background image

W5 

Smart

14

All rights to changes reserved.

2020-11-19

Summer mode

Mode
Fresh air limit
Fresh air start limit

5°C

User

14°C

Room temperature start limit

Off

Supply air temperature min.
AC boost
Room temperature boost limit

User

14°C

22°C

Hood boost

Use in away mode

 

Outdoor air limit

 determines at which outdoor air 

temperature the function is permitted. 

Outdoor air start 

limit

 determines the need of cooling. 

If you select “Room air temperature limit”, the need 
of cooling is determined by the room air’s temperature 
exceeding the 

Room temperature start limit

. The supply 

air limit determines the supply air’s minimum tempera-
ture. If you change the value, you must take the risk of 
condensation on the pipes into consideration.

By changing the value 

Boost limit value room temp.

 dur-

ing 

AC boost

 you can determine at which room tem-

perature the ventilation shall start to variably boost. 

Selecting 

Hood boost

 allows you to operate the damper 

on a compatible cooker hood to the open position to 
boost cooling. 

Selecting

 In use in Away mode

 allows you to determine 

whether ventilation boosting will be permitted in Away mode. 

3.3.3 Cooker hood function

The cooker hood function balances the ventilation when 
the cooker fan is used to help prevent excessive negative 
pressure and improves fume extraction capability of the 
cooker hood. This function enables you to boost the venti-
lation if necessary. The function starts automatically when 
the damper in a Swegon CASA cooker hood is opened or 
for a cooker hood defined I/O input (IO-control) receives 
the signal and runs until the damper is closed. 

The function is put into service from the 

Settings

/

Smart 

functions/Cooker hood boost menu.

 The settings menu 

is opened when the function is put into service.

Cooker hood function

Home state Compensation
Boost state Compensation

20%

Hood boost

0%

Roof fan

85%

In use

Commissioning mode

Select “Commissioning mode” for air flow settings. This 
activates the signal to be set and the damper is oper-
ated to the open position. 

3.3 Smart functions

The Smart functions can be activated from the control 
panel or via external inputs, or they can act as so-called 
background functions as required. These functions are 
set as needed from the “Smart functions” menu.

Smart functions

Smart functions

Summer mode
Cooker hood function
Central vacuum function
Fireplace function

Auto Home/Away/Boost
Auto RH control
Auto Air Quality control
Temperature boost

3.3.1 Shortcuts

From the “Shortcuts” menu you can set which functions 
are to be visible to the user. When boost is selected, 
boosting is used on all connected sensors.

Smart functions

Fireplace function

Travelling
Central vacuum function
Boost
Summer mode

Temperature boost
Shut down

3.3.2 Summer mode

Summer mode bypasses the ventilation unit’s heat 
exchanger when it needs to cool and the outdoor air is 
colder than the room air. You then get cool outdoor air 
in the room.

The heat exchanger takes care of the cool indoor air 
during hot summer days. The capacity in summer mode 
can be selected from a quick menu, and the ventilation 
unit will then automatically determine the cooling. 

If you wish to set the function’s settings in more detail, 
you select “User” mode on the settings menu.

Содержание CASA SMART W9 Econo

Страница 1: ...W5_e_EN t CASA W5 SMART Installation commissioning and maintenance instruction TECHNICAL MANUAL...

Страница 2: ...l 16 3 3 9 Temperature boost 16 3 4 Heating cooling 17 3 5 Anti frost protection 17 3 6 Restoring factory settings 17 3 7 Changing the service code 17 3 8 Use 17 4 Service 18 4 1 Service reminder 18 4...

Страница 3: ...ct so that the air heater cannot freeze during a power failure and unit freezing pro tection works correctly Condensation The surface temperature of the ventilation unit can drop down to low during pe...

Страница 4: ...lass ISO ePM1 50 F7 and with extract air filter according to filter class ISO coarse G3 The need of filter replacement is indicated on the con trol panel and on a CASA Smart cooker hood 1 4 Heat excha...

Страница 5: ...s and feel a click the overtemperature protection thermal overload cut out has then been reset Ventilation unit with water heated air heater The ventilation unit with water heated air heater has a tem...

Страница 6: ...ntilation unit on a wall by means of a wall mounting bracket which is included in the delivery If the wall is composed of vertical studs and wall boards the wall must be reinforced with horizontal stu...

Страница 7: ...bles through the ceiling mounting frame To make it easier to lift the ventilation unit the inspec tion cover can be removed and the heat exchanger can be dismantled from the unit See the Servicing Sec...

Страница 8: ...sory P05PP for sealing the vapour barrier in the loft ceiling beams Cut up the openings with approx 10 mm smaller diam eter than that of the ducts Secure the mounting frame in the ceiling with screws...

Страница 9: ...accessories are not included in the supply In general ventilation ducts should be insulated in the following manner Insulate outdoor air ducts run through warm spaces Exhaust air ducts should always...

Страница 10: ...ntrol panel can be mounted up to 40 metres from the unit using 2 x 20 metre long modular cables The front panel on the Smart control panel is released using a screwdriver to push the retaining clips t...

Страница 11: ...11 W5 Smart All rights to changes reserved 2020 11 19...

Страница 12: ...ilation unit s fans run at the speed being set and functions that can disrupt the setting such as anti freeze protection are disabled Airflow adjustments Commissioning mode Home exhaust Away supply Aw...

Страница 13: ...ccessory When you connect external equipment to the venti lation unit the function of I O connections must be defined in the menu Setting IO control the standard option is shown in the figure IO contr...

Страница 14: ...d defined I O input IO control receives the signal and runs until the damper is closed The function is put into service from the Settings Smart functions Cooker hood boost menu The settings menu is op...

Страница 15: ...m pensation value so that the air flows are kept as set out in the ventilation plan Compensation boost Fine tune Boost mode s com pensation value if necessary Cooker hood boost Adjust the function s b...

Страница 16: ...rom the Settings Smart Functions Auto air quality control menu NOTE The function is only visible if the sensor has been detected Auto Air Quality control Mode Boost limit Full boost limit 1400 ppm 800...

Страница 17: ...functions menu if the room temperature that is measured with a separate thermometer deviates from the temperature shown by the ventilation unit Important Turning off the internal post heating or lower...

Страница 18: ...ses and filter capacity If an incorrect filter is used it is not cer tain that the ventilation unit will work as designed Check in the list of components that you have selected correct filters 4 4 Hea...

Страница 19: ...Extract air filter 3 Heat exchanger 4 Heat exchanger s sealing plate 5 Condensate discharge 6 Air heater pre heating 7 Air heater reheating 8 Supply air fan s mounting plate behind the air heater pack...

Страница 20: ...eating coil is too high Control air heater fault or overtempera ture protection has tripped Contact a service company Check the function of the air heater for preheating Freeze risk water heated air h...

Страница 21: ...unit so that no uninsulated surface is visible Even a small gap in the insulation could cause among others condensation and acoustic problems 2 Make sure that the pipes connections to the ventilation...

Страница 22: ...changer 61035 8 Cover DW5RL 9 Damper motor 60348 10 Service switch 50319 11 Condensate discharge tube 502103 12 Wall mounting bracket W05WMB 13 Anti vibration mountings 2 pcs 60790 Accessories Smart c...

Страница 23: ...essure differential Pa Supply airflow Extract airflow 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 l s 100 90 8...

Страница 24: ...ans 238 W Air heater pre heating 1500 W Air heater reheating 500 W Total output 2248 W Power consumption 0 50 100 150 200 250 300 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 100 90 80...

Страница 25: ...54 46 27 26 15 0 48 60 67 57 57 50 31 29 18 2 51 70 72 61 62 55 35 34 23 7 56 80 74 63 64 57 37 36 25 9 58 90 75 65 65 58 39 37 26 10 59 100 76 66 67 59 40 38 28 11 61 Sound emitted to supply air duc...

Страница 26: ...od which are sold as accessories 3 External electrical connections See the sec tion Control functions with optional items of equipment 4 Service switch 5 Air heater preheat 1 500 W 6 Air heater reheat...

Страница 27: ...27 W5 Smart All rights to changes reserved 2020 11 19...

Страница 28: ...ATION BUS TERMINATION 3 IO 3 4 IO 4 5 IO 5 6 DDC Out 7 5 V Out 8 GND SEC 16 15 14 3 102TKC 2 x 0 5 IO1 IO5 GND 4 2 1 3 117KHH 2 x 0 5 IO1 IO5 GND 5 1 NC 2 3 NO L N 230V AC 50Hz 105A1 2 x 0 5 2 x 1 5 I...

Страница 29: ...ion points on the ventilation unit IO1 IO2 24 V 5 V selection from circuit board 15 SET module Smart Extension Temperature module connection card for external duct equipment 16 SEC Smart Extension Cab...

Страница 30: ...matic defrost system that prevents the heat exchanger from freezing by enabling the preheater and if necessary by chan ging the fan speed IF THE SAFETY EQUIPMENT TRIPS If an overheating protection wit...

Страница 31: ...0 168 432 630 73 72 951 993 597 630 1 2 3 4 5 1 2 3 4 73 72 5 Duct connections 1 2 3 4 Supply air 160 Extract 160 Outdoor air 160 Exhaust air 160 5 Condensate connection 7 6 Dimensions Left hand model...

Страница 32: ...W5 Smart R 500 W RH CO2 W05VR05S10CAA W5 Smart R 500 W RH CO2 W05VL05S10CAA Econo model available by using external heating duct coil in the supply air duct Sensors and actuator are included in the d...

Страница 33: ...frame R L W05CMB Base W05FMB Water trap UVL Air cooler for cooling the supply air For 160 mm ducts SDCW 160W For 200 mm ducts SDCW 200W For 250 mm ducts SDCW 250F Air heater for heating the supply air...

Страница 34: ...change 0 Cooker hood function boost of cooker hood 0 Fahood function operation of roof fan Not used Central vacuum function compensation 20 Air flows NOTE All the fan modes should be preset Project pl...

Страница 35: ...35 W5 Smart All rights to changes reserved 2020 11 19...

Страница 36: ...viceportal swegon com fi docs TM_W5_SE Installasjons igangkj rings og vedlikeholdsveiledning https serviceportal swegon com fi docs TM_W5_NO Installations Inbetriebnahme und Wartungsanleitung https se...

Отзывы: