1
Revision A.00
FanSet
OPERATION AND
MAINTENANCE
www.swissrotors.com
Страница 1: ...1 Revision A 00 FanSet OPERATION AND MAINTENANCE www swissrotors com ...
Страница 2: ... 6 2 3 Operationallimits 6 2 4 Serial number identification 7 2 5 Air Volume measuring 7 3 TRANSPORTATION 9 3 1 Packing 9 3 2 Quality control 9 3 2 1 Examine the package 9 3 2 2 Examine the unit 9 3 3 Storage 9 4 INSTALLATION MOTORCONNECTION 10 4 1 Generalsafety 10 4 2 Productdescription 10 4 3 Technical specifications 11 4 4 Connection Diagrams 13 4 5 Communication 16 4 5 1 Analog input 16 4 5 2 ...
Страница 3: ...trical Voltage Important Information Useful Hint Please read carefully the entire user manual and all other accompanying documents before first start up Improper use of the product may void the warranty Keep it as a reference for future maintenance and service procedures 1 2 Disclaimer The following instruction unless otherwise stated applies to all Swiss Rotors FanSet units In exceptional circums...
Страница 4: ...comes in few configurations Tab 1 All FanSet s are statically and dynamically balanced before shipment For balancing are used special balancing weight In first step the FanSet is mounted into balancing machine At the next step balancing of the fan needs to be performed by glued of the balancing weight Fig 2 Mounting location of the weights will be displayed on the screen FanSet is balanced and rea...
Страница 5: ...5 Revision A 00 Figure 1 FanSet SR190 Series left and FanSet SR225 250 315 Series right Figure 2 Balancing weight Figure 3 Swiss Rotors FanSet overall dimensions ...
Страница 6: ...that the centrifugal effect increases the pressure and power of the fan Ventilating cone of dedicated diameter is mounted on the opposite side All parts are made of high quality materials Fig 4 presents the principle operation of the FanSet inside the Air Handling Unit It is crucial to note that exhausting airstreams are directed perpendicularly to the fan axis Fig 5 Figure 4 FanSet s inside AHU F...
Страница 7: ... Size Nominal size of fan impeller Serial number A set of characters that uniquely identifies a single unit and can be used for traceability and warranty purposes Quality check date Date of checking and approval of correct operation of the device QR Code Unique code to call a service Table 2 Identification label explanation 2 5 Air volume measuring FanSet units are equipped with the inlet cone Air...
Страница 8: ...pe of fan is deviation of the airflow smaller than 10 This factor is determined by comparative measurement on a standard test rig For Swiss Rotors FanSet s the calculated K factor s have the following values FanSet SR190 k10 36 FanSet SR225 k10 49 FanSet SR250 k10 56 FanSet SR315 k10 105 ...
Страница 9: ...cept the parcel 4 Check if the received parcel matches with your order Inspect the product identification label plates for confirmation 5 In case of noticing any damage please contact our support immediately phone numbers are listed at the Support chapter of this guidebook or at our official website www swissrotors com 3 2 2 Examine the unit 1 Remove packing materials from the product 2 Dispose al...
Страница 10: ... may result in fatal injury caused by electric shock If it is necessary to open the motor wait at least 5 minutes after disconnecting from the power supply NOTE It is the user and the installer responsibility to provide the system with the proper grounding and protection in accordance with national and local standards Swiss Rotors is not responsible for any damages or injuries caused by incorrect ...
Страница 11: ... Nm 725W 4500 rpm 0 10VDC Modbus RTU 250 to 600 54 SR225 07 UL EC102 35E3G 01 02 UL 110 240V AC 50 60Hz 3 2A 230VAC 1 56 Nm 725W 4500 rpm 0 10VDC Modbus RTU 250 to 600 54 SR250 07 EC102 35E3G03 04 230V AC 50 60Hz 5 1A 1 76 Nm 700W 3800 rpm 0 10VDC Modbus RTU 250 to 600 54 SR250 07 UL EC102 35E3G 01 03 UL 110 240V AC 50 60Hz 3 7A 230VAC 1 76 Nm 700W 3800 rpm 0 10VDC Modbus RTU 250 to 600 54 SR315 0...
