Table:

MAIN MENU SETTINGS

DESCRIPTION

VALUE

Status

Set Setpoint

With the Hand-held micro terminal set to the "HTERM" mode in the "Start/Stop"/"Control" menu, set the required 
set point in the EC in %. With the Hand-held micro terminal in the "0-10VDC" mode in the "Start/Stop"/"Control" 
menu, read the current set point in %.

0 – 100 %

% Out

Shows the current speed of rotation as a percentage of the range (See Section 11).

0 – 100 %

Rpm Out

Shows the current speed of rotation

0 - ?* min-1

Power

Shows current input power

0 - ?* kW

External Set

Shows the current voltage on the External setting input

0 - 10.0 V

External STOP

Shows the current status on the ON/OFF input, Terminals 7 and 8.

”1” = Stop /  
”0” = Start

External FIREMODE

Shows the current status on the fire input, Terminals 9 and 10.

”1” = Normal /  
”0” = Brand

Op. time

Shows the current operating time as number of days.

0 - ? days

Op. time

Shows the current operating time in minutes.

0 - ? minutes

I out

Shows present output current

0 -?* A

V in RMS

Shows current input voltage

0 - ?* V

Temp.

Shows the current temperature inside the control system.

? - ? °C

Exit

Return to the Main menu.

Start/Stop

Operation

Start/Stop the motor

Stop/Start

Control

Selection of control signal

Control = HTERM 

EC is controlled from the hand-held micro terminal. 
External signals are ignored, including: 
Start/Stop on Terminals 7 and 8 (ON/OFF).
The fire signal on Terminals 9 and 10 (Firemode) as well as the external control signal on Terminals 13 and 14 (0 – 10 V in).

Control = 0-10 V DC

EC is controlled from external control signals, including:
Start/Stop on Terminals 7 and 8 (ON/OFF).
The fire mode signal on Terminals 9 and 10 (Firemode) as well as the external control signal on Terminals 13 and 14 (0 – 
10 V in).
External stop and stop from the hand-held micro terminal have higher priority than start from the hand-held micro 
terminal.

HTERM / 0-10 V DC

FIRE

Activate the Fire mode. "Fire" from the hand-held micro terminal or external input have higher priority than "Nor-
mal". Important! For high internal temperature inside the EC control system, the display window backlight is turned 
off when "Fire" is active.

”1” = Fire /  
”0” = Normal

Exit

Return to the Main menu.

Alarms

Reset Alarm

Is activated in order to reset alarms when the maximum number of restarts has been exceeded.

Alarm stop

Shown when the motor has stopped due to an alarm.

Voltage low

Shown when an alarm has been initiated due to excessively low line voltage.

Voltage high

Shown when an alarm has been initiated due to excessively high line voltage.

Phase error

Shown when an alarm has been initiated because one line voltage supply phase is missing.

Current high

Shown when an alarm has been initiated due to excessively high output current.

Current limiting

Shown when an alarm has been initiated because the current limiting function is active (e.g. if the ramp time is 
excessively short or if the motor is overloaded).

I ripple

Shown when an alarm has been initiated due to unstable line voltage.

Temperature high

Shown when an alarm has been initiated due to excessively high temperature in the frequency inverter.

Rotor Blocked

Shown when the rotor is blocked.

Internal error

Shown when an alarm has been initiated due to an internal fault inside the frequency inverter.

EC com. error

Internal communication error between the junction box and the EC- control system.

Exit

Return to the Main menu.

Edit setup

Min. rpm

Setting of the lowest speed of rotation (See also Section 11).

0 - ?* min-1

Max. rpm

Setting of the highest speed of rotation (See also Section 11).

0 - ?* min-1

Up Ramp

Setting of the ramp up time (See also Section 10).

0 - ?* s

Down Ramp

Setting of the ramp down time (See also Section 10).

0 - ?* s

Switch Hz

Setting of the switching frequency on the output.

Auto, Low, High

Exit

Return to the Main menu.

Modbus

Address

Setting of the Modbus address display.

Baudrate 

Setting of the baudrate display.

4 800, 9 600,19 200, 
38 400, 57 600, 
115 200 Bps. 

Parity 

Setting of the parity display.

None/Odd/Even 

Stop bits 

Setting and display of stopbits.

None/1/2

Exit

Return to the Main menu.

About EC

SLAVE ADDRESS

Status of the EC control system's internal address.

EC type

Status of the type of EC control system. 

1000- ?*

FC SW ver.

Status of the EC control system's program version.

I/O SW ver.

Status of the I/O module's program version.

Boot SW ver.

Status of the EC control system's boot program version.

Term SW ver.

Status of the hand-held micro terminal's program version.

Exit

Return to the Main menu.

 *= Depends on size of the connected control system