13
2.
Options:
Press ENTER Button
2.1
Entry of the density measuring range in
50 kg/m³ - steps.
2.2
Entry of the throughput range in 100 kg/m³ - steps.
Final value of measuring range [kg/h] = 20mA
2.3
Entry of the average time for the
velocity (0..120s)
à
Damping of the signal
2.4
Entry of the average time for the
density (0...120s)
à
Damping of the signal
2.5
Entry of the pipe diameter in mm.
Necessary for the correct calculation
of the quantity.
2.6
Entry of the correction factor for the
throughput (0.1...10)
Here the value received can be corrected
lateron by changing the preset value to 1.
2.7 Send
parameter
By pressing YES the parameters factor correction,
throughput range, density measuring range will be
send via RS485 interface to all connected instruments
2.8 Select
Language
between German and English
OPTIONS
Density Range
= 800 [Kg/m³]
Average D
= 10s [ 25 ]
Average V
= 10s [ 25 ]
Correction Factor
= 1.0
Pipe Diameter
= 32.0 mm
Throughput Range
= 20000 Kg/h
Parameter send
= No / Yes
Language
English