background image

3

Swegon reserves the right to alter specifications. 

20120718 

www.swegon.com

WISE

 

Electrical connections.

All the connections are wired to the CONNECT Adapt junc-
tion box. From there, the Master air diffuser is connected 
by means of the LINK Adapt (RJ45) cable included in the 
delivery. The slave air diffusers, if required, are connected 
by means of the same type of cable to their respective slave 
contacts. If there are more than 2 slave air diffusers, a SPLIT 
Link Adapt should be used for further connection to the last 
slave air diffuser. See Figure 6. If SPLIT Link Adapt is used, 
the maximum length of LINK Adapt from the junction box to 
the last air diffuser is 15 meters. If ADAPT is to be connected 
through Modbus communication, this should be done with 
the LINK Modbus (RJ12) cable. The maximum length of 
SPLIT Link Modbus is 10 meters from the junction box to 
the last air diffuser. Use double CONNECT Adapts if longer 
distances are required. All cables and contacts are different 
so that they will not be confused or incorrectly connected.

Electrical data

ADAPT is supplied with power via the junction box. See 
the wiring diagram in figure 6 or relevant diagram from the 
Swegon Templates application, containing details for the 
specific installation. It is important that cables with appro-
priate cross-sectional area, transformers of correct size and 
power supply cables of correct length are selected. This 
can for example be carried out with the dimensioning tool 
“Cable and Transformer Design”, available for download 
from www.swegon.com (the application is available in 
english and swedish language versions). 
 

Supply voltage

24 V AC ±10 % 

Max. power consumption (controller only)

3 VA

Cable rating (controller only)

0,6 A

Ambient temperature

0 °C - +50 °C

Figure 4. Commissioning with TUNE Adapt.

2

3

1

24 V

Modbus

Figure 5. Air diffuser connections.

1. Connection for LINK Adapt cable (RJ45) 
2. Connection for the LINK Modbus cable (RJ12).

 

3. Direct 24 V connection if a junction box is not used and the air 
diffuser will be completely “stand alone”.