form single-phase, split-phase, or 3-phase systems

The UPS-3000S-2U data sheet showing these specifications and other information can be found 

at the web site 

www.SynQor.com/UPS

.

Содержание UPS-3000-S-2U

Страница 1: ...ninterruptible Power Supply 1 888 567 9596 USA only SynQor Headquarters 155 Swanson Road Boxborough MA 01719 1316 USA www synqor com Made in USA UPS 3000 S 2U N M Redundancy optional Operator s Guide...

Страница 2: ...cy 13 Total Output Power that can be derived from the AC INPUT 14 Power Cable Wiring Diagram 17 Power Cable Wire Size 18 Section III Operation Set Up 19 Start Up 20 Shut Down 20 Power Cable Connection...

Страница 3: ...arallel F option 39 Multi unit AC Output On Off Control Expanded Parallel R option 39 AC Output Neutral Grounding 39 Section V Battery Pack Battery Technology 40 Electronic Circuitry within the Batter...

Страница 4: ...ce of AC power and not connected to the UPS do not contact the exposed terminals of the AC input cable Do not assume that the source of AC power is not present Connections between the AC input cable a...

Страница 5: ...t apply external voltages to the pins of an exposed battery pack connector It is not possible to charge the battery pack from an external source and excess voltages could damage internal control circu...

Страница 6: ...pdf Please contact the factory for all other questions regarding the UPS battery pack CAUTION Do not dispose of batteries in a fire The batteries may explode CAUTION Do not open or mutilate batteries...

Страница 7: ...with a crest factor up to 2 5 and any load power factor from 0 0 to 1 0 There are two optional DC outputs at various voltage and power levels The total AC plus DC output power is limited to 2500 W Th...

Страница 8: ...sources the AC INPUT the optional DC INPUT or the battery with that order of priority based on availability EMI filters are present at all external inputs and outputs AC INPUT DC INPUT DC2 OUTPUT 2x...

Страница 9: ...ch cannot be used directly in parallel The DC2 option provides a single parallelable output up to 2500 W When the DC2 option is selected the DC Input is not available The DC1 and DC2 outputs are isola...

Страница 10: ...power AC plus DC A 2U high 65 lbs rackmount unit that uses two standard battery packs which provide 10 minutes of battery run time at full power Each format has various options that can be specified...

Страница 11: ...d Temperature 15 26 V at 0 A 22 V at 100 A 2200 W 28 V Option Voltage Regulation Over Load Temperature 13 30 V at 0 A 26 V at 96 2 A 2500 W Specifications subject to change without notice ENVIRONMENTA...

Страница 12: ...CANNON 24 10 A D C B G E F B 5 15 1 6 11 1 6 11 10 5 15 10 OFF OFF O N O F F O N O F F ITT 22 2 A C B POWER OUT POWER IN LOAD CHARGE FAN BATT BATT UPS POWER OUT POWER IN LOAD CHARGE FAN BATT BATT UPS...

Страница 13: ...he UPS 3000 series uninterruptible power supplies delivers power to its AC OUTPUT from a 230 Vrms AC INPUT an 115 Vrms AC INPUT or a 28 V DC INPUT 70 0 75 0 80 0 85 0 90 0 95 0 0 400 800 1200 1600 200...

Страница 14: ...on on transient conditions 0 400 800 1200 1600 2000 2400 2800 25 30 35 40 45 50 55 Output Power Watts Air Temperature C UPS Output Power vs Air Temperature VAC IN 105VRMS or VDC IN 22V or power drawn...

Страница 15: ...ween the curves shown For example the total output power that can be derived from the AC INPUT when the voltage is 97 5 Vrms would be 2500 W up to an ambient temperature of 50o C 122o F and then derat...

Страница 16: ...ly while the AC output is loaded to 1500 W or greater the available DC1A and or DC1B output power is reduced as shown in Figure 4 In order to achieve the rated DC1 output power the AC output must be l...

Страница 17: ...functions and locations AC INPUT Pin Function A Line B Neutral C Ground ITT 22 2 A C B DC INPUT Pin Function F E D Vin A B C Vin Return ITT CANNON 24 10 A D C B G E F AC OUTPUT Pin Function A Line B N...

Страница 18: ...cables because the current flowing through it is very high as high as 124 A for the UPS 3000 Series and the voltage across it is already relatively small as low as 22 V In fact a common problem that...

Страница 19: ...the correct polarity Connect the USER I O cables Connect all INPUT cables first to the UPS and then to the various sources An overcurrent protect and disconnect device should be installed on the DC IN...

Страница 20: ...ng as the battery has charge left in it This is sometimes referred to as a COLD START in the industry Under this condition the LED above the ON OFF switch and the battery pack s LEDs will initially al...

Страница 21: ...a load that might be connected to the other output NOTE that disconnecting an input or output power cable while that cable is handling power will likely cause an arc to form as the terminals are pulle...

Страница 22: ...not otherwise maintain its specified maximum temperature for its internal circuitry the fans will be driven at a speed that exceeds their rated long term running speed There is an LED on the front pan...

Страница 23: ...Indication Green UPS is Running Outputs are Enabled Amber UPS is on Standby Outputs are Enabled Red UPS has a Fault Condition Off UPS is Off LEDs on the Battery Packs Each battery pack has 16 LEDs as...

Страница 24: ...Source of Power Amber Input has Returned within Range and Diagnostic Tests are Being Performed Off Input is Not within Range Or the DC INPUT Option is not Installed Power Out Indicators LEDs in positi...

Страница 25: ...reen B3 Off Total Load Power 75 B0 B1 B2 Green B3 Dimmed Green Total Load Power 100 B0 B1 B2 Green B3 Blinking Red Total Load Power 100 Battery State of Charge Indicators LEDs in positions E0 E3 The L...

Страница 26: ...S Temperature Fans Running at 100 Red Maximum UPS Temperature Fans Running at 110 Battery Pack Temperature Indicator LED in position F1 The LED in position F1 indicates the temperature of the battery...

Страница 27: ...Recently Had Degraded Performance and Diagnostic Tests are Being Performed Red One or All Fans Presently Have Degraded Performance Battery Pack Service Required Indicator LED in position C1 The LED i...

Страница 28: ...Both Battery Packs and the Remaining Charge of at Least One Pack is 10 Hot Swapping the Battery Packs The battery packs can be removed from and reinserted into the UPS without disrupting the delivery...

Страница 29: ...acks installed has been qualified to the following requirements of MIL STD 810G MIL STD 810G Test Method Name Procedure Details 500 5 Low Pressure I II and III 18 000 ft operating 40 000 ft storage 50...

Страница 30: ...ith redundant parallel units in multi unit systems Ordering Information Standard Vs Redundant Parallel AC Output Neutral Wire option Example PN Single Unit no paralleling G UPS 1500 S 1U W1GS00 ECE St...

Страница 31: ...witch on or by sending the appropriate signal over the USER I O cable If any UPS unit is off all of the UPS units will disable their outputs If any UPS unit cannot deliver output power because it cann...

Страница 32: ...USER I O cables Sending a OUTPUT DISABLE command to a UPS will cause only that UPS to be disabled Other UPS units in the system will continue running Sending a SYSTEM DISABLE command over the RS 232...

Страница 33: ...phase systems redundant 3 phase systems or redundant single phase systems with more than three units Parallel Connection of the AC Outputs Two or three SynQor UPS units can have their AC OUTPUTs conne...

Страница 34: ...redundant parallel the wiring diagram for the AC OUTPUT cables and the CONFIGURATION cable is shown below L1 N PEGND L1 N PEGND L1 N PEGND CONFIGURATION cable SYN 9315 or SYN 9343 AC OUTPUT AC OUTPUT...

Страница 35: ...ally hot meaning at a high potential relative to the neutral or PEGND One will be phase shifted by 180 degrees one half cycle from the other meaning that when one hot wire is at its positive peak the...

Страница 36: ...AC OUTPUT cable all the cable sections should have the following minimum wire size depending on whether the AC OUTPUT of the individual UPS units is 115 Vac or 230 Vac UPS AC Output Voltage Cable Mini...

Страница 37: ...hat configuration cables for two unit and three unit single phase systems are offered as standard products See the previous pages for part numbers Line 1 UPS Unit 1 0 Line 2 UPS Unit 1 180 Line 1 UPS...

Страница 38: ...ed to sources of power They could be connected to the same AC and or DC source respectively They could be connected to different AC and or DC sources respectively All that is necessary is to ensure th...

Страница 39: ...e e g no AC or DC input and depleted battery the combined AC output will shutdown Multi unit AC Output On Off Control Expanded Parallel R option For expanded parallel multi unit operation any on front...

Страница 40: ...s into multiple segments is to allow the battery pack to remain useful even if one of its battery cells fails In a normal battery configuration the failure of a single cell would disable the entire ba...

Страница 41: ...battery pack fits into the 2U high UPS 3000S unit Two battery packs are required for proper operation of the UPS 3000 Storage of the Battery Pack The storage temperature range of the battery pack whe...

Страница 42: ...this chassis and the exposed power terminal strip is not subjected to extreme mechanical shock or to excessive moisture UPS battery packs must be shipped per Federal DOT Regulations as a Class 9 Full...

Страница 43: ...optional connection to a host system computer so that it can control the UPS and receive information regarding the status of the UPS The Configuration male DB15 connector on the right is for a connect...

Страница 44: ...8 2N3904 Input Pin 50k Ohms 100 Ohms 5V 500 Ohms PS2581L 1N4148 I O Circuits OUTPUT ON OUTPUT OFF 5V Pin SHUTDOWN Input Pin Remote On Off Switch SPDT Momentary ON OFF ON 100 Ohms 5V 8 500 Ohms 13 PS25...

Страница 45: ...ollector output where low indicates the UPS is drawing power from its battery OUT_OK 14 Open collector output where low indicates AC Output voltage is within range OVER_TEMP 15 Open collector output w...

Страница 46: ...carriage returns with line feeds and use local echo UPS 3000 S 2U with DC Input DC1 Output Options Exhaust Fans DC1 Output Option AC Output Ethernet Port Option User I O CONFIG Port Ground Stud 1 4 2...

Страница 47: ...pdf Ethernet Interface The optional Ethernet interface provides a web page based user interface for monitoring and control of the UPS The user can configure email alerts for UPS alarm conditions The i...

Страница 48: ...n and eyes It may be toxic Always use the proper SynQor battery pack See the battery replacement chart on page 41 Fans The fans on the rear panel have sealed bearings that do not require any maintenan...

Страница 49: ...ed by the user The 16 LEDs on the front panel of the battery pack are the best and first place to look to determine what might be wrong with the UPS The table on the next several pages is therefore or...

Страница 50: ...oltage is either too low or too high The DC INPUT cable may have too much series resistance Thicker wire should be used A1 AC OUTPUT Power LED LED is OFF The UPS is OFF and needs to be turned ON LED i...

Страница 51: ...o keep the unit cool The maximum recommended temperature may be exceeded but the fans are keeping things cool enough to avoid triggering the over temperature shut down circuitry F1 Battery Pack Temper...

Страница 52: ...The UPS s battery run time will therefore be similarly reduced The battery pack should be replaced at the earliest convenient time All 16 LEDs All LEDs are OFF The battery pack is not fully inserted i...

Страница 53: ...ted to the UPS Or it may happen when the load itself is turned on and or connected to the AC OUTPUT of a UPS that is already running Common examples of such loads are motors and incandescent lights bu...

Страница 54: ...drop from the upstream to the downstream end of the cable This voltage drop if large enough will cause the either UPS to determine that the voltage at its AC INPUT or its DC INPUT is below its minimum...

Страница 55: ...s trying to draw power from the DC INPUT for one minute After this one minute another set of 3 cycles are repeated followed by another stop for one minute and so on This same problem can also occur fo...

Страница 56: ...rade Uninterruptible Power Supply 006 0006504 02 27 18 Rev R 1 888 567 9596 USA only SynQor Headquarters 155 Swanson Road Boxborough MA 01719 1316 USA www synqor com Made in USA Operator s Guide UPS 3...

Отзывы: