11
MS-13-PTI-PM-E
Rev 0 6-04-WEL
■
Press button 1 to confirm the selection. The display shows “1.out” again.
■
When pressing button 1 again, the device will display “1.Err” (preferred state of output 1).
■
Use button 2 or button 3 to set the desired initial state in case of an error.
Display
Kind of Output
Note
Off
Inactive in case of an error
Active in case of an error
Low- / High-side switch is opened in case of an error.
Push-Pull output is low in case of an error.
On
Low- / High-side switch is closed in case of an error.
Push-Pull-output is high in case of an error.
■
Press button 1 to confirm the selection. The display shows “1.Err” again.
■
If you selected a 3-point controller, the level 2 settings must be the same as level 1 settings.
“2.dEL” (delay of output 2), “2.out” (kind of output 2), “2.Err” (preferred state of output 2).
■
When pressing button 1 again, (only if you configured the device with min/max alarm), the device will display
“A.out“ (type of alarm output).
■
Use button 2 or button 3 to select the type of alarm output.
Display
Kind of Alarm Output
Note
nPn
Low-Side
NPN, open collector, switching GND
High-Side
PNP, open collector, swiUb
Push-Pull
Switching output is closed (connected to GND) as long there
is no alarm condition and is opened if there is an alarm condition.
PnP
Pu.Pu
Switching output is high with no alarm condition and changes to
low if there is an alarm condition.
Switching output is closed (is under voltage) as long there is
no alarm condition and is opened if there is an alarm condition.
■
Press button 1 to confirm the selection. The display shows “A.out” again.
Depending on the selected output function, you have to make the settings for switching or alarm points.
See description in section “switch points and alarm boundaries” for further information.
Note: The settings for the switching and alarm points can be made later in an extra menu (see Section 5).
Note: The switching outputs are inverted when used as alarm outputs. This means as long there is no alarm condition,
the switching output will be active. In case of an alarm condition, the output will become inactive.
Note: When using the output function “min / max alarm, individual“ the setting for type of alarm output is used for both alarm
outputs.