Use the following procedure to adjust the bypass:
1.
Close the valve to
Position A
2.
Turn on the circulation pump
3.
Slowly open the valve towards Position B until the display error code of “E03” disappears.
Once the message clears, the default display is the current water temperature. Starting
sequence will now begin.
ATTENTION
Bypass Installation
Operation without a bypass or with improper bypass adjustment may result in suboptimal
heat pump operation and possible damage to the heat pump. Failure to observe this
instruction will void the warranty.
Heatseeker NovaS Heat Pump
Installation & User Manual
17