Page | 24
09
Battery backup time setting
Y
Y
Y
Y
Y
Y
10
Reserved
Reserved for future
11
Reserved
Reserved for future
12
Hot standby function enable/disable
Y
Y
Y
Y
Y
Y
13
Battery voltage adjustment
Y
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
Y
15
Inverter voltage adjustment
Y
Y
Y
16
Output voltage calibration
Y
Y
Y
17
Reserved
Reserved for future
Y
means that this program can be set in this mode.
NOTE
:
All parameter settings will be saved only when UPS shuts down normally with internal or
external battery connection. (Normal UPS shutdown means turning off input breaker in bypass
mode)
01:
Output voltage setting.
INTERFACE
SETTING
Parameter 2: Output voltage
For
208/220/230/240 VAC
models, you may choose the
following
output voltage:
208:
presents output voltage is
208Vac.
220:
presents output voltage is
220Vac.
230:
presents output voltage is
230Vac.
240:
presents output voltage is
240Vac.
02:
Output Frequency.
INTERFACE
SETTING
60 Hz, CVCF mode
Parameter 2: Output Frequency
Setting the output frequency. You may choose following
three options in
parameter 2
:
50.0Hz:
The output frequency is setting for
50.0Hz.
60.0Hz:
The output frequency is setting for
60.0Hz.
AT:
If selected, output frequency will be decided
according to the latest normal utility frequency. If it is
from
46Hz to 54Hz,
the output frequency will be 50.0Hz.
If it is from
56Hz to 64Hz,
the output frequency will be
60.0Hz.
AT is default setting.