1. General

The BCBB mixing section has three interconnected dampers 
at one level for outdoor air, recirculated air and exhaust air. 
The mixing section has flow-perpendicular dampers with 
counter-rotating  damper  blades  made  of  aluminium-zinc 
coated, double-skin sheet steel, to environment class M3. 
The mixing section offers excellent air mixture with linear 
flow characteristic.

On the size 004-027 units, the damper actuator can be installed 
on the right-hand or left-hand side; on the size 035–055 units, 
it can be installed between the dampers at the centre of the 
mixing section.
The damper blades are journalled in nylon bearings.
The outdoor air damper and the exhaust air damper are coupled 
in parallel. The recirculated air damper pivots in the opposite 
direction. The three damper assemblies are individually adjust-
able for obtaining the appropriate mixing ratio.

1.1 Specification

The  version,  size,  etc.  are  specified  in  the  delivery  docu-
ments.

2. Installation

2.1 Mounting

Fit the mixing section with the damper shafts horizontal.

The BCBB should be connected to the ducting as follows:
a) With BCBZ-1-aaa-18 connection frame

b) With flanged duct

Seal

Slip clamp

BCBZ-1-aaa-16 
Flexible connection

BCBZ-1-aaa--18 
Connection frame

Seal

Pop rivet or
self-tapping screw

Содержание BASIC BCBB 004

Страница 1: ...ight hand or left hand side on the size 035 055 units it can be installed between the dampers at the centre of the mixing section The damper blades are journalled in nylon bearings Theoutdoorairdamperandtheexhaustairdamperarecoupled in parallel The recirculated air damper pivots in the opposite direction The three damper assemblies are individually adjust able for obtaining the appropriate mixing ...

Страница 2: ...s Two of the dampers are interconnected while the thirddamperoperatesindependently Thismeansthatatotal of two actuators are required one actuator operates two dampers and the other operates one damper The torque has been calculated for one damper The size 035 055 mixing sections are equipped with two dampers per opening i e a total of six dampers The two dampers that are located in the same openin...

Страница 3: ...300 1400 60 171 206 020 1946 1026 1359 500 1400 60 239 292 027 2306 1206 1359 500 1700 77 288 353 Sizes 014 027 B H L 103 103 W Q Q ø15 X 3 2 Dimensions Sizes 004 009 B H L 103 103 W Q 103 160 X ø15 BCBB B H L Q W X Weight Std EI 30 004 1039 546 759 200 800 65 84 101 006 1259 656 759 200 1000 55 101 121 009 1459 756 959 300 1000 70 142 173 ...

Страница 4: ...101 Specifications are subject to alteration without notice 4 www swegon se BCBB B H L Q W Weight Std EI 30 035 2706 1406 1559 600 2300 400 479 055 3206 1656 1559 600 2900 462 565 Sizes 035 055 B H L 103 103 W Q Q ø15 ...

Отзывы: