6. CONNECTION
RN-16D
voltage relay is connected to a standard socket of
230
V / 50 Hz
power supply network. The socket must be rated at the current
16 A.
Protected devices are connected to the output socket of the voltage relay.
The voltage relay is designed for operation indoor only. The device ope-
ration is inadmissible in places with high humidity and where ingress of
liquid on its case is possible. Ambient temperature during the voltage relay
operation must
be in the range +10 to +35 °С
.
Before connecting equipment to the voltage relay it is necessary to set
actuation
values, namely, high voltage switching off threshold (U
H
), low
voltage switching
off threshold (U
L
) and turn-on delay time after voltage
normalization of the power supply network (t
d
) (see p. 7). It is recom-
mended to set these values in accordance with operation manuals of
connected equipment. T
he turn-on delay time value after allowable voltage
renewal is selected depending on the type of connected electrical
appliances. For refrigerators, air-conditioners and other compressor
devices the delay value should be not less than 3 minutes.
ENG
Voltage Relay
6