4. Function
The hand-held micro terminal has a display screen with
eight lines, a navigation knob and two LEDs.
Scrolling up and down in the menu is done by turning
the adjusting knob on the hand-held micro terminal, and
selections are entered by pressing on the adjusting knob.
Modification of the selected values is done by turning the
adjustment knob. Select "Exit" to leave the menu.
The hand-held micro terminal communicates with the
motor control system via Modbus commands. Factory
and user settings are stored in the control system. The
settings are preserved in the memory even if the line
voltage is switched off or if the hand-held micro terminal
is removed.
The mortor control system's function selector switch
should normally be set to Position 1, but for communica-
tion with the hand-held terminal, the function selector
switch should be set to Position 0.
The possible settings and displays are shown in the table
on the next page.
Note that you must enter a PIN code in order to open the
Config menu and in this way be able to make changes in
the motor control system configuration. Contact Swegon
to obtain a PIN code.
Table:
MAIN MENU
SETTINGS
DESCRIPTION
VALUE
Status
Operation
With the Hand-held micro terminal set to the "Modbus" mode, set "Start/Stop in" in the "Start/
Stop"/"Control" menu.
Start/Stop
Set Setpoint
With the Hand-held micro terminal set to the "Modbus" mode in the "Start/Stop"/"Control" menu, set the
required set point in the DV in %.
With the Hand-held micro terminal in the "0-10VDC" mode in the "Start/Stop"/"Control" menu, read the
current setpoint in %.
0 - 100%
% Out
Shows the current speed of rotation as a percentage of the range (See Section 10).
0 – 100 %
Rpm Out
Shows the current speed of rotation
PM: 0 - ?* rpm
Power
Shows current input power
0 - ?* kW
Analogue_In 1
Shows the current voltage on the external input for adjustments
0 - 10.0 V
Digital_In 1
Shows current status
"LO" = Active
"HL" = Inactive
Digital_In 2
Shows current status of Alarm reset
"LO" = Active
"HL" = Inactive
Digital_In 3
Shows current status of the Firemode jumper.
"LO" = Jumper connected
"HL" = Jumper discon-
nected
Op. time
Shows the current operating time as number of days.
0 - ? days
Op. time
Shows the current operating time in minutes.
0 - ? minutes
I out
Shows present output current
0 -?* A
V in RMS
Shows current input voltage
0 - ?* V
Temp.
Shows the current temperature inside the control system.
? - ? °C
FIREMODE
Activate the Fire mode. "Fire" from the hand-held micro terminal or external input have higher priority than
"Normal".
Important! For high internal temperature inside the DV control system, the display window backlight is
turned off when "Fire" is active.
Fire /
Normal
Exit
Return to the Main menu.