The hand-held micro terminal has a display screen with 
eight lines, a navigation knob and two LEDs.

Scrolling up and down in the menu is done by turning 
the adjusting knob on the hand-held micro terminal, and 
selections are entered by pressing on the adjusting knob. 
Modification of the selected values is done by turning the 
adjustment knob. Select "Exit" to leave the menu.

The hand-held micro terminal communicates with the 
motor control system via Modbus commands. Factory 
and user settings are stored in the control system. The 
settings are preserved in the memory even if the line 
voltage is switched off or if the hand-held micro terminal 
is removed. 

The mortor control system's function selector switch 
should normally be set to Position 1, but for communica-
tion with the hand-held terminal, the function selector 
switch should be set to Position 0.

The possible settings and displays are shown in the table 
on the next page. 

Note that you must enter a PIN code in order to open the 
Config menu and in this way be able to make changes in 
the motor control system configuration. Contact Swegon 
to obtain a PIN code.

Table:

MAIN MENU

SETTINGS

DESCRIPTION

VALUE

Status

Operation

With the Hand-held micro terminal set to the "Modbus" mode, set "Start/Stop in" in the "Start/
Stop"/"Control" menu.

Start/Stop

Set Setpoint

With the Hand-held micro terminal set to the "Modbus" mode in the "Start/Stop"/"Control" menu, set the 
required set point in the DV in %.
With the Hand-held micro terminal in the "0-10VDC" mode in the "Start/Stop"/"Control" menu, read the 
current setpoint in %.

0 - 100%

% Out

Shows the current speed of rotation as a percentage of the range (See Section 10).

0 – 100 %

Rpm Out

Shows the current speed of rotation

PM: 0 - ?* rpm

Power

Shows current input power

0 - ?* kW

Analogue_In 1

Shows the current voltage on the external input for adjustments

0 - 10.0 V

Digital_In 1

Shows current status

"LO" = Active
"HL" = Inactive

Digital_In 2

Shows current status of Alarm reset

"LO" = Active
"HL" = Inactive

Digital_In 3

Shows current status of the Firemode jumper.

"LO" = Jumper connected
"HL" = Jumper discon-
nected

Op. time

Shows the current operating time as number of days.

0 - ? days

Op. time

Shows the current operating time in minutes.

0 - ? minutes

I out

Shows present output current

0 -?* A

V in RMS

Shows current input voltage

0 - ?* V

Temp.

Shows the current temperature inside the control system.

? - ? °C

FIREMODE

Activate the Fire mode. "Fire" from the hand-held micro terminal or external input have higher priority than 
"Normal".
Important! For high internal temperature inside the DV control system, the display window backlight is 
turned off when "Fire" is active.

Fire /  
Normal

Exit

Return to the Main menu.