7. PARAMETER SETTINGS
•
To set the parameters, connect the voltage relay to the mains. The display
will begin counting down the time before the load power is turned on.
•
To enter the parameter setting mode, press the button
«SET»
b
. There will
be flashing «SET HV» symbol and the upper switching-off threshold
value
(
U
H
) in volts on the display
a
.
Set a required value using buttons “
UP
”
c
and “DOWN”
d
. The range of possible values of the
U
H
parameter is 225 to
275 V.
•
Start setting lower switching-off threshold value by pressing the button
«SET»
b
.
There will be flashing
«SET LV» symbol and the upper
switching-off threshold value (U
L
) in volts on the display
a
. Set a required
value using buttons “
UP
”
c
and “DOWN”
d
. The range of possible values
of the
U
L
parameter is 150 to 215 V.
•
Start setting turn-on delay value by pressing the button
«SET»
b
. There
will be the flashing
«SET DS» symbol and delay value (t
d
) in seconds on the
display. Set a required value using buttons “
UP
”
c
and “DOWN”
d
. The
range of possible values of the t
d
parameter is 5 to 999 seconds
.
•
The set parameters will be saved in the voltage relay nonvolatile memory
in 10 seconds after the last button press. You can force to exit the
programming mode by pressing the «ON» button.
•
If you want to connect consumers, bypassing the pause, press and hold
the «ON» button.
ENG
User’s Manual
7
RN-16d