background image

2

Swegon reserves the right to alter specifications. 

20120718 

www.swegon.com

WISE

Maintenance

The exterior surface of the ADAPT air diffusers can be 
cleaned whenever necessary using lukewarm water with 
dishwashing detergent added. Normally the best method 
of cleaning is vacuuming with a brush nozzle. 
The duct system is accessible through the air diffuser and 
the commissioning box. 

Commissioning

All the ADAPT Air terminals are delivered preset into com-
missioning mode, which means that the air diffuser is set to 
max. airflow by force control. 
When the ADAPT air diffuser is in commissioning mode, 
the light-emitting diode shines orange. The different LED 
indications:
•  Steady green LED: Normal operation, the air diffuser is 

operating normally.

•  Flashing green LED: The air diffuser has just been ener-

gised and calibration is in progress.

•  Steady red LED: Function failure, see separate docu-

mentation for TUNE Adapt.

•  Steady orange LED: The commissioning mode, max. 

airflow

•  Flashing orange LED: Other commissioning modes 

and all the forced control situations of the feed-back 
control system. 

More information about the commissioning process itself 
can be read in the Project Manual for the Wise system and 
in the documentation for TUNE Adapt. 

Figure 3. Lighting fixtures or similar objects must not be installed 
beneaht the diffuser as this disrupts the presence detection and  
room temperature measurement.