AIR FOR COMBUSTION AND VENTILATION

 WARNING: This fi rebox shall not be installed in a 

room or space unless the required volume of indoor 
combustion air is provided by the method described in 
the National Fuel Gas Code, ANSI Z223.1/NFPA 54, the 
International Fuel Gas Code, or applicable local codes. 
Read the following instructions to ensure proper fresh air 
for this and other fuel-burning appliances in your home.

Today’s homes are built more energy effi cient than ever. New materials, 
increased insulation and new construction methods help reduce heat 
loss in homes. Homeowners apply weather strip and caulk around 
windows and doors to keep the cold air out and the warm air in. During 
heating months, homeowners want their homes as airtight as possible.
While it is good to make your home energy effi cient, your home needs 
to breathe. Fresh air must enter your home. All fuel-burning appliances 
need fresh air for proper combustion and ventilation.
Exhaust fans, some fi replaces, clothes dryers and some fuel-burning 
appliances draw air from the house to operate. You must provide ad-
equate fresh air for these appliances. This will ensure proper venting 
of vented fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION

The following are excerpts from National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation 
classifi cations:
1.  Unusually Tight Construction
2. Unconfi ned Space
3.  Confi ned Space
The information on 

Pages 7 through 8 

will help you classify your space 

and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough 
fresh air for combustion and ventilation. However, in buildings of 
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defi ned as construction where:

a.  walls and ceilings exposed to the outside atmosphere have a 

continuous water vapor retarder with a rating of one perm (6 x 
10

-11

 kg per pa-sec-m

2

) or less with openings gasketed or sealed 

and

b.  weather stripping has been added on openable windows and 

doors and

c.  caulking or sealants are applied to areas such as joints around 

window and door frames, between sole plates and fl oors, be-
tween wall-ceiling joints, between wall panels, at penetrations 
for plumbing, electrical and gas lines and at other openings.

If your home meets all of the three criteria above, you must provide ad-
ditional fresh air. See Ventilation Air From Outdoors, 

Page 8

If your home does not meet all of the three criteria above, proceed 
to Determining Fresh-Air Flow For Firebox Location.

Confi ned and Unconfi ned Space

The National Fuel Gas Code, ANSI Z223.1/ NFPA54 allows two meth-
ods for determining whether the space in which the heater is being 
installed is confi ned or unconfi ned space. The standard method 
defi nes a confi ned space as a space whose volume is less than 50

cubic feet per 1,000 Btu per hour (4.8 m

3

 per kw) of the aggregate 

input rating of all appliances installed in that space and an unconfi ned 
space as a space whose volume is not less than 50 cubic feet per 
1,000 Btu per hour (4.8 m

3

 per kw) of the aggregate input rating of all 

appliances installed in that space. Rooms communicating directly with 
the space in which the appliances are installed*, through openings not 
furnished with doors, are considered a part of the unconfi ned space.
Where the air infi ltration rate of a structure is known, the Known Air 
Infi ltration Rate Method may be used. Follow The National Fuel Gas 
Code, ANSI Z223.1/NFPA 54 to use this method to determine if the 
space is confi ned or unconfi ned.
* Adjoining rooms are communicating only if there are doorless 
passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR FIREBOX LOCATION

Determining if You Have a Confi ned or Unconfi ned Space  Using 
the Standard Method

Use this work sheet to determine if you have a confi ned or uncon-
fi ned space.
Space: Includes the room in which you will install heater plus any ad-
joining rooms with doorless passageways or ventilation grills between 
the rooms.
1.  Determine the volume of the space (length x width x height).
 

Length x Width x Height =__________cu. ft. (volume of space)

 

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling 
height) = 3,168 cu. ft. (volume of space)

 

If additional ventilation to adjoining room is supplied with grills 
or openings, add the volume of these rooms to the total volume 
of the space. 

2.  Multiply the space volume by 20 to determine the maximum Btu/Hr 

the space can support.

 

 _______ (volume of space) x 20 = (Maximum Btu/Hr the space 
can support)

 

Example: 3,168 cu. ft. (volume of space) x 20 = 63,360 (maximum 
Btu/Hr space can support)

3.  Add the Btu/Hr of all fuel burning appliances in the space.
 

Vent-free fi replace   ________  Btu/Hr

 

Gas water heater*   ________  Btu/Hr

 

Gas furnace 

  ________  Btu/Hr

 

Vented gas heater   ________  Btu/Hr

 

Gas fi replace logs   ________  Btu/Hr

 

Other gas appl  _____  Btu/Hr

 

Total 

=  _______  Btu/Hr

 

* Do not include direct-vent gas appliances. Direct-vent draws 
combustion air from the outdoors and vents to the outdoors.

 Example:
 

Gas water heater     40,000 Btu/Hr

 

Vent-free fi r 39,000 Btu/Hr

 

Total 

= 79,000 Btu/Hr

4.  Compare the maximum Btu/Hr the space can support with the 

actual amount of Btu/Hr used.

 

 ______ Btu/Hr (maximum the space can support) 

 

 ______ Btu/Hr (actual amount of Btu/Hr used)

 

Example:

 63,360 Btu/Hr (maximum the space can support)

 

 

79,000 Btu/Hr (actual amount of Btu/Hr used)

Содержание VRE4536WH

Страница 1: ...US C Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any e...

Страница 2: ...y or death from burns fire explosion electrical shock and carbon monoxide poisoning You must operate this fireplace with the provided fireplace screen and hood in place Make sure these parts are in pl...

Страница 3: ...ter It requires no outside venting or chimney making installation easy and inexpensive COMMONWEALTH OF MASSACHUSETTS REQUIREMENTS These appliances are approved for installation in the US state of Mass...

Страница 4: ...D 4 PRODUCT SPECIFICATIONS 36 MODELS Figure 1 36 Models VRE4536RS VRE4536WS VRE4536RH and VRE4536WH 20 1 4 Ref 1 1 4 22 1 2 19 36 HEARTH 29 30 1 2 30 36 54 1 2 11 1 8 45 1 8 36 3 8 35 1 4 9 1 2 3 3 8...

Страница 5: ...RODUCT SPECIFICATIONS continued 42 MODELS Figure 2 42 Models VRE4542RS VRE4542WS VRE4542RH and VRE4542WH 42 HEARTH 21 3 4 8 3 4 3 3 8 9 1 2 26 3 8 41 3 8 4 7 8 1 1 4 3 3 4 32 3 8 36 3 8 11 1 8 7 7 8 5...

Страница 6: ...6 Figure 3 50 Models VRE4550RS VRE4550WS VRE4550RH and VRE4550WH 21 3 4 8 3 4 9 1 2 3 3 8 13 50 50 7 30 34 3 8 38 3 8 4 7 8 49 3 8 36 3 8 59 1 8 54 1 2 11 1 8 3 3 4 32 3 8 7 7 8 23 Ref 50 HEARTH PRODU...

Страница 7: ...ebox Location Confined and Unconfined Space The National Fuel Gas Code ANSI Z223 1 NFPA54 allows two meth ods for determining whether the space in which the heater is being installed is confined or un...

Страница 8: ...ned space When ventilating to an adjoining unconfined space you must provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces se...

Страница 9: ...ottom of your firebox except where standoff spacers are integrally attached If standoff spacers are attached to your firebox these spacers can be placed directly against wall or framing materials Use...

Страница 10: ...ational product standard Fol low all minimum clearances shown in this manual NOTICE Ifyourinstallationdoesnotmeettheminimum clearances shown you must do one of the following raise the mantel to an acc...

Страница 11: ...es This firebox may be installed using a cabinet mantel against a wall in your home The firebox and cabinet mantel can be installed directly on the floor Mantels may be available from your retailer or...

Страница 12: ...he right and left refractory panels with the gas line knock outs orientated down toward the bottom refractory Align the left and right panels with the rear panel so the grout lines line up 5 Install t...

Страница 13: ...l furnace cement Install the gas appliance or cap off gas line if desired A gas line or gas log lighter may be installed for the purpose of installing a vent free decorative gas appliance incorporatin...

Страница 14: ...1 20 1 19 5 14 15 16 13 12 11 9 7 6 8 17 2 12 18 4 PARTS MODEL NO CAT NO INTERIOR VRE4536WS F0474 White Stacked VRE4536WH F0476 White Herringbone VRE4542WS F0478 White Stacked VRE4542WH F0480 White He...

Страница 15: ...EPLACE 36 1 RP110454 02 TOP FIREPLACE 42 1 RP110454 01 TOP FIREPLACE 50 1 9 J6997 SPACER FIREPLACE TOP 42MC 4 10 FIREPLACE SURROUND ASSEMBLY 1 11 J4362 SPACER CLEARANCE 36 42 50 6 12 J5329 BRACKET F P...

Страница 16: ...itute materials not approved by IHP Use of non approved parts can result in poor performance and safety hazards 1 2 5 3 4 6 6 IMPORTANT Installation of brick panels should be done after the fireplace...

Страница 17: ...ORY HEARTH 36 STD WHITE 1 REFRACTORY HEARTH 42 STK WHITE 1 REFRACTORY HEARTH 50 STK WHITE 1 3 REFRACTORY RIGHT 36 STK WHITE 1 REFRACTORY RIGHT 36 HER WHITE 1 REFRACTORY RT 42 STK WHITE 1 REFRACTORY RT...

Страница 18: ...yed ignition fireplace will not produce specified heat for propane LP unit propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local gas supplier TECHNICAL SE...

Страница 19: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a re hazard c...

Страница 20: ...ributor for fireplace code information Printed in U S A 2014 Innovative Hearth Products P N 127029 01 Rev D 01 2017 1508 Elm Hill Pike Suite 108 Nashville TN 37210 SuperiorFireplaces US com Record the...

Отзывы: