On-Line UPS
User Manual
Models: UPS-1500-OL, UPS-2000-OL, UPS-3000-OL
SX-BDL-1500, SX-BDL-2000
LED Descriptions
There are four lines of information in the LCD display. Each line provides specific information related to the unit
status and/or operation. Line information will be described from top to bottom with the top being line one.
Line One
Provides data in to numeric sections, with the data corresponding to the applicable category in line one
and two
Line Two
Allows the user to identify which variable information is being displayed.
•
Input
•
Output
•
Battery
•
Load
•
Temperature
Line Three
This is a graphics section with load graphics on the left and battery graphics on the right. The failure
icon will appear in this section when a failure occurs.
Line Four
This indicates the status of the UPS.
•
ON LINE = utility mode
•
ON BATT = battery mode
•
ON BPS = bypass mode
•
UPS OFF = standby mode
RS-232 Standard Interface
The RS-232 interface uses a 9-pin female D-sub connector. Information provided includes data about utility,
load and the UPS. The interface port pins and their functions are identified in the following table:
PIN #
FUNCTIONS
1,4,6,7,8
NOT USED
2
TRANSMIT
3
RECEIPT
5
GND
9
REMOTE WAKE UP
CAUTION: MAX RATED VALUES 12VDC