![SurgeX SX-BDL-1500 Скачать руководство пользователя страница 31](http://html1.mh-extra.com/html/surgex/sx-bdl-1500/sx-bdl-1500_user-manual_1407291031.webp)
© SurgeX | Technical Support: 800-645-9721 | surgex.com
Page 30
On-Line UPS
User Manual
Models: UPS-1500-OL, UPS-2000-OL, UPS-3000-OL
SX-BDL-1500, SX-BDL-2000
15. Appendix A: Extended Battery Pack (EBP) User Guide
Estimated Run Time for UPS with Extended Battery Packs
MODEL
LOAD
RUNTIME FOR QTY OF EXTENDED BATTERY PACKS IN MIN.
VA
WATTS UPS
(1) EPB (2) EPB (3) EBP (4) EBP
(5) EBP
SX-BDL-1500
UPS-1500-OL
750
525
18
68
124
184
248
315
1500
1050
9
32
60
90
120
152
SX-BDL-2000
UPS-2000-OL
1000
700
29
109
200
298
402
510
2000
1400
14
52
97
144
194
247
UPS-3000-OL
1500
1050
18
67
123
184
248
315
3000
2100
9
32
60
89
120
152
CAUTION: It is very critical to connect the correct voltage EBP with the UPS intended.
UPS-BPX-1500 is for SX-BDL-1500/UPS-1500-OL
UPS-BPX-2000 is for SX-BDL-2000/UPS-2000-OL/UPS-3000-OL
Connecting the incorrect battery pack to the UPS may result in damage to the UPS and/or battery pack
will void the warranty.
All EBPs have a different DC voltage configuration intended only for the UPS’s listed above. Please do
not mix BPX’s and make sure you only connect the EBP to like EBPs or UPS indicated above. DC
voltages are marked on both the UPS and the EBP – MAKE SURE THEY MATCH.
CAUTION LABEL ON EBP CABLE CONNECTORS –
PLEASE CHECK VOLTAGES CAREFULLY