GB.GOLDSKFPX.210324
We reserve the right to alter specifications.
www.swegon.com 21
6.3.3.2 Size 014-040
Shows the motor protection switch and safety isolating switch for different combinations of fan sizes and capacity variants. Fan A or B
can be a supply air fan or an extract air fan or vice versa.
The air handling unit’s rating plate shows the combinations of fan sizes and capacity variants.
GOLD PX, size
Fan combination
Internal motor protection
switch (A)
Fan A, size/
capacity variant
Fan B, size/
capacity variant
Fan A
Fan B
Safety
isolating
switch (A)
014/020
14-1
14-1
6.3
6.3
25
14-1
14-2
6.3
6.3
14-1
20-1
6.3
6.3
14-1
20-2
6.3
7.0
14-2
14-2
6.3
6.3
14-2
20-1
6.3
6.3
14-2
20-2
6.3
7.0
20-1
20-1
6.3
6.3
20-1
20-2
6.3
7.0
20-2
20-2
7.0
7.0
025/030
25-1
25-1
10.0
10.0
25
25-1
25-2
10.0
10.0
25-1
30-1
10.0
10.0
25-1
30-2
10.0
10.6
25-2
25-2
10.0
10.0
25-2
30-1
10.0
10.0
25-2
30-2
10.0
10.6
30-1
30-1
10.0
10.0
30-1
30-2
10.0
10.6
30-2
30-2
10.6
10.6
035
035-1 (4.0 kW)
035-1 (4.0 kW)
10.0
10.0
40
035-2 (5.0 kW)
035-2 (5.0 kW)
10.6
10.6
040
040-1 (6.5 kW)
040-1 (6.5 kW)
13.2
13.2
40
040-2 (10 kW)
040-2 (10 kW)
18.0
18.0
63