Страница 12: ...05 78 SR225 03UL EC092 25EF3G 03 02 UL 1 2 2214 0188 105 78 SR250 03 EC092 25E3G01 04 1 2 2214 0184 105 78 SR250 03UL EC092 25EF3G 03 03 UL 1 2 2214 0190 105 78 SR315 03 EC092 35E3G01 03 1 2 2214 0186 116 88 SR315 03UL EC092 35EF3G 01 02 UL 1 2 2214 0192 116 88 SR225 07 EC102 35E3G03 03 1 2 2214 0183 131 5 88 SR225 07UL EC102 35E3G 01 02 UL 1 2 2214 0189 131 5 88 SR250 07 EC102 35E3G03 04 1 2 2214...
Страница 13: ...fter disconnecting from the power supply Notes on proper installation Use fuses at power line Check the wires condition before operating Make sure that there are no short circuits Use cables fulfilling the voltage current load and insulation installation requirements Use only high quality hard wire or fiber copper wire with ferrule Use shield cable Make sure that motor label plate specification ma...
Страница 14: ...14 Revision A 00 Figure 11 EC169W B190 44P1 05 CONNECTION DIAGRAM Figure 12 Wires and factory connectors EC169W B190 44P1 05 ...
Страница 15: ...15 Revision A 00 Figure 13 EC092 series and EC102 series CONNECTION DIAGRAM Motor EC092 series and EC102 series ...
Страница 16: ...nd control methods are presented below 5 5 1 Analog input AN1 Analogue input 1 Electronics can be controlled by external analogue input voltage 10 0 VDC Electronics controls speed linear from RPM min to RPM max Maximal or minimal speed is defined as input voltage 9 5V 3 AN1Min parameter can be set to the desired minimum setpoint AN1Max parameter can be set to the desired maximum setpoint AN1Min an...
Страница 17: ...ets are generated by the master Controller which periodically polls all connected slave devices Data travels over the single line in both directions Multiple EC drives can be connected to a control or master using the RS 485 standardized interface Maximal number of Compacto EC Drives connected to the network is 32 Use parallel connections method to connect multiple frequency converters To connect ...
Страница 18: ...verter too hot to operate 0 10 I2R IGBT Fault 0 1 1 Software IGBT protection triggered 0 13 lis RESERVED 0 14 Restart Fault 0 1 1 Fault condition repeated several times in a short time Converter power should be power cycled or reset 0 15 RESERVED 0 16 17 RESERVED 0 18 Waiting To Stop 0 1 1 Motor should be stopped but is still spin ning 0 19 23 RESERVED 0 24 RpmReg 0 1 Speed regulator active 0 25 P...
Страница 19: ...t 2 MODBUS Speed 0 7 Modbus Address 1 247 Set Modbus address Write 10000 to Password to save Restore by writing to broadcast address 0 in case you forgot address 1 8 MODBUS connection detection 0 1 Detection MODBUS connection loos 1 MODBUS disconnection ignored 0 MODBUS disconnection used for motor stop 0 9 MODBUS connection detection timeout 0 65536 s timeout to stop motor after loose connection ...
Страница 20: ...ator IRMS RMS Stator current in A 0 0 001 8 Power W 0 0 1 9 Analogue1 300 2000 Analogue input 1 voltage 0 0 01V 19 Error Code 0 7 7 motor failed to start repeatedly 6 under or overvoltage 5 motor misconnected faulty 4 internal frequency converter fault 3 temperature protection active 2 active overcurrent protection 1 slow blink standby 0 always on operating normally 0 20 21 RESERVED 0 23 Op Minute...
Страница 21: ...e There are no traces of rust There are no unwanted objects inside the casing which are not internal fan parts The impeller rotates without rubbing against other elements The impeller has no undesirable vibrations during operation There are no unwanted objects inside the casing which are not internal fan parts Fixing bolts are firmly tightened The fan blades are not damaged there are no cracks Eng...