6.3 Electrical Data
6.3.1 Air Handling Units
6.3.1.1 Size 004-012
MIN. POWER SUPPLY
GOLD 004:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 005, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 005, capacity variant 2:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 AT
or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 007, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT
or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 007, capacity variant 2:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 AT
or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 008, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 AT
or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 008, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 011, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 AT
or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 011, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 012, capacity variant 1 and 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT