AIR FOR COMBUSTION AND VENTILATION  

continued

The space in the example is a confi ned space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. 
You must provide additional fresh air. Your options are as follows:
A.  Rework worksheet, adding the space of an adjoining room. If the 

extra space provides an unconfi ned space, remove door to adjoining 
room or add ventilation grills between rooms. See Ventilation Air 
From Inside Building.

B.  Vent room directly to the outdoors. See Ventilation Air From 

Outdoors.

C.  Install a lower Btu/Hr fi replace, if lower Btu/Hr size makes room 

unconfi ned.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space 
can support, the space is an unconfi ned space. You will need no ad-
ditional fresh air ventilation.

 WARNING: If the area in which the heater may be 

operated does not meet the required volume for indoor 
combustion air, combustion and ventilation air shall 
be provided by one of the methods described in the 
National Fuel Gas Code, ANSI Z223.1/NFPA 54, the 
International Fuel Gas Code, or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfi ned space. When 
ventilating to an adjoining unconfi ned space, you must provide two 
permanent openings: one within 12" of the ceiling and one within 12" 
of the fl oor on the wall connecting the two spaces 

(see options 1 and 

2, 

Figure 4

).

 You can also remove door into adjoining room 

(see option 

3, 

Figure 4

).

 Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 

54, Air for Combustion and Ventilation for required size of ventilation 
grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must 
provide two permanent openings: one within 12" of the ceiling and 
one within 12" of the fl oor. Connect these items directly to the out-
doors or spaces open to the outdoors. These spaces include attics 
and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Air for Combustion and Ventilation for required size of 
ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air 
into attic if attic has a thermostat-controlled power vent. 
Heated air entering the attic will activate the power vent.

Figure 4 - Ventilation Air from Inside Building

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12"

12"

Figure 5 - Ventilation Air from Outdoors

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Содержание VRE4536WH

Страница 1: ...US C Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any e...

Страница 2: ...y or death from burns fire explosion electrical shock and carbon monoxide poisoning You must operate this fireplace with the provided fireplace screen and hood in place Make sure these parts are in pl...

Страница 3: ...ter It requires no outside venting or chimney making installation easy and inexpensive COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS These appliances are approved for installation in the US state of Mass...

Страница 4: ...D 4 PRODUCT SPECIFICATIONS 36 MODELS Figure 1 36 Models VRE4536RS VRE4536WS VRE4536RH and VRE4536WH 20 1 4 Ref 1 1 4 22 1 2 19 36 HEARTH 29 30 1 2 30 36 54 1 2 11 1 8 45 1 8 36 3 8 35 1 4 9 1 2 3 3 8...

Страница 5: ...RODUCT SPECIFICATIONS continued 42 MODELS Figure 2 42 Models VRE4542RS VRE4542WS VRE4542RH and VRE4542WH 42 HEARTH 21 3 4 8 3 4 3 3 8 9 1 2 26 3 8 41 3 8 4 7 8 1 1 4 3 3 4 32 3 8 36 3 8 11 1 8 7 7 8 5...

Страница 6: ...6 Figure 3 50 Models VRE4550RS VRE4550WS VRE4550RH and VRE4550WH 21 3 4 8 3 4 9 1 2 3 3 8 13 50 50 7 30 34 3 8 38 3 8 4 7 8 49 3 8 36 3 8 59 1 8 54 1 2 11 1 8 3 3 4 32 3 8 7 7 8 23 Ref 50 HEARTH PRODU...

Страница 7: ...ebox Location Confined and Unconfined Space The National Fuel Gas Code ANSI Z223 1 NFPA54 allows two meth ods for determining whether the space in which the heater is being installed is confined or un...

Страница 8: ...ned space When ventilating to an adjoining unconfined space you must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces se...

Страница 9: ...ottom of your firebox except where standoff spacers are integrally attached If standoff spacers are attached to your firebox these spacers can be placed directly against wall or framing materials Use...

Страница 10: ...ational product standard Fol low all minimum clearances shown in this manual NOTICE Ifyourinstallationdoesnotmeettheminimum clearances shown you must do one of the following raise the mantel to an acc...

Страница 11: ...es This firebox may be installed using a cabinet mantel against a wall in your home The firebox and cabinet mantel can be installed directly on the floor Mantels may be available from your retailer or...

Страница 12: ...he right and left refractory panels with the gas line knock outs orientated down toward the bottom refractory Align the left and right panels with the rear panel so the grout lines line up 5 Install t...

Страница 13: ...l furnace cement Install the gas appliance or cap off gas line if desired A gas line or gas log lighter may be installed for the purpose of installing a vent free decorative gas appliance incorporatin...

Страница 14: ...1 20 1 19 5 14 15 16 13 12 11 9 7 6 8 17 2 12 18 4 PARTS MODEL NO CAT NO INTERIOR VRE4536WS F0474 White Stacked VRE4536WH F0476 White Herringbone VRE4542WS F0478 White Stacked VRE4542WH F0480 White He...

Страница 15: ...EPLACE 36 1 RP110454 02 TOP FIREPLACE 42 1 RP110454 01 TOP FIREPLACE 50 1 9 J6997 SPACER FIREPLACE TOP 42MC 4 10 FIREPLACE SURROUND ASSEMBLY 1 11 J4362 SPACER CLEARANCE 36 42 50 6 12 J5329 BRACKET F P...

Страница 16: ...itute materials not approved by IHP Use of non approved parts can result in poor performance and safety hazards 1 2 5 3 4 6 6 IMPORTANT Installation of brick panels should be done after the fireplace...

Страница 17: ...ORY HEARTH 36 STD WHITE 1 REFRACTORY HEARTH 42 STK WHITE 1 REFRACTORY HEARTH 50 STK WHITE 1 3 REFRACTORY RIGHT 36 STK WHITE 1 REFRACTORY RIGHT 36 HER WHITE 1 REFRACTORY RT 42 STK WHITE 1 REFRACTORY RT...

Страница 18: ...yed ignition fireplace will not produce specified heat for propane LP unit propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local gas supplier TECHNICAL SE...

Страница 19: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a re hazard c...

Страница 20: ...ributor for fireplace code information Printed in U S A 2014 Innovative Hearth Products P N 127029 01 Rev D 01 2017 1508 Elm Hill Pike Suite 108 Nashville TN 37210 SuperiorFireplaces US com Record the...

Отзывы: