• LIQUID LEVEL / LWCO CONTROLLER

The electronic controller automatically maintains proper
water level, and shuts off the generator when water
supply in the boiler drops below a safe operating level.

• WATER LEVEL SIGHT GLASS

Allows constant observation of water level while
boiler is in operation.

• ON-OFF SWITCH

Complete with pilot light, for switching on the
generator.

• INTEGRAL ELECTRICAL CONTROL

Magnetic contactors energize the elements and
are integrally mounted in the control unit.

• BLOWDOWN/DRAIN VALVE

Facilitates emptying the pressure vessel during

blowdown/drain sequence.

• J-BOX

for motor/pump connection.

• LONG LIFE HEATING ELEMENTS

Industrial grade, heavy duty stainless steel heating
elements equipped with one piece resistance welded
terminations for added strength and safety.

• OPERATING PRESSURE CONTROL

Operates automatically to maintain steam pressure
within generator.

• MANUAL RESET PRESSURE CONTROL

Provides high limit pressure cut-out with manual reset.

• STEAM SAFETY VALVE

ASME Code valve, automatically opens to reduce
pressure should excessive steam cause pressure build-up.

• STEAM PRESSURE GAUGE

Allows visual observation of steam pressure over full
range.

• ENERGY SAVING AND MINIMUM

MAINTENANCE

Fully insulated pressure vessel minimizes heat loss
and maximizes energy savings.

• EASY CONTROL MAINTENANCE

All controls and components are easily accessible.
Fully-louvered openings avoid component heat build-up.

• RUGGED CONSTRUCTION

Performance is insured for all typical industrial
applications.

ES 30A - ES36A - HP 30A Electric Steam Generator

Installation, Operation and Maintenance Manual

_____________________________________________________________________________

2

Standard Features

Meeting Code Requirements

Pressure vessel rated at 100PSIG to ASME Section I,

Code M and National Board registered.

UL listed, cUL certified built to NEC.

Units are trimmed at 100PSIG as standard.

15PSIG trim also available.

Incoming water line pressure must be 10 PSIG

greater than generator operating pressure. If not, a
motor/pump must be used. Specify Sussman ES
38002A high pressure water feed motor/pump system.

When ordering specify Model No., KW,

Volts/PH and motor/pump if required.

Water Connection is 1/4” NPT.

Содержание ES30A

Страница 1: ...pproving your generator It must be kept near the generator at all times KW Design Max Work Model Range Steam Rate BHP Pressure Pressure ________________________________________________________________...

Страница 2: ...automatically opens to reduce pressure should excessive steam cause pressure build up STEAM PRESSURE GAUGE Allows visual observation of steam pressure over full range ENERGY SAVING AND MINIMUM MAINTEN...

Страница 3: ...and N E C requirements following wiring diagram supplied Wire size specified adjacent to field wiring terminal block s Use 90 C copper wire only Purchaser should use a disconnect switch employing circ...

Страница 4: ...ation Operation and Maintenance Manual _____________________________________________________________________________ 4 Factory Wiring Field Wiring NOTE See Boiler Nameplate for Input Requirements Wiri...

Страница 5: ...ting pressure control to a low pressure setting Set hi limit control at 10 PS1G above that setting Switch boiler on to allow for steam pressure build up Pressure gauge reading will build and the opera...

Страница 6: ...off the boiler switch unless further operation is desirable 6 If you have been supplied with a Manual Reset Low Water Control as required in some states the reset button on the control must be pushed...

Страница 7: ...on terminals on element assembly are in line with previously disconnected wire leads to facilitate easy connections NOTE Observe markings on element flange Install element marking TOP on top 7 Use onl...

Страница 8: ...both ends of the gauge glass Push both packings about an inch up the gauge glass 4 Gently insert one end of the glass into the top gauge fitting Keeping the glass inside the top fit ting gently rotate...

Страница 9: ...e gauge glass daily keep maintenance records and conduct routine replacements DO protect glass from sudden changes in temperatures such as drafts water spray etc MAINTENANCE Examine the gauge glass re...

Страница 10: ...RE FREQUENT BLOWDOWN IS REQUIRED RECOMMENDED LIMITS WITHIN A BOILER TOTAL DISSOLVED SOLIDS ppm 3500 TOTAL ALKALINITY ppm 850 SUSPENDED SOLIDS ppm 300 SILICA Si02 ppm 125 SULFITE SO3 ppm 25 50 PHOSPHAT...

Страница 11: ...Rise ____________________________________________________ Spare Parts List ____________________________________________________ 99136 Safety Valve 100PSIG 1 2 NPT _____________________________________...

Страница 12: ...PN 100600 1 17 A Division of Sussman Automatic Corporation 43 20 34th Street Long Island City NY 11101 718 937 4500 1 800 238 3535 Fax 718 937 4676 www sussmanboilers com Email seb sussmancorp com...

Отзывы: