THE CHIMNEY SYSTEM

Chimney Installation Notes

1.  If possible, install an interior chimney as it will provide better perfor-

mance.  In areas with continuous temperatures below 0°F (-18°C), 

the use of an exterior chimney increases the likelihood of operating 

problems such as low draft, high rate of creosoting, and poor start-up 

characteristics.  Exterior chimneys are also prone to down-drafting 

and flow reversal.  Installations which are located on lower floors in 

the house, such as in a basement, in combination with an outside 

chimney, are especially prone to flow reversal.

2.  The fireplace model WCT6840WS may be installed only with Security 

Chimneys International Ltd  7” diameter chimney systems model 

Secure Temp

®  

S2100+

*

 / Nova Temp

®

  

HT6000

*

 / Secure Temp GX

*

 

(U.S. only) or ACBI

*

.

3. A chimney venting a fireplace shall not vent any other appliance.

4. The minimum chimney height is 12 feet (3.7 m) excluding the fire-

place.

5.  All chimney installations must include at least one support in order to 

be able to take any lateral load.  The maximum chimney length that 

can be supported by the fireplace is nine (9) feet (2.75 m) for Secure 

Temp

 

S2100+

*

 / Nova Temp

 

*

 / Secure Temp

 

GX

*

 and 26 feet 

(8m) for ACBI chimney.  In altitude, add 18” (450 mm) to the chimney 

for every 2,000 feet (600 m) above sea level.

6. The chimney must extend at least three (3) feet (915 mm) above its 

point of contact with the roof and at least two (2) feet (610 mm) higher 

than any wall, roof or building within ten (10) feet (3 m) of it 

(Figure 

20)

.

7. If the chimney extends higher than five (5) feet (1,500 mm) above 

its point of contact with the roof, it must be secured using a roof 

brace.

8. A rain cap must be installed on top of the chimney. Failure to install 

a rain cap may cause corrosion problems.

9. Cut and frame square holes in all floors, ceilings, and roof that the 

chimney will go through to provide a 2” (51mm) clearance between 

the chimney and any combustible materials. At the point of penetration 

through the floors, ceilings or roof, a 1” (25mm) clearance is acceptable 

for AC chimney

*

 only

 (see 

Table 2)

.  Do not fill the required clearance 

spaces with insulation or any other combustible material.

10. Portions of the chimney which may extend through accessible spaces 

must be enclosed to avoid contact with combustible materials or 

damage to the chimney. 

11.When offsets are used, the pipe may not penetrate a ceiling or floor 

unless it is running vertical (no 30° offsets).

CHIMNEY MODEL

*

SqUARE HOLE

SIZE OPENING

Secure Temp

®  

S2100+  Nova Temp

®  

Secure Temp

 

GX

15 in (380 mm)

ACBI: Ceiling, Floor and Roof 

(1” clearance *)

15 in (380 mm)

Wall

17 in (432 mm)

NOTE: See Table 3 for Sloped Roof Framing

Table 2 - Flat Roof Framing

* The following exception has been approved for this appliance; The required 2” 

pipe clearance may be reduced to a 1” clearance at the ceiling, floor and roof 

penetration points for AC chimney

*

 only. All other locations require 2” clearance.

NOTE: 2" clearance to combustibles around chimney components required.

NOTE: Blown or fill type insulation materials must not be in contact with 

the fireplace or in the enclosure frame as described in ‘’Enclosure’’ section.

NOTE: Local codes may not require firestopping at the ceiling levels for 

outside chase installations. However, it is recommended for safety and 

the reduction of heat loss. 

CHIMNEY INSTALLATION INSTRUCTIONS

1.  Cut and frame the holes in the ceiling, floor and roof where the chimney 

will pass (see 

Figure 21).

 Use a plumb-bob to line up the center of 

the holes.  The sizes are indicated in 

Table 2 

 for the floor and ceiling 

holes and 

Table 3 (Page 16)

 for the roof holes.

Figure 20

two (2) feet Min.

three (3) feet Min.

ten (10) feet

*

Available from Security Chimneys™ 

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

14

Содержание WCT6840WS

Страница 1: ...10 and UL 127 Report No 304 7213 EPA Cert No 609 WARNING Hot Do not touch The glass and surfaces of this appliance will be hot during operation and will retain heat for a while after shutting off the appli ance Severe burns may result Carefully supervise children in the same room as appliance If small children are present in the home it is recommended that this appliance be fitted with an adjustab...

Страница 2: ...Neverleavechildrenunattended when there is a fire burning in the fireplace IMPORTANT GENERAL SAFETY PRECAUTIONS READ AND UNDERSTAND THESE SAFETY RULES BEFORE YOUR FIRST FIRE WARNING Never leave your fireplace unat tended while it is burning WARNING THE FIREPLACE MUST BE OPER ATED WITH THE DOORS FULLY OPENEDORDOORSFULLYCLOSED IF THE DOORS ARE LEFT PARTLY OPENED GASANDFLAMEMAYBE DRAWN OUT OF THE FIR...

Страница 3: ...s will void the certification and the warranty of the fireplace and may result in an unsafe installation These appliances are designed to provide supplementalheattotheimmediateareaonly Therefore it is advisable to have an alternate heat source when installed in a dwelling These appliances are not approved for Manufactured Home installations Parts Required Fireplace model WCT6840WS 7 diameterchimne...

Страница 4: ...m For this reason the room should be well ventilated for the first few fires Heat Output TheWCT6840WSfireplaceisthelargestmember of the IHP high efficiency fireplaces The heat generatedfromitsfireismoreefficientlycaptured and distributed In spite of the large amount of heat that the WCT6840WS fireplace can deliver it should not replace the main source of heat in yourhome Thisfireplacewillbringextr...

Страница 5: ...cally go to that level after the fire is fully established and the air boost is closed The unit will burn best with 2 3 pieces of cord wood spaced 1 to 2 inches apart and allowing air to get under the fuel Criss crossing or ar ranging the fuel so that air can get underneath will help the fire to get started easily The unit should be operated with the air control fully open long enough to get the c...

Страница 6: ...ese steps 1 IMPORTANT Close the fireplace door and the combustion air controls this will stifle the fire 2 Alert your family of the possible danger 3 If you require assistance alert your fire department 4 If possible use a dry chemical fire extin guisher baking soda or sand to control the fire Do not use water as it may cause a dangerous steam explosion 5 Ensure that sparks and hot embers com ing ...

Страница 7: ...WS fireplace Replace ment glass should be purchased from a IHP dealer see Replacement Parts on Page 22 DO NOT OPERATE THE UNIT WITH CRACKED OR BROKEN GLASS Glass Cleaning The WCT6840WS fireplace is designed to keep the glass clean under normal operating conditions If the WCT6840WS fireplace is operated continuouslywiththecombustionaircontrolsclosed theglasswilltendto get dirty unless the fuel fire...

Страница 8: ...re important factor affecting the chimney performance To allow a maximum draft and to reduce wind turbulence the chimney must Penetrate the highest part of the roof Be installed as far as possible of roof offsets trees or any other obstructions that may cause wind turbulence and back drafts in the chimney The least amount of offsets elbows possible NOTE A maximum of 2 offsets is allowed NOTE DIAGR...

Страница 9: ...ng and mantel must be in accordance with the stan dards and the following illustrations Figures 10 and 11 A Frame the fireplace using 2 x 3 or heavier lumber B WARNING Combustible materials can not be used in the space directly above the fireplace except for the studs above the facade that support the facing and mantel This area must remain empty for a height of 80 2 032 mm mea sured from the base...

Страница 10: ... spacer minus 1 2 inch for drywall to be flush with the facing 7 Min B G 2 x 3 Min K Combustion Air Kit 1 Combustible material must be installed flush with the fireplace It may not project in front of and on the fireplace i e the steel facade of the fireplace Figure 14 2 Non combustible materials such as brick stone or ceramic tile may project in front of and onto the fireplace facing Figure 12 IM...

Страница 11: ...Brick Fireplace Frame Section Top View Figure 12 Only non combustible material should be superposed or project ing over the front of the fireplace Figure 14 50 Min SEE NOTE MANTEL and FACING The mantel must be installed at least 56 1143 mm above the base of the fireplace Figure 13 Nailing Flanges Four nailing flanges are provided to secure the fireplace to the floor see figure below Bend the naili...

Страница 12: ...th the unit located on the bottom right corner of the fireplace If you wish to adjust the blower speed the variable speed control VRUW provided must be installed in line with the wiring Again use a qualified electrician for installation If the blower requires servicing 1 Remove the doors and decorative facade 2 Remove the screw located below the blower motor that holds it to the back of fireplace ...

Страница 13: ...to ten 10 feet long 4 Adaptor for fireplace connection Outside Air Installation The outside air assembly may be installed according to the following requirements A Duct length should be kept to a minimum The maximum length of a 4 interiordiameter 100mm insulatedflexibleductis20feet 6 1m The duct can be extended to a maximum of 40 feet 12 m using a 6 interior diameter 150 mm insulated flexible duct...

Страница 14: ...osion problems 9 Cut and frame square holes in all floors ceilings and roof that the chimney will go through to provide a 2 51mm clearance between thechimneyandanycombustiblematerials Atthepointofpenetration throughthefloors ceilingsorroof a1 25mm clearanceisacceptable for AC chimney only see Table 2 Do not fill the required clearance spaces with insulation or any other combustible material 10 Por...

Страница 15: ...n place and seal the joint between the roof and the flashing with roofing pitch see Figures 24 and 25 For sloping roofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to the roof using roofing nails 6 Place the storm collar over the flashing and tighten it with the bolt supplied Finally seal the joint between the storm collar and the chimney using si...

Страница 16: ...t be used on the first 15 section 5 m 7 Continue with the regular installation ACBI Chimney 1 Install the first elbow Turn it in the required direction To lock it in place turn 1 8 of a turn Fastenthestrapsattachedtotheelbow to the surrounding frame using nails or drywall screws Figure 27 2 Install the necessary chimney lengths to achievetherequiredoffset Lockthechimney lengths together If penetra...

Страница 17: ... 54 1 8 1375 mm B 17 9 16 446 mm 20 7 16 519 mm 24 5 8 625 mm 28 7 8 733mm 37 3 8 949 mm 42 1067 mm 44 3 4 1137 mm 49 1245 mm 59 9 32 1353 mm 61 3 4 1568 mm Chimney Elbow Offset Height One Length Between Elbows Two Lengths Between Elbows 12 18 36 48 12 48 18 48 36 48 48 48 ACBI 7 15º A 5 1 2 140 mm 7 178 mm 11 1 2 292 mm 14 3 4 375 mm 17 1 2 445 mm 19 483 mm 23 5 8 600 mm 26 3 4 679 mm B 32 1 4 81...

Страница 18: ...ney in a insulated chase Straps Chimney ACBI ACBI Starter Section Straps Outside Wall OFFSET CHIMNEY INSTALLATION WITH WALL PENETRATION Support NOTE This illustration is not to scale It represents how the chimney must be supported A 30 degree offset only is allowed in the USA and a 45 degree maximum offset is allowed in Canada Available from Security Chimneys NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO...

Страница 19: ...ney height exceeds 15 feet 4 6 m Table 6 gives maximum height of supported chimney NOTE For the ACBI chimney a support section ACBI7SL must be used every 30 feet 9m or an universal support every 20 feet 6m instead of the universal roof support ST CHIMNEY MAXIMUM HEIGHT OF SUPPORTED CHIMNEY 7 Diameter Offset Support Roof Support Secure TempS2100 Nova Temp HT6000 Secure Temp GX 16 feet 5 49 m 18 fee...

Страница 20: ...chimney 2 In the middle of the oval drill a hole in the masonry chimney at 30º 3 Increase the size of the hole until a 30º Tubinox liner elbow can be easily slipped through 4 Slide the liner down from the top of the masonry chimney until you reach the hole level 5 Slip through the hole a 30º liner elbow and connect it to the liner 6 Add a small liner section to the liner elbow which will allow the...

Страница 21: ...B26ZE90 H8948 Elbow 45º 8 dia 7B26ZE45 H8949 Telescopic length 8 dia 15 to 26 7B26ZLA H8950 Adjustable length 8 dia 2 5 7B26ZL2A H8951 Length two 2 feet 8KL2 H8954 Length one 1 feet 8KL1 H8953 Wall radiation shield 8 I D 7B26ZR H8952 Optional installation accessories Fireplace Kits Description Cat Part No Rigid firescreen BTZN BTZN Central Forced Air Kit Accessories u Central Forced Air Kit Centra...

Страница 22: ...CMEFBK Decorative Screw Caps Brushed Nickel 2 PR SACMEFBN Timer PR SR2425 Ceramic Glass Left PR SR2356G Ceramic Glass Right PR SR2356D Secondary Air Tube 4 PR SR2379 Log Retainers 2 PR B2CH Around the Glass Gasket 61 3 4 PR SR1685C On the Door Frame Gasket 48 3 8 PR SR1823I Between the Doors Gasket 17 5 8 PR SR1823J Door Radiation Shield Kit PR SR2401KIT Touch up Paint Aerosol Black Metallic H8159...

Страница 23: ...7XRSMI30 7XRSMI30 Wall Band XBM XBM Fireplace Model WCT6840WS Approved Venting Components manu factured by Security Chimneys International only 7 diameter chimney ACBI air cooled Secure Temp GX U S only and Secure Temp S 2100 or Nova Temp HT6000 7 diameter chimney for relining masonry chimneys Tubinox chimney or Projet SS 7 diameter with adaptor for installation in a masonry chimney NOTES j Nova T...

Страница 24: ...M at 2100º F Description Cat Part No 6 Length 7 Dia 7LL6 7LL6 12 Length 7 Dia 7LL12 7LL12 24 Length 7 Dia 7LL24 7LL24 36 Length 7 Dia 7LL36 7LL36 48 Length 7 Dia 7LL48 7LL48 Adjustable Length 7 to 11 7 Dia 7L7A 7L7A Split Base Tee 7 Dia 7LT 7LT Tee Cap 7 Dia 7TCS 7TCS Twist Lock Tee Cap 7 Dia 7LTC 7LTC Elbow 30º 7 Dia 7LE30 7LE30 Elbow 45º 7 Dia 7LE45 7LE45 Elbow 90º 7 Dia 7LE90 7LE90 Rain Termina...

Страница 25: ... normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burning characteristics including but not limited to fuel such as driftwood coal or plywood and wood products using a binder may burn at excessive temperatures and may cause damage to the Product or may ca...

Страница 26: ...e 22 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the appliance 2 The serial number of the appliance 3 The part number 4 The description ...