Chapter 7 Configuration Settings
www.supmea.com
26
7.4.2 Low report settings:
Set the alarm value and hysteresis value of the low alarm relay. When (measured
value < alarm value), the normally open contact of the low alarm relay is closed,
and the normally closed contact is disconnected. When (measured value > alarm
value + hysteresis) When the low alarm relay normally open contact is
disconnected, the normally closed contact is closed
.
:
Select to set parameter data digits
:
Change data size
:
Jump to hysteresis parameter setting, save the setting parameters
:
Back to monitoring interface
:
Return to the alarm value parameter setting, return to the alarm setting
interface
Note: The unit xx and the data size are automatically switched according to the
selected sensor
Figure 44
--Alarm Setting--
1.High Alarm
2.Low Alarm
--Low Alarm --
Value
Hysteresis