* Other approved chimney brand is Simpson Dura-Vent DV-GS.

PRE-INSTALLATION

RATINGS

DXS3030TMN-35

DXS3030TMN-25

NATURAL GAS

LP GAS

NATURAL GAS

LP GAS

Max/Min Input BTUh 0-2,000 Feet

(0-610 M

)

u

35,000/23,000

35,000/23,500

25,000/17,500

25,000/18,000

Manifold Pressure (IN. WC)

3.5

10.0

3.5

10.0

Min. Inlet Pressure (IN. WC)

5.0

11

5.0

11

Maximum heat output BTUs/hour-steady state

29,050

 29,050

20,750

20,750

P4 Efficiency

 

w

61.65%

65.74%

65.08%

66.56%

Steady-State Efficiency

 

v

82-85%

82-85%

82-85%

82-85%

O

rifice (DMS) 0-2,000 Feet (0-610 M)

u

#34 (.111 IN).

#50 (.070 IN).

#42 (.093 IN).

#53 (.059 IN).

u

U

nit factory equipped for 0-2000 FT/0-610 M, In Canada 0-4500 FT/0-1370 M

v

The Steady State Efficiency numbers based on maximum vent configuration.

w

Tested to CSA P.4.1-02 “Testing Method for Measuring Annual Fireplace Efficiency.

Electrical Rating: 120 VAC, 60 HZ, Less Than 2 Amps

FEATURES

Installation Options

 Residential

  Vented vertical and horizontal

  Manufactured (mobile) home

  Natural gas (NG) or propane (LP)

  Bedrooms  

 

  Optional wall-mounted or remote thermostat

                                                                                                              

Venting

This appliance can be vented with Secure Vent

®

 direct-vent pipe. Coaxial 

pipe diameters are 6-5/8” outer and 4” inner.  The combustion air for this 

stove is drawn from outside the house through the outer DV (direct-vent) 

pipe. Room air is not required for combustion.

When planning your installation, select the correct length of vent pipe 

for your particular requirements. Determine the minimum clearance to 

combustibles from the rear of the unit to the wall. It is also important 

to note the thickness of the wall. Before cutting the vent hole through 

the wall make sure that ALL vent and termination clearances (see 

Page 

17

will be met.

Electrical

The standard fan motor requires 120 Volts AC for operation. The stove is 

not dependent on the fan or an outside electrical supply to operate. 

WARNING - Electrical Grounding Instructions - This appliance 

is equipped with a three-prong (grounding) plug for your pro

-

tection against shock hazard and should be plugged directly 

into a properly grounded three-prong receptacle. Do not cut or 

remove the grounding prong from this plug.

Millivolt Valve

This appliance is operated with a millivolt valve and therefore burns even 

during a power outage.

Fuel

This appliance comes from the factory equipped to burn natural gas at a 

specified elevation. The appliance can be converted to burn LP gas (liquid 

propane) by changing the cassette (valve and pilot assembly) or installing 

a conversion kit. Only IHP conversion kits can be used to convert from 

NG to LP or LP to NG. Contact your IHP dealer for details.

Specifications

Pipe:Type - direct-vent

Recommended manufacturer*

 

Secure Vent

®

 by IHP*

 

Diameter - 6-5/8” x 4” for all installations

Stove Packaging List

The gas stove comes with the following parts:

 

1  Stove Body with Burner Cassette

 

1  150 CFM Blower

 

1  Brick Panel

 

1  Log Set

 

1  Bag of Ember Material 

1  Installation and Operation Manual

Options

•  Wall-mounted or Remote Thermostat

•  Painted,  Gold,  or  Nickel  Plated  Door  Trim  and  Grill  Assembly  (re

-

quired)

Содержание DXS3030TMN

Страница 1: ...les instructions du fournis seur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur s par un installateur ou un service...

Страница 2: ...Residential and Mobile Home Installations 13 Vent Considerations 13 Vent Parts List 14 Horizontal Vent Installation 14 Vertical Vent Installation 15 Flue Restrictors 15 Horizontal Terminations 16 Vert...

Страница 3: ...aller service agency or the gas supplier WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance voiding its warranty Any change t...

Страница 4: ...nected to a chimney or flue serving a separate solid fuel burning appliance These appliances are vented gas appliances Do not burn wood or other material in these appliances This appliance is only for...

Страница 5: ...pag ndola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperficiedelaplacadelinterruptorquecontrola la chimenea Figura A o en el termostato de pared...

Страница 6: ...ppliance Has been certified for use with either natural gas or propane Is not for use with solid fuels Is approved for sitting rooms and or bedrooms THE GAS STOVE ORIFICE SIZE ALTITUDE ADJUSTMENT For...

Страница 7: ...accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 latest edition or the Canadian Electrical Code CSA C22 1 latest edition NEW YORK CITY NEW Y...

Страница 8: ...Determine the minimum clearance to combustibles from the rear of the unit to the wall It is also important to note the thickness of the wall Before cutting the vent hole through the wall make sure th...

Страница 9: ...ty hazard The IHP warranty will be voided if one of the following occurs Installation of any damaged stove or vent system component Unauthorized modification of the direct vent system Installation oth...

Страница 10: ...tween the alcove side walls is 51 1295mm The minimum height of the alcove is 46 1168mm and the maximum depth is 35 889mm Floor Protection A non combustible hearth pad is not required This stove may be...

Страница 11: ...s or they will snap the studs off To install the spring handle first close the door and screw the handle into the receiving nut Then spray a household glass cleaner or water on the shaft of the handle...

Страница 12: ...e logs are not properly installed your appliance will not function correctly Parts list rear log right log left log center log brick panel packaged separately 1 Remove the logs from the box and carefu...

Страница 13: ...on of the direct vent system Installation of any vent component part not approved or manufactured by the approved vent manufacturer Installation other than as instructed by IHP and vent manufacturers...

Страница 14: ...inals may not be recessed into a wall or siding 1 Set the unit in the desired location Check whether or not wall studs are in the way when the venting system is attached If wall studs are in the way y...

Страница 15: ...and note which restrictor setting is recommended The flue restrictor is shipped in the firebox of your stove To install the restrictor see Figure 18 Remove the two 5 32 allen head screws A below Using...

Страница 16: ...35 LP 0 3 horizontal 14 Snorkel Required No Light Obstructor DXS3030TMN 35 NG 0 3 horizontal 14 Snorkel Required No Light Obstructor Offsets must remain within maximum and minimum lines To install th...

Страница 17: ...ded above meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly 3 feet 91 cm within a height of 15 feet above the meter regulator assembly I Clearance to...

Страница 18: ...to the right of the inlet tap To check manifold pressure with the appliance burning at the high burn setting insert a small flat bladed screwdriver into the tap and turn a half turn counterclockwise C...

Страница 19: ...e been furnished with the fireplace be affixed to the operation and control points of the fireplace per the instructions on Page 5 It is the installers responsibility to ensure these warnings are prop...

Страница 20: ...cian Force or attempted repair may result in a fire or explosion D DO NOT use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance a...

Страница 21: ...cause the flames to turn orange sooner may result in poor combustion sooting and a hazardous situation See the drawing to the right showing proper flame appearance When testing for proper operation If...

Страница 22: ...sound of rush ing air may be heard The blower sounds may be reduced by adjusting the speed control located on the blower assembly Also a slight clicking soundmaybeheardasthegasvalveorblowerswitchistu...

Страница 23: ...ing the thermostat or remote control and set the thermostat or remote control to the lowest temperature when you wish to use the rocker switch only otherwise one may override the other Millivolt Contr...

Страница 24: ...pile and thermocouple and extend across the main burner tube ports Be careful not to back the screw out of its threads o Check that the area around the stove is kept clear and is free of combustible m...

Страница 25: ...cleaner with ammonia on the door and glass gasket as it may dis solve the gasket glue Repair If the glass is broken in the glass door the entire door metal frame gasket and glass should be replaced a...

Страница 26: ...ocess 2 Remove the log set see Log Installation 3 Remove the two phillips head screws from the back of the burner 4 Lift the right end of the burner and slide if off the orifice and shutter tube Remov...

Страница 27: ...n pilot position for 1 2 minutes and light Check for spark at electrode and pilot if no spark and electrode wire is properly connected replace igniter See Lighting Instructions Pilot will not stay lit...

Страница 28: ...des commandes tiquetez tous les fils avant de les d brancher Des erreurs de c blage peuvent entra ner un fonctionnement inad quat et dangereux Figure 31 BLOWER Female Spade 1 4 Female Spade 1 4 Femal...

Страница 29: ...nform ment ces sch mas et ou si des pi ces autres que celles sp cifiquement approuv es avec cet appareil sont utilis es Contact an IHP dealer to obtain any of these parts WARNING Never use substitute...

Страница 30: ...r may be wall mounted or placed in the valve compartment Cost Effective Solution Simple On Off operation Workswithmillivoltandlowvoltageelectronic ignition controls Kit includes Remote and Receiver Wa...

Страница 31: ...5 000 23 500 25 000 17 500 25 000 18 000 MANIFOLD PRESSURE IN WC 3 5 10 0 3 5 10 0 MIN INLET PRESSURE IN WC 5 0 11 5 0 11 ORIFICE DMS 0 2 000 FT 0 610 M 34 111 IN 50 070 IN 42 093 IN 53 059 IN UNIT FA...

Страница 32: ...tactez un installateur qualifi un agent de service ou un fournisseur de gaz Si vous op rez cet appareil sans qu il ne soit correctement raccord un conduit d vacuation vous pourriez risquer d tre empoi...

Страница 33: ...ural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c d...

Страница 34: ...e serial number of the appliance 3 The part number 4 The description of the part 5 The quantity required 6 The installation date of the appliance If you encounter any problems or have any questions co...

Отзывы: