5. Electrical connections

Connect the hand-held micro terminal to contact "C" in 
the junction box (installed on the side of the fan mounting 
frame) via a bus cable (cable type MPFK6S or the like) with 
an RJ12/6-connector at both ends, see figures below. 

Same order of colours

6. Indications, LEDs

The hand-held micro terminal has two integrated LEDs 
(See figure) with the following function:

Steady 

glow

Flashing

Red LED

-

Alarm active

Green LED

OC

Oversteering with hand-held 

micro terminal.

OC

(green)

Alarm
(red)

7. Alarm

For particulars of current alarms, see table in Section 4.

Alarms are reset automatically if the fault ceases to exist 
and the EC control system starts up again. 

If the maximum number of restarts has been exceeded the 
resetting of alarms can take place by selecting "Reset 
Alarm" in the alarm menu. As an alternative, the "Alarm 
Reset" input can be short-circuited (Terminal 11 (Alarm 
reset) and 12 (   ) in the junction box) or the line voltage 
to the EC control system can be replaced.

8. Trouble shooting

Symptoms

Cause

Action

No values in the hand-held 

micro terminal 

– Display window off

The EC control system is switched off

Start the EC control system

Modbus cable is defective

Repair or replace the Modbus cable

Incorrectly set baudrate, communication speed

Set the function selector switch in the junction box to posi-

tion ”0”  

(See Section 4)

The RJ12 connector is not correctly connected

Check the contact connections in both the hand-held micro 

terminal and in the junction box.

In the junction box the contact ”C” should be used for con-

nection of the hand-held micro terminal.

Both the RJ12 connectors are active and can be used in the 

hand-held micro terminal.