CCO 

kit

Technical/mechanical design

Characteristics & advantages

The flow sound from the valve is very low, lower than for 
traditional valves of the same dimension. 
The design means that heating and cooling can never be 
run simultaneously, but both circuits will be in contact 
with one another which means that a very minute volume 
of heated water and chilled water will be exchanged 
when the valve switches between heating and cooling. 
It is important that systems are designed to be able to 
handle the system liquid moving between the cold and 
hot system.

Adjustment of the Kv-value

Kv-values can be set for cooling and heating using sepa-
rate adjustment screws. 
Turn the screw clockwise to its stop position, then open 
it a number of turns in order to achieve a specific Kv-value

Kv-value

Number of turns that the adjustment screw is open

A

B

C

D

E

F

G

H

Turns

0.5 turn

0.75 turn

1 turn

1.25 turn

1.5 turn

2 turns

3 turns

4 turns

Kvs m

3

/h

0.042

0.072

0.116

0.171

0.24

0.327

0.6

0.9

A      B      C       D    E     F         G      H

Example:

In a typical case, a flow of 144 l/h is 
required to obtain correct capacity in 
the cooling case, and a pressure drop 
of 10 kPa across the valve is desirable 
to obtain good regulation.
In the diagram (see red marking), you 
can see that this is achieved at the 
preset Kv-value between F and G, i.e. 
the screw should be opened approx. 
2.5 turns, see Table above.