GB.ELQZ428.050101

Specifications are subject to alteration without notice.

www.swegon.se     3

IMPORTANT!
The arrow on the plastic cover must 
point in the same direction as that of 
the air flowing through the duct.

1

2

Drill an opening in the duct.          • 35 mm dia. opening for smoke detector without mounting bracket.
   

 

                

• 50 mm dia. opening for smoke detector with mounting bracket (see item 10).

3

Do not cut this end!

• Measure the ventilation duct.
• Cut the tube to an appropriate length, if needed.
• The tube should penetrate 90% of the duct diameter        
   into the duct.
• Insert the end plug.

End plug.

• Lock the tube in 
position by means 
of the stop screw.

• Slip the seal onto the tube.
• Insert the tube in the bottom of the  
   detector housing.

4

• Mount the tube and the detector on the duct.
• Secure the detector housing at the 3 points indicated by      
the arrows.

Содержание GOLD ELQZ-2-428-2

Страница 1: ...tor transmits an alarm signal to the con trol unit Any accumulation of impurities in the smoke detector will make it more sensitive and gradually approach its alarm condition To avoid unnecessary alarms caused by fouling the detector is equipped with a service alarm green LED When lit this LED indicates that the detector ought to be cleaned Tecnical details Type of detector Ionising Power supply 2...

Страница 2: ...conden sation inside the detector housing To ensure satisfactory smoke detection the smoke detector should be located at a distance in the direction of airflow that is equivalent to at least 3 x the hydraulic diameter of the duct upstream of the nearest source of disturbance in the ducting see the examples of sources of disturbance below If it is located downstream of the nearest source of disturba...

Страница 3: ...m dia opening for smoke detector with mounting bracket see item 10 3 Do not cut this end Measure the ventilation duct Cut the tube to an appropriate length if needed The tube should penetrate 90 of the duct diameter into the duct Insert the end plug End plug Lock the tube in position by means of the stop screw Slip the seal onto the tube Insert the tube in the bottom of the detector housing 4 Moun...

Страница 4: ...sable to consider relocating the detec tor 6 Insert the block 7 Electric wiring Connect the electric wiring as shown in the wiring diagram If only one smoke detector is connected to the system install the final resistor 2 2kΩ in this detector If several smoke detectors are to be connected to one control unit wire the final resistor 2 2kΩ in the last detector in the loop Fit only one resistor per loo...

Страница 5: ...era tes correctly Expose the detec tor to smoke from a match or a suitable spray for testing smoke detectors Secure the cover by means of screws Fit the cover on the detector Do not drill any holes in the plastic cover for fitting identification plates or the like Doing so will cause leakage which will seriously impair detector performance ...

Страница 6: ...n no smoke is present The smoke detector has been located where condensa tion can form inside it such as outdoors in a cold attic a kitchen or the like An alarm is indicated by the control unit only Measure the resistance of the loop 2 2kΩ from the control unit Check that the control unit is OK by wiring the final resistor to the smoke detector output on the control unit Use a voltmeter to check th...