conventional procedures shall be used. However, it is important that best practice is 
followed since flammability is a consideration. The following procedure shall be adhered 
to: 

• Remove refrigerant;  

• Purge the circuit with inert gas;   

• Evacuate;  

• Purge again with inert gas;  

• Open the circuit by cutting or brazing.  

The refrigerant charge shall be recovered into the correct recovery cylinders. The system 
shall be “flushed” with OFN to render the unit safe. This process may need to be repeated 
several times. Compressed air or oxygen shall not be used for this task.   

Flushing shall be achieved by breaking the vacuum in the system with OFN and 
continuing to fill until the working pressure is achieved, then venting to atmosphere, and 
finally pulling down to a vacuum. This process shall be repeated until no refrigerant is 
within the system. When the final OFN charge is used, the system shall be vented down to 
atmospheric pressure to enable work to take place. This operation is absolutely vital if 
brazing operations on the pipe-work are to take place.  

Ensure that the outlet for the vacuum pump is not close to any ignition sources and there 
is ventilation available. 

13. Charging procedures

Annex DD.10

 

In addition to conventional charging procedures, the following requirements shall be 
followed.  

– Ensure that contamination of different refrigerants does not occur when using charging 
equipment. Hoses or lines shall be as short as possible to minimise the amount of 
refrigerant contained in them.  

– Cylinders shall be kept upright.   

– Ensure that the refrigeration system is earthed prior to charging the system with 
refrigerant.  

– Label the system when charging is complete (if not already).   

– Extreme care shall be taken not to overfill the refrigeration system.  

Prior to recharging the system it shall be pressure tested with OFN. The system shall be 
leak tested on completion of charging but prior to commissioning. A follow up leak test 
shall be carried out prior to leaving the site. 

Содержание 8.436.545.202.692

Страница 1: ...Conditioner User Manual MODEL SVAN291PF Thank you for selecting our quality appliance Please be sure to read this user manual carefully before using Any question please contact the professional servi...

Страница 2: ...the same outlet it can result in the risk of electric shock Do not disassemble or modify the appliance or the power cord it can result in the risk of electric shock or fire All other services should...

Страница 3: ...e of supporting up to 110lbs 50kg Installation on a weak or unlevel floor can result in the risk of property damage and personal injury If the appliance have the Wi Fi function the transmission power...

Страница 4: ...ntinuous sources of ignition for example open flames gas or electrical appliances in operation Do not puncture and do not burn Refrigerant gases can be odourless The appliance must be installed used a...

Страница 5: ...manufacturer Do not pierce or burn Be aware that the refrigerants may not contain an odour Compliance with national gas regulations shall be observed Keep ventilation openings clear of obstruction Th...

Страница 6: ...nsport of equipment containing flammable refrigerants Annex CC 1 Compliance with the transport regulations 2 Marking of equipment using signs Annex CC 2 Compliance with local regulations 3 Disposal of...

Страница 7: ...in the local area shall be instructed on the nature of work being carried out Work in confined spaces shall be avoided The area around the workspace shall be sectioned off Ensure that the conditions w...

Страница 8: ...istance The following checks shall be applied to installations using flammable refrigerants The charge size is in accordance with the room size within which the refrigerant containing parts are instal...

Страница 9: ...hall include damage to cables excessive number of connections terminals not made to original specification damage to seals incorrect fitting of glands etc Ensure that apparatus is mounted securely Ens...

Страница 10: ...tection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used Leak detection equipment shall...

Страница 11: ...vented down to atmospheric pressure to enable work to take place This operation is absolutely vital if brazing operations on the pipe work are to take place Ensure that the outlet for the vacuum pump...

Страница 12: ...times by a competent person Recovery equipment and cylinders conform to the appropriate standards d Pump down refrigerant system if possible e If a vacuum is not possible make a manifold so that refr...

Страница 13: ...ition a set of calibrated weighing scales shall be available and in good working order Hoses shall be complete with leak free disconnect couplings and in good condition Before using the recovery machi...

Страница 14: ...sing has no significant effect on the safety Nevertheless it is possible that leaking refrigerant may accumulate inside the enclosure and flammable atmosphere will be released when the enclosure is op...

Страница 15: ...utside or in a workshop specially equipped for servicing units with flammable refrigerants Ensure sufficient ventilation at the repair place Be aware that malfunction of the equipment may be caused by...

Страница 16: ...cause any danger In doubt one person should guard the outlet Take special care that drained refrigerant will not float back into the building Evacuate the refrigerant circuit Purge the refrigerant ci...

Страница 17: ...presentative if in doubt that the appliance is properly grounded ELECTRICAL CONNECTIONS Before plugging the appliance into the mains socket check that The mains power supply corresponds to the value i...

Страница 18: ...ndows walls etc The purpose of a dehumidifier is to remove the excess moisture from the air avoiding the damage caused by condensation Experts have established that the optimum environmental condition...

Страница 19: ...mote control Battery 1 set Drainage hose 1 set Note All the illustrations in this manual are for explanatory purposes only Your appliance 1 Control panel 2 Handle both side 3 Castors 4 Deflector 5 Int...

Страница 20: ...m exhaust air can be ducked outside First position unit on a flat floor and make sure there s a minimum of 17 7 45cm clearance around the unit and is within the vicinity of a single circuit outlet pow...

Страница 21: ...t in the window opening Never cut out the hole in window slider kit WINDOW SLIDER KIT INSTALLATION 1 Parts name A Panel Second slider may not supplied B Panel with one hole C Screw to lock window kit...

Страница 22: ...when rolling on carpeted surfaces Use caution and Protect floors when rolling over wood floors Do not attempt to roll the unit over objects The unit must be placed within reach of a properly rated gro...

Страница 23: ...manage part functions without remote controller Only heating models have heating function 1 Timer button 2 Fan button 3 Increase button 4 Display screen 5 Decrease button 6 Mode button 7 ON OFF butto...

Страница 24: ...ehumidify the room To set this mode correctly Press the button a number of times until the Cool symbol light appears Select the target temperature18 32 64 90 by pressing the or button until the corres...

Страница 25: ...ance should be prepared in the same way as for cool mode with the air exhaust hose attached to enable the moisture to be discharged outside To set this mode correctly Press the button a number of time...

Страница 26: ...ade by the appliance to change In this mode you may have to wait for a few minutes before the appliance starts giving out hot air In this mode the fan may operate for short periods even though the set...

Страница 27: ...hen Timer symbol is displayed on screen Press again the button the timer will be canceled and the Timer symbol will disappear from screen Switch the unit of temperature When the appliance is running h...

Страница 28: ...essages are displayed on the appliance display IF IS DISPLAYED WHAT SHOULD I DO PROBE FAILURE sensor damaged If this is displayed contact your local authorize service centre FULL TANK safety tank full...

Страница 29: ...iance without obstacles between the remote control and the receiver The remote control must be handled with extreme care Do not drop it or expose it to direct sunlight or sources of heat If the remote...

Страница 30: ...ngth of time remove the batteries COOL mode Ideal for hot muggy weather when you need to cooling and dehumidify the room To set this mode correctly Press the button a number of times until the Cool sy...

Страница 31: ...d for low speed fan As the figure below DRY mode Ideal to reduce room humidity spring and autumn damp rooms rainy periods etc In dry mode the appliance should be prepared in the same way as for cool m...

Страница 32: ...When you choose the sleep function the screen will reduce the brightness and the fan speed is low The SLEEP function maintains the room at optimum temperature without excessive fluctuations in either...

Страница 33: ...will be active then Timer symbol is displayed on screen Press again the button the timer will be canceled and the Timer symbol will disappear from screen Programming shut down Under the running of app...

Страница 34: ...rect exposure to the sun by partially closing curtains and or blinds to make the appliance much more economical to run fig 22 Never rest objects of any kind on the appliance Do not block the air inlet...

Страница 35: ...he pan 5 After the water is drained replace the lower drain plug firmly 6 Turn on the unit Continuous Draining fig 25 1 Unplug the unit from the power source 2 Remove the drain plug While doing this o...

Страница 36: ...may spill so please have a pan to collect the water 3 Connect the drain hose 1 2 or 12 7mm maybe not supplied fig B 4 The water can be continuously drained through the hose into a floor drain or buck...

Страница 37: ...the appliance with water It could be dangerous Never use petrol alcohol or solvents to clean the appliance Never spray insecticide liquids or similar CLEANING THE AIR FILTERS To keep your appliance wo...

Страница 38: ...pletely of water remove the cap fig 32 Run off all water left into a basin When all the water has been drained put the cap back in place Clean the filter and dry thoroughly before putting back Stricte...

Страница 39: ...on There is no current It is not plugged into the mains The internal safety device has tripped Wait Plug into the mains Wait 30 minutes if the problem persists contact your service center The applianc...

Страница 40: ...ibed above The appliance does not operate for about three minutes after restarting it The internal compressor safety device prevents the appliance from being restarted until three minutes have elapsed...

Отзывы: