24
Manufacturer reserves the right to alter specifications
Manual stop
• Hold both comfort panel - buttons for about
5 seconds to turn off the unit. Stop fun-
ction can also be connected via an external
switch, see page 14. Wait 5 minutes until the
unit stops.
• Pull the plug before opening the unit.
Alarm
The control system monitors the unit’s functions.
An emergency number is displayed on an ac-
tion, implausible values .
Alarm 12
• When there is a month left to change the
filter, alarm LED flashes. Drift diod is green.
• On reaching time for filter change lights both
the alarm (red) and drift diod (green) steady.
• If the filters are not replaced by another
month the unit stops. The alarm LED is lit
(red) and drift diod off.
Stop & Alarm
Stop sequence of unit
Stopping the unit with electric heater
Warning
• Note that the unit stops rotating parts a
while after the unit have been made power-
les.
Manual stop: hold
- buttons simultan-
eously for about 5
seconds
Comfort panel will now display the alarm 13
(external stop). To start the unit again,reset the
alarm by pressing and holding fan of regulation
+ and - buttons for 5 seconds, see picture on
the right. Power failure reset the alarm automa-
tically.
Emergency stop of unit
Comfort panel displays alarm 1 (emergency
stop triggered). All functions are stopped without
delay!
This function can be activated by external wiring
of emergency stop. (Normally, this function is
bridged on delivery). Check electric heater over-
heating protection as no cooling is done. Check
reason of stop!