DOC-1000512-A-2
Page 3
Wiring Instructions and Wiring Diagram
WARNING: TO AVOID FIRE, SHOCK, OR DEATH: TURN OFF POWER
AT CIRCUIT BREAKER OR FUSE AND VERIFY THAT POWER IS
OFF BEFORE WIRING!
INSTALLATION AC POWER
1.
Connect the electrical service black wire (hot) to the black wire (Line) on the DIM10-220.
2.
Connect the black wire of the LED driver to the red wire (load
)
output on the DIM10-220.
3.
Connect the electrical service white wire (neutral) to the white wire on the DIM10-220 And the neutral wire of the luminaire.
DIMMING CONTROL
4.
Connect the DIM+ wire on the LED driver to the purple wire DIM+ wire on the DIM10-220.
5.
Connect the DIM- wire on the LED driver to the gray wire DIM- wire on the DIM10-220.
SENSOR WIRING
6.
Connect the DIM10-220 blue wire sensor input to the sensor control/output connection of the sensor.
7.
Connect the DIM10-220 white/blue (common) to the Common (ground) connection on the sensor.
8.
Connect the DIM10-220 brown wire (sensor power) to the 24VDC power connection on the sensor.
DIMMING RECOMMENDATIONS
Below are some recommendations for successful dimming using the DIM10-220.
•
Use appropriate gauge wire for the application.
•
Do not ground the DIM- wire. This is a return signal and is critical for dimming.
•
When possible, route dimming wires away from AC lines
Wiring Instructions and Wiring Diagram- (Continued)
FUNCTION
WIRE COLOR
CLASS
LINE / L1
BLACK
CLASS 1
NEUTRAL / L2
WHITE
CLASS 1
LOAD / L1
RED
CLASS 1
DIM +
PURPLE
CLASS 1/2
DIM -
GRAY
CLASS 1/2
+24VDC SENSOR CONTROL
BLUE
CLASS 2
+24VDC SENSOR POWER
BROWN
CLASS 2
SENSOR COMMON
WHITE/BLUE
CLASS 2
Note: External Surge is
not provided, but
highly recommended
10KV or higher