Maximum angle deviation of a proper installation:
6.5 Performing the zero flow calibration
The zero flow calibration is a compulsory operation during the
installation of the sensor. Use one of the following methods to perform
the calibration:
•
The service App S4C-FS, available on the Google Play store or our
Website for free download
•
The optional local display
6.5.1 Prerequisites
Before you start the calibration, make sure the following conditions are
met:
•
The sensor must have been mounted on top of the G 1/2" ball
valve.
•
The ball valve must be opened with the sensor tip outside of the
pipe. That is, the sensor tip still remain inside the ball valve.
These ensure that the sensor is exposed to the system pressure during
calibration.
6.5.2 Using the service App S4C-FS
This is the most convenient way especially when the sensor is not
equipped with the optional local display.
1. On your mobile device, download the S4C-FS App from the
SUPPORT
>
Downloads
Google Play store as needed.
2. Turn on Bluetooth on your mobile device.
3. Launch the
S4C-FS
App.