Swegon CASA R85 Series Скачать руководство пользователя страница 3

HOME VENTILATION

3

Swegon reserves the right to alter specifications.

www.swegon.com

The R85 wall-mounted in a laundry room.

Figure A.

RECOtite pressure equalizer.

RECOtite

The ratio between the pressure in the outside air and the extract 
air ducts, how clean the filters are, etc. have an effect on the 
pressure differential between the upper and lower top seals at 
the transition point of the rotary heat exchanger. If the pressure 
differential becomes too high, the upper seals will begin to leak 
and the airflows will mix with one another in an undesirable 
way. In ventilation systems where there are low airflows, such 
as in small homes, the pressure differential often becomes too 
high and air inside the ventilation unit begins to leak from the 
extract air section to the supply air section as shown in Figure A.
Normally when airflows are to be adjusted, only the supply 
and extract airflows of the home are measured. If the leakage 
is then too high, the actual outside air flow and the extract 
airflow will deviate from the planned values and the basic 
home ventilation rate may even be as much as 30% less than 
planned. If the air change rate is less than anticipated, the venti-
lation system’s capacity for extracting moisture out of the home 
will not be sufficient to meet the load, and moisture will begin 
to accumulate inside the home. Leakage also has the adverse 
effect that moisture in the extract air is conveyed back into the 
home together with the supply air.
The traditional method used for compensating the pressure 
differential is to increase the pressure in the extract air duct by 
restricting the airflow with a regulating damper. However by 
doing so, the ventilation unit can no longer reach the efficiency 
promised. The airflow often becomes too low, e.g. when it is 
boosted and this radically increases the amount of power con-
sumed by the fan (negatively affecting the SFP value).

A RECOtite

 pressure equalizer equalizes the difference in pres-

sure between the extract air and the supply air sections, and, as 
a result, no leakage flow of air occurs any longer at this point. 
The leakage has been moved to the adjacent top seal, and the 
leakage flow now occurs from supply air to supply air. There are 
also flows below the pressure equalizer in the heat exchanger 
and the heat recovery efficiency is thus not affected.

Содержание CASA R85 Series

Страница 1: ...sound level For installation in a kitchen machine room storage space laundry room etc Can also be located together with a cooker hood at the place intended for a spice rack above the cooker The extra...

Страница 2: ...in the lower speed range The power supply and control cables have quick fit con nectors and the fans can be easily removed from the unit if required Filters The ventilation unit has class F7 fine fil...

Страница 3: ...ilation rate may even be as much as 30 less than planned If the air change rate is less than anticipated the venti lation system s capacity for extracting moisture out of the home will not be sufficie...

Страница 4: ...r programs You can set the desired times if you want the unit to activate a desired function The unit runs in the economical minimum speed mode at other times Away Functions Home Away Boost Cool You c...

Страница 5: ...ing the room when you light the log fire Negative pressure compensation When the cooker hood is in use negative pressure arises in the home since the extract airflow becomes substantially higher than...

Страница 6: ...ed to the unit via a 20 metre long modular cable An extra control panel can also be connected if it is de sirable to control the ventilation unit from several places Front plate of the door The ventil...

Страница 7: ...hoods are sized specifically for connection to the ventilation unit with Premium control engineering If you do not want to connect the cooker hood to a ventilation unit you can select a controllable...

Страница 8: ...good alternative for replacing an old cooker extraction fan with a new one is to install the ventilation unit as you would a wall cabinet on the wall above the cooker by means of the wall mounting bra...

Страница 9: ...l s Thick line SFP 2 0 or lower Extract air flow Available pressure Pa Airflow l s Total output W Airflow l s Power consumption R85 R85 X L Connection 230 V 50 Hz 1 1 A 230 V 50 Hz 3 3 A Fans 238 W 23...

Страница 10: ...17 45 80 59 62 52 45 35 27 20 49 90 60 65 55 48 38 30 23 13 52 100 62 68 57 50 40 32 25 15 55 Sound emitted to extract air duct Acoustic data Fan setting Sound power level broken down into octave ban...

Страница 11: ...26 49 70 61 63 55 50 44 37 30 16 52 80 67 66 59 53 47 40 35 22 56 90 69 69 62 56 49 43 37 26 59 100 70 72 65 59 51 45 41 30 61 Sound emitted to kitchen bypass duct Sound emitted to the surroundings E...

Страница 12: ...ium control panel e g for entering settings or service work Cable with modular connectors Premium control panel R85 Cable with modular connectors Control from a Premium control panel Mains power plug...

Страница 13: ...Alarms Humidity sensor Carbon dioxide sensor temperature sensor Presence detector Misc 4 x 0 5 2 x 0 5 4 x 0 5 2 x 0 5 Modbus RTU See separate instructions E g 6 x 0 5 Example diagram 2 PREMIUM CONTR...

Страница 14: ...sation 2 x 0 5 230 V 10 A 230 V 10 A Modbus gateway W80 EC W100 EC W130 EC W230 EC R85 EC R120 EC Home Away Boost 24 hour weekly timer Fireplace switch Alarm Humidity sensor Carbon dioxide sensor temp...

Страница 15: ...xhaust air 125 Cooker hood s exhaust air 100 Wall mounting bracket 4 1 3 2 K 4 1 3 2 K K K Swegon CASA R85 L Top Bottom Swegon CASA R85 R Variants Right hand or left hand version In order to facilitat...

Страница 16: ...iling wall installation R right hand version PR085RKA L left hand version PR085LKA Mounting frame with moisture barrier PR085YP Water trap UVL Front plate of the front panel Stainless steel PR085B6R F...

Отзывы: