Installation
19
Connecting to Secure I/O 2
Secure I/O 2 is an I/O device, can be connected to FaceStation F2 with the RS-485 cable. Security can be maintained even if
the connection between FaceStation F2 and Secure I/O 2 has been lost or the power supply to FaceStation F2 has been shut
off due to external factors.
•
Use an AWG24 twisted pair with a maximum length of 1.2 km for the RS-485 cable.
•
If connecting with a RS-485 daisy chain, connect the termination resistor
(120 Ω) to both ends of the daisy chain
connection. If connected to the middle line, the signal level becomes smaller and the communication performance will
deteriorate. Make sure to connect it to both ends of the daisy chain connection.
NOTE
•
FaceStation F2 can be used as a multi-door controller with the slave devices with the RS-485 cable. The slave devices are used
as dummy readers and authentication is performed in the master device.
•
If a fingerprint authentication device is configured as a slave device in FaceStation F2, you cannot add another FaceStation F2
as a slave device.
•
If the fingerprint authentication device is the master device, FaceStation F2 cannot be added as a slave device.
•
When you connect FaceStation F2 as a slave device while FaceStation F2 is the master device, only one FaceStation F2 can be
added as a slave device.
•
If FaceStation F2 is configured as a slave device for the face recognition terminal, you can connect one additional Secure I/O 1
and DM-20 each.
•
If FaceStation F2 is configured as a slave device for the face recognition terminal, you cannot connect additional OM-120.
•
The maximum number of slave devices available to connect varies according to the authentication method, number of users,
and number of devices. Also note that the number of slave devices affects the authentication speed.
•
A master device can control 31 slave devices. The bandwidth of RS-485 allows for up to 7 fingerprint authentication devices to
be connected.
•
For more information, contact the Suprema technical support team (support.supremainc.com).
FaceStation F2
PC
Door lock
Secure I/O 2
Door sensor
RS-485 connection
1 - 485 TRXP
Blue
2 - 485 TRXN
Yellow
3 - 485 GND
Black
4 - SH GND
Gray
Cable shield (optional)
DC power
DC power
DC power
Hub
RS-485
Power
Power supply connection
1 - PWR +VDC
Red (White stripe)
2 - PWR GND
Black (White stripe)
Door